TESTING APPLICATION STANDARD (TAS) 105-98
APPENDIX A
FIELD WITHDRAWAL RESISTANCE TEST RESULTS REPORT
4875 Park Ridge Blvd- Suite 108 • Boynton Beach, Florida 33426 • (561) 734-3818 (Phone) • sduhon@dreroofconsulting.com
SERVING FLORIDA AND BEYOND
INFORMATION:
Job Name:
Foxx Residence
Project Number:
18-2164.00
Job Address:
403 N 40th St. Pierce, FL 34947
Contact Individual at job site (if any):
Area Tested:
Deck D
Date Tested:
9/20/2018
Report Number:
4
AGENCY/EQUIPMENT INFORMATION:
The undersigned acknowledges that all testing has been conducted and results have been reported in compliance
with TAS 105 or TAS 105 Appendix
A
Testing Agency Name:
Duhon's Roof Consulting, LLC - FBPE CA#: 32207, NOA# 18-0801.02
Address:
4875 Park Ridge Blvd., # 108
Boynton Beach, Florida 33426
Telephone:
561-734-3818
Fax:
N/A
Technician:
Certified By:
Signature & Date:
V4
Erich Velzy
Hector Vergara, FL P.E. License #25764
Test Apparatus (Gen') Description):
Force Measurement System DMD PT1000
AS 105-11
Page 1
'ILDING/ROOF SYSTEM INFORMATION: Area No. Deck D
Roof Area Height: deck height (ft) 10
Roof Area Dimensions: largest dimension (ft) 40
second largest dimension (ft) 12
total roof area 454 ft2
squares 5 sqs
perimeter width 3.00 '
perimeter area 276 ft2
(see RAS 117)
Roof Submittal (if known): Miami -Dade NOA No.
Page No. of
FASTENER INSTALLATION INFORMATION:
Is the fastener a self driller? Yes X No
If yes, list the type of tool used for fastener installation: Dewalt 20V Max
Speed of Tool: 0-2000/min rpm's
EST INFORMATION:
Number of Tests Conducted: n = 10
• 10 tests for the first 10,000 sf + 3 test for each additional 5,000 sf.
• Multiply by 125% for lightweight concrete.
• See Section 8.f of TAS 105
• Note the location of all tests on `Sketch of Roof', attached hereto
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
krea No. Deck D Fastener Type: # 14 HD
Refer to deck dimensions referenced on page 2 Fastener Manufacturer: OMG
Component to be secured: Pre -drilled?
Insulation X Yes No X
Membrane X If yes, Drill bit size:
Anchor or Base Sheet
Wood blocking Hole Depth:
Metal Profiles
See Section 8.o of TAS 105 to determine number of tests (If drill bit is high tolerance, include range in 1/1000" tolerances)
AS 105-11 Page 2
" dia.
iE�
SAMPLE
NO;
PLAN°IDENTIFIER
INITIAL FAILURE LOAD
.""�^ (Ibtj
"Q"'
:„ d . , r i,�FIELD, PERIM_ET_
+ r " A �
ER OR"CORNER�(cxicle".oue)"` `" "
1
1
391
F
(P)
C
I'I 2
2
324
F
P
(C)
3
3
54
F
(P)
C
4
4
391
F
P
(C)
5
5
343
F
P
(C)
6
6
564
F
(P)
C
III 7
7
408
(F)
P
C
L 8
8
481
(F)
P
C
9
9
118
(F)
P
C
10
10
376
(F)
P
C
STATISTICAL ANALYSIS:
Mean Failure Load: F = 345.00 lbf
Sample Standard Deviation: SF = 153.58 lbf
Minimum -Characteristic Resistance Force F' = 316.99 lbf
Dotes: 1. Use of the results herein to determine the required number of fasteners for insulation attachment or an
acceptable anchor or base sheet fastener spacing, as outlined in TAS 117, shall utilize the minimum
characteristic resistance force (F'), determined in compliance with Section 9.f TAS 105. No margin of
safety shall be applied to field withdrawal resistance test results determined in compliance with TAS 105.
2. A safety factor of 2 to I shall be applied to all results of laboratory testing.
3. The following pages shall be completed for each roof area and included with all Field Withdrawal
Resistance Test Recording Sheets.
Notes:
Conclusion: This wood deck passed the TAS 105 Fastener Withdrawal Test as per the 2017
Florida Building Code to anchor a new roof.
AS 105-11 - Page 3
iC
F AREA NO.: Deck D
Building and Parapet Heights below. If no parapet exists, enter "N/A".
fAS 105-11 Page 4
IC'
+
j
MEW-
p q
_��l.a�,�.�
(1�I
•b........+�
i
,,.'..`.'.��
' �'f
�
;
-1+••
��
�
r �7 -.-it
_ _''� - _
i.. �7
�
, �. �'
j a..n..^...•.r..'
�d
1'
Rfw.... 7 ...ae!. �. � ��/Alti/�
r�
AAA
V
' :. (
i
T. , �� �1•y ''I,
;
_ Y _ _ F+! Yp_
_ y i `^�Tp^"�:�-.....:....
-
�"•' q! "—'��^ . i
� -
#"`, �ii � .:.�.
�
.r _ fie...._.
p
1
-,
T-1
,
3'
A
_@ _'1
LF
kk
33
1
yy
4
�.
i . '
�.�,�.� ai.-�'-'
a.•�.<�..�v.�.-.os•--�'�<.� :._-.:.,.•�.ti.� f ;-.-,v . :�.r�.�.w......
�
- mr.sa�.. �'s� --
�' -{4�1 ' �_......},..,..:
�
99
C,-�tificate of Calibratioia '
# KELC-536047-R -
1.imball lectronic Laboratory, Inc.
4
Purchase Order # ERICH
NOW
;a .�-»''�""-n fr-•�;.r7 �-.,-,.r-,.,��,� .,-*7•;Tr^--. .� : .s^, ��j�, �s .—..,-,
KIMBALL ELECTRONICrLABORATO Y, INC. DUHON S ROOF CONSULTING,-LLC_
8081- W 2 LANE 4875 PARK RIDGE BLVD
HIALEAH FL."33016 SUITE 108
tt4t294835�7371 BOYNTON BEACH FL 33426
Desch )tion: FORCE MEASUREIV ENT SYSTEMS
�' Cal Date: 14-Au 18
Martafao user: DMp g-
Model,Nui ber•: PT1000 Cal. Due Date: 14-Nov-18
Part Nu ber: PT1000 Cal. Interval: 3 MONTHS
Rc' ge: 0-2000 "LBS Received: IN TOLERANCE
Calibration Result: PASS
Serial:Nu m ber. 1702001 Environmental Conditions: 73 DEG F / 40 % RH
Custome ,I.D.: N/A Performed By: ELIU
cust..Bar ode: NIA ! LAGO
bust.. 1 pt.: N/A Procedure: SYN55
Specifca ions: +/- 0.25% F.S. Cal "Location: IN-HOUSE
This is to cer4fj'Urat the above listed instrument meets of exceeds all specifications as stated in the referenced procedure at the points tested (unless otherwise noted). it has
been "calibrot f using measureme6t,-standards traceable to the National.lnstitute of Standards. and Technology (NISI), or to NISI acceptedintrinsic standards of measurement, or
derived by the do type;of"self calibration techniques. This calibration Is in accordance with Kimball Electronic Laboratory; Inc Quality Assurance Manual: KELI's Quality system is
A2I A Accredit to ISOII f 17D25 2005 and compliant, vith MIL-STD-45662A and ANSVNCSL Z540.3-2006. TORS when applicable;are greater than or equal'to 4:1; with expanded
uncertainty-u d "to calculate the Test Uncertainty Ratio'Iwith a coverage factor of"K=2 at a confidence level of approximately 95%,.unless biherwise noted.
Any numbdf of actors may cause the.calibration "item to drift out of calibration before the recommended Interval has expired.
THIS `UNITjWAS--FQUND-TO`BE .JN TOLERANCE AT THE TIME OF CALIBRATION,
PERFORM D ROUTINE.CAL. NO ADJUSTMENTS REQUIRED
. _..
11
Company
._ .. . ..
I.D.
_., . ,,.. - -I .
Manufacturer Model/PN Description Serial_Number
Last Cal.
Cal. Due Date
KIM001
i
10100
MOREHOUSE INSTRUMENT COMPANY, INC 0. PRECI,c3176 / GB2-101102-
27 Dec 17
31-Dec-18
`Tec nician: �' Quality Assurance:
ELIU JAVIER
I
LAGO 14-Aug-18 1:58:24 PD1 SALCEIRO 15-Aug-18 8:37:37 Ali
This report rry not be reproduced, except.in full, unless'permission for the publication of an approved abstract is obtained in writing from KELI Labs., Inc.
Kimball Electronic Laboratory, Inc. - 8081 W. 21 st Lane - Hialeah, FL. 33016
Tel:"305-822-5792 - Toll Free: 800-393-1094 - Fax: 305-362-3125 - Web: www.kelilabs.com
j 1