HomeMy WebLinkAboutFIELD WITHDRAWL RESISTANCE TEST RESULTS DECK Bote: TESTING APPLICATION STANDARD (TAS) 105-98 APPENDIX Ap "Ir FIELD WITHDRAWAL RESISTANCE TEST RESULTS REPORT 4875 Park Ridge Blvd., Suite 108 • Boynton Beach, Florida 33426 • (561) 734-3818 (Phone) • sduhon®dreroofconsulting.com SERVING FLORIDA AND BEYOND . INFORMATION: Job Name: Foxx Residence Project Number: 18-2164.00 Job Address: 403 N 40th St. Pierce, FL 34947 Contact Individual at job site (if any): Area Tested: Deck B Date Tested: 9/20/2018 Report Number: 2 AGENCY/EQUIPMENT INFORMATION: The undersigned acknowledges that all testing has been conducted and results have been reported in compliance with TAS 105 or TAS 105 Appendix A Testing Agency Name: Duhon's Roof Consulting, LLC - FBPE CA#: 32207, NOA# 18-0801.02 Address: 4875 Park Ridge Blvd., # 108 Boynton Beach, Florida 33426 Telephone: 561-734-3818 Fax: N/A Technician: Erich Velzy Certified By: Hector Vergara, FL P.E. License #25764 Signature & Date: Test Apparatus (Gen') Description): Force Measurement System DMD PTI000 105-11 Page 1 C L II ' /ROOF SYSTEM INFORMATION: Roof Area Height: Roof Area Dimensions: deck height (ft) largest dimension (ft) second largest dimension (ft) total roof area squares perimeter width perimeter area (see RAS 117) Area No. .Deck B 47 18 Roof Submittal (if known): Miami -Dade NOA No. Page No. of ASTENER INSTALLATION INFORMATION: Is the fastener a self driller? Yes X No If yes, list the type of tool used for fastener installation: Dewalt 20V Max Speed of Tool: 0-2000/min rpm's 'EST INFORMATION: Number of Tests Conducted: n = 10 • 10 tests for the first 10,000 sf + 3 test for each additional 5,000 sf. • Multiply by 125% for lightweight concrete. • See Section 8.f of TAS 105 • Note the location of all tests on `Sketch of Roof, attached hereto 'IELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET sea No. Deck B Fastener Type: # 14 HD 'efer to deck dimensions referenced on page 2 Fastener Manufacturer: OMG 'omponent to be secured: Pre -drilled? Insulation X Yes No X Membrane X If yes, Drill bit size: Anchor or Base Sheet Wood blocking Hole Depth: Metal Profiles ee Section 8.o of TAS 105 to determine number of tests (If drill bit is high tolerance, include range in 1/1000" tolerances) AS 105-11 Page 2 723 ft2 7 sqs 4.00 ' 456 ft2 " dia. jil 7 1 7 1 563 (F) I P C l 8 1 8 1 430 (F) I P C ILI 9 1 9 1 415 1 (F) I P I C I 'ATISTICAL ANALYSIS: Mean Failure Load: F = 432.00 lbf Sample Standard Deviation: SF = 117.65 lbf Minimum -Characteristic Resistance Force F' = 407.49 lbf tes: 1. Use of the results herein to determine the required number of fasteners for insulation attachment or an acceptable anchor or base sheet fastener spacing, as outlined in TAS 117, shall utilize the minimum characteristic resistance force (F'), determined in compliance with Section 9.f TAS 105. No margin of safety shall be applied to field withdrawal resistance test results determined in compliance with TAS 105. 2. A safety factor of 2 to 1 shall be applied to all results of laboratory testing. 3. The following pages shall be completed for each roof area and included with all Field Withdrawal Resistance Test Recording Sheets. Notes: Conclusion: This wood deck passed the TAS 105 Fastener Withdrawal Test as per the 2017 Florida Building Code to anchor a new roof. 105-11 Page 3 F AREA NO.: Deck B Building and Parapet Heights below. If no parapet exists, enter "N/A". 105-11 Page 4 G ti ,_ .w,..w�.,r.;.+•..j: � ,, - i _..... _ .. - �' � 1 ._.....,, ��� _.. � A.. �$.w....•....,.....,i' �.a.�......-1-h...... I` acLa....: �- f �� j oC°' - : } ,a»_wrc.,•,, :-: ! .�.1.::> - - -..j - _ ' - -' i ., j � � d. T � ■ /" , asAm 1ti { jf �• jf�-, �_� I - i � �, _ , ,�xT`•� �_.:t•w.;., �: 'f "ate �� _ F � "i"" -ter--�d:.�a.,..�:•;.�; ` �_ jjy . �„�....�� � �-_e.,...�.: - I' - } ......may.•,. �.-..«.J r� _ "11 ..,:ds w-•—....�--�-� y_ ff44„ f_ f - � � t ' # i - P� — µ�� 'L_a,...._._..�i.� - -- °.-_.o..�E.—�.. _ ......._.�....._L.,-u•L.J��C�l`-3 -„I��,.�. } (D -• --3, r ��'�-• " � S_ � - : �...»_,. _..-.�;.� �' r...=�:,'„ss,�..:.,...�..w::*.r.+w...-..-': ��4i�...�.._..: " E � 4 a � � � `0 -. . 41 Y . S '� 3C� 1 ` ( r 3 ( ei d; ;44; } p { `• M ii 1 i 3 t I• r -q I j t ��1�}. r; � � _ w° '.,�^.# :'y - _ ..._.. ��7i S ...�._--J _ ..ui_.�i-'.-"S"""�.:-.e t T�pd}( _- '§ _.r"' IjT ; Wit..^^--�p..."'i."'.."" j`.""'^"i ..r-{ w:..-..ry-.;..;-., r. _ ...,i�;.ei.-.=- (j-n...-.-e _ _' �.•..«.. v..aq..�..m.,.�..� .'�..•_•..,e-. ��� �- ::3Q�•--� ........ !f •.,_;_ � - - !,' , �.:.. I 'Kimball F�lecvo1nic Laboratory, l �[e ROt I�IX��I�IIEBIIINI��P�� Purchase Order # ERICH ,�f"v..ri.. t+, rr.^nf:�'.�.-p--,-:.�,, � r J �'u R'Kc .: �-Y' T `� r 4� ^•a^*. A r'^;�r' ��+}}^.•-'-/^}�}.-�...^r-+ Ny u� y^..�^ r. ^^k-++..-n-=+--, ��E _it 2t� c l ass" fn ii`�uo'ai.f KIMBALL� LECTRONIC LABORATOh Y, INC. DUHON S ROOF CONSULTING,-LLC 8081 W 2 LANE 4875 PARK RIDGE BLVD HIALEAH; FL. 33016 SUITE .108 BOYNTON BEACH FL 33426 Desgn tion: FORCE MEASUREN ENT SYSTEMS Manufacrer: DMD Cal Date: 14-Aug-18 Model Nu i, ber: PT1000 Cal. Due Date: 14-Nov-18 -Part "Nut I ber: PT1000 Cal. Interval: 3 MONTHS RP ge: 0-2000 LBS Received: IN TOLERANCE Calibration Result: PASS Serial -Nu ber: 1702001 Environmental Conditions: 73 DEG F / 40 % RH Custome jI.D.: N/A Performed By: ELIU Cust .,Bar de:. N/A LAGO CuSt. d� pt.: N/A Procedure: SYN55 SpecifcaI�ons: +/- 0.25% F.S. Cal Location: IN-HOUSE This is to certifyr'that the above listed instrument meets or exceeds all specifications as stated in the referenced procedure at the points tested (unless otherwise noted). It has been 'calibrated ��. ing'measurement,standards traceable to the National Institute of Standards and Technology (MIST), or to NIST accepted intrinsic standards of measurement, or derived by the do type of s— alitiration techniques. This calibration is in acpordance with Kimball Electronic Laboratory; Inc Quality Assurance Manual. KELI's Quality system is A2LA Accredit to ISO/iEC-17025:2005.and compliantiwith.MIL-STD-45662A and ANSI/NCSL Z540.3-2006. TORS when applicable are greater than or equal'to 4:1; with expanded uncertaintyu to caicutate the Test: Uncertainty Ratio, with a.coverage,fac►orof•K=2 at a confidence level of approximately-95%,.udtess otherwise noted. Any numbei`of� ctors:may cause.the calibration item toldrift out of calibration before the recommended Interval has expired. THIS'UNIT; 'S,FOUND'TO BE': IN TOLERANCE AT THE TIME OF CALIBRATION. PERFORM D ROUTINE. CAL. NO ADJUSTMENTS REQUIRED 4 Company I.D. Manufacturer Model/PN Description Serial Number Last Cal. Cal. Due Date KIM001 10190 MOREHOUSE INSTRUMENT COMPANY, INC 0. PRECI:31761 G132-101102- 27;Dec=17 31-Dec-18 i This report ni LI- Quality Assurance: ELIU �~ AVIER LAGO 14-Aug-18 1:58:24 PM BALCEIRO 15-Aug-18 8:37:37 P.M not be reproduced, except.in full; unless'permission for the publication of an approved abstract is obtained in writing from, KELI Labs., Inc. Kimball Electronic Laboratory, Inc. - 8081 W. 21st Lane - Hialeah, FL. 33016 Tel: 305-822-5792 - Toll Free: 800-393-1094 - Fax: 305-362-3125 - Web: www.kelilabs.com