HomeMy WebLinkAboutHVAC - LOAD CALCULATIONSRenar Homes Cayman 1763 Lot 58.Rainwood Court
HVAC Load Calculations
for
Renar Homes SCANNED
BY
St Lucie County
_ * i
HVAC LAD$
Prepared By:
Preferred Air Conditioning & Mechanical
1643 Donna Road
West Palm Beach, FI. 33409
561-689-1093
Thursday, August 23, 2018
RhvaOs an ACCA approved Manual J and Manual D computer program.
Calcul tions are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvac Residential 8� Light Commercial HYAC Loads, Elite Software Development, Inca,
Renar Homes Cayman 1763 Lot 58 Court
Preferr d Air Gonditiornng & Mech ; .Rainw
Pa e 2
1GVesiRalm Beach .FL33409, <,
f' o oct Report
4 F
Project Title: Renar Homes Cayman 1763 Lot 58 Rainwood Court
Desig led By: Preferred Air Cinditioning & Mechanical
Proje t Date: 08-23-2018
Client lame: Renar Homes
Company Name: Preferred Air Conditioning & Mechanical
Comp ny Address: 1643 Donna Road
Comp ny City: West Palm Beach, FI. 33409
Comp ny Phone: 561-689-1093
Comp ny E-Mail Address:
Comp ny Website GETCOLD NET
DA� A 'J �(t.:. '�i'. ski.-,� j. .ko ?.a.L {.x,A ..b; �,L�sx.G»a .60 <. ., �'k _.'v_ 44+. ..a- .�,- - .., r.. >.,.,. .. .,r ...:,.<.. F. .✓ :' .. .
Refer 'rice City: Fort Pierce, Florida
Building Orientation: Front door faces East
Daily Temperature Range: Medium
Latitude: 27 Degrees
Eleva�'on: 25 ft.
Altitude Factor: 0.999
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum D[y Bulb Difference
Winte 42 39.4 n/a n/a 70 n/a
Sum er: 90 78 59% 50% 75 61
CFeckFi
�_
"ores.... ` w:.
Total
Squard
uilding Supply CFM: 1,048 CFM Per Square ft.: 0.648
ft. of Room Area: 1,618 Square ft. Per Ton: 586
Volume
(ft.) 12,94
LB.ulltllrt
Total eating Required Including Ventilation Air. 38,561 Btuh 38.561 MBH
Total ensible Gain: 25,762 Btuh 78 %
Total Latent Gain: 7,378 Btuh 22 %
Total ooling Required Including Ventilation Air: 33,140 Btuh 2.76 Tons (Based On Sensible + Latent)
„ •
� 3� � ax � � h A ,� 4 , x � z,' . mac„ e+� x ''' � r°> , F
Rhva
Calcul
,iris an ACCA approved Manual J and Manual D computer program.
tions are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All co
Be sur
'puted results are estimates as building use and weather may vary.
to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your
designs
conditions.
i
C:\ ...\R NAR CAYMAN 1763.rh9 Thursday, August 23, 2018, 1:12 PM
Rhva
Frefeed
ential;:8 Light;Ccmmerciai HVAC Loatls r "Elite Software Develop
Residment, Inc:
Ain Conditiornng Renar Homes Cayman 1763 Lot Ramwood Court
58,'
VUestbalin':Be
.,.."'Pace3
ac33409'=�:.°"
hFLi
Tdtal
Building Summary Loads
Com
onent g s k z l Y s { Area 77,7A, n Lat Sen Total '
y .:.
m �.Gain-.
i 78 0 3,221 3,221
RENAR SGH: Glazing-RENAR SINGLE HUNG, u-value 55.5 1,6
11�08, SHGC 0.49
RE N ��R FIXED: Glazing -FIXED .47 / .24, u-value 0.47, 13.2 174 0 160 160
S,� C 0.24
REN i R SGD: Glazing-SGD .61 / .23, u-value 0.61, 52.8 902 0 739 739
S1 GC 0.23
REN R-SGH: Glazing-RENAR SINGLE HUNG, u-value 30 454 0 400 400
0 �54, SHGC 0.25
7A-3: Glazing -Glass or plastic block, narrow ribs or flutes, 13.2 222 0 480 480
fi I erglass screen, no coating, u-value 0.6, SHGC 0.33
11 P: )oor-Metal - Polyurethane Core 19.8 161 0 149 149
11 D:boor-Wood - Solid Core 17.2 187 0 174 174
13A- ocb: Wall -Block, board insulation only, R-4 board 49 203 0 111 111
i 1sulation, open core, brick finish
R-4.2" Wall -Custom, STUCCO BLOCK R4.2 DRYWALL 1093.5 17,881 0 11,112 11,112
12C-Qbw: Wall -Frame, R-13 insulation in 2 x 4 stud 174.8 445 0 191 191
civity, no board insulation, brick finish, wood studs
1613- 0: Roof/Ceiling-Under Attic with Insulation on Attic 1582 1,418 0 2,532 2,532
F�oor (also use for Knee Walls and Partition
f�eilings), Vented Attic, No Radiant Barrier, Dark
Shingles or Dark Metal, Tar and Gravel or
2sphalt
embrane, R-30 insulation
16A-�0: Roof/Ceiling-Under Attic with Insulation on Attic 36 32 0 81 81
F oor (also use for Knee Walls and Partition
eilings), Unvented Attic, No Radiant Barrier, Any
F oofing Material, Any Roof Color, R-30 insulation
22A-1�h: Floor -Slab on grade, No edge insulation, no 188 7,147 0 0 0
inIsulation below floor, any floor cover, passive, heavy
n foist soil
Sub
otals for structure: 30,904 0 19,350 19,350
Peo
le: 2 400 460 860
Equi
ment: 0 0 0
Ligh
ing: 1 3 3
Duct
ork: 3,041 752 1,973 2,725
Infiltiation:
Winter CFM: 0, Summer CFM: 0 0 0 0 0
Ventilation:
Winter CFM: 150, Summer CFM: 150 4,616 6,226 2,473 8,698
AED,Excursion:
..............._..
0 0 1,503 1,503
___._____.___............._._........._..._...._........_._......_...__......_..�._.--------.................._......._.._..._..........._._............._.._........_........._........._..._....._.._..._.. --_......__...._...__....-...._............ -......................................... _.........__....._...................
Tota
Building Load Totals: 38,561 7,378 25,762 33,140
Ch'edkyFi
ufes . ,K .•->�.�s.> ..:. a= a F r ._.. -v �:,.. <..0 . ?fir. -.e+-
Total
Building Supply CFM: 1,048 CFM Per Square ft.: 0.648
Square
ft. of Room Area: 1,618 Square -ft. Per Ton: 586
Volume
(ft3): 12,944
Tot:
Heating Required Including Ventilation Air: 38,561 Btuh 38.561 MBH
Tot a
Sensible Gain: 25,762 Btuh 78 %
Tota
Latent Gain: 7,378 Btuh 22 %
Total
Cooling Required Including Ventilation Air: 33,140 Btuh 2.76 Tons (Based On Sensible + Latent)
.Note'
, _ ....._
Rhv1lations
c is an ACCA approved Manual J and Manual D computer program.
Calc
are performed per ACCA Manual J 8th Edition, Version and ACCA M
Manual D.
All c
mputed results are estimates as building use and weather may vary.
Be s
re to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your
design
conditions.
I
C:\ ...RENAR CAYMAN 1763.rh9 Thursday, August 23, 2018, 1:12 PM
h
Rhva
Preferred
I Residential 8Light Commercial HYAC Loads Ehte Software Development,.lnc.
Wr;Conddiotimg & Mech Renar Homes Cayman 1768 Lot 58'Rainwood Court
West
P,aln ` each Page 4
Sy4"tent
I Room Load Summary
fitg6 a mink °,Run z Runs Clg
s
�+ S11,
11"IRoomz°�, Arear Sesr`Hfig� Dl�dt sryDuct t k r nsLat Clg Sys
<tE�v _CFM`':
r y SFkyBtuf�s}GFMIVeF,w hw. "Btub CFM .
---Zo
ie 1---
1
Bath 2 55 683 9 217 416 0 19 19
2
Bedroom 3 168 7,907 103 565 5,485 0 250 250
31Foyer
42 927 12 320 614 0 28 28
4
Great Room 462 1,520 20 638 1,224 0 56 56
5
'Dining Room 96 3,836 50 534 2,305 0 105 105
6
Kitchen 120 1,968 26 609 1,169 0 53 53
7
Laundry 50 2,155 28 476 912 0 41 41
8
Bedroom 2 130 2,714 35 510 2,202 0 100 100
9
Wic 1 36 2,255 29 641 1,229 0 56 56
10
li Master Bedroom 195 5,333 69 476 3,656 400 166 166
11
Master Bath 121 2,160 28 556 1,667 0 76 76
12
Bedroom 4 �_ 143 2,404_ 31 _ 500 2,159 ^_ 0 _ 98 _ 98
^
Ventilation 4,616 2,473 6,226
Duct Latent 657
Return Duct 84 250 95
.-_-----......__._ ___. _._._.._..__.____._.__......_.____.._______---....._._..._...._._...__..._....-_........
_..__.
_
_._....._._.-.___.__.
System 1 total 1,618 38,561 _ 440 �- 25,762 7,378 .1,048 1,048
Sys t
m 1 Main Trunk Size: 12x16 in.
Velo
ity: 786 ft./min
Loss
per 100 ft.: 0.092 in.wg
/1 ^I
S';stem�rSumina �
-_
k: rGoo[Ing�� 5enstl�ie tent�� ��Seraslbhe Latent,
kl f,V 5 i
`£J�Tons�� S ltt �8tuh
Total:
B#uh;
a.
.�,<x...
Net
Required: 2.76 78% / 22% 25,762 7,378 33,140
Actu
1: 2.85 75% / 25% 25,650 8,550 34,200
E ui
t
menfi�Data �
T e`
Heating System Cooling System
Air Source Heat Pump Air Source Heat Pump
Mod'
I: CH14NB036*0**B* CH14NB036*0**B*
Indo
r Model: FB4CNP042L
Brand:
CARRIER AIR CONDITIONING CARRIER AIR CONDITIONING
Description:
Air Source Heat Pump Air Source Heat Pump
Effic'ency:
8.2 HSPF 14.5 SEER
Sound:
0 0
Cap
city: 33800 Btuh 34200 Btuh
Sen
Bible Capacity: n/a 25,650 Btuh
Latest
Capacity: n/a 8,550 Btuh
AH �I
Reference No.: n/a 9162515
This
equipment was selected in accordance with ACCA Manual S.
Man
isystem's
S equipment sizing data: SODB: 90F, SOWB: 78F, WODB: 42F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen. gain:
25,7
gal
12 Btuh, Lat. gain: 7,378 Btuh, Sen. loss: 38,561 Btuh, Entering clg. coil DB: 77AF, Entering clg. coil WB: 65.2F,
Ente
ing htg. coil DB: 60.3F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 1048 CFM, Req. htg. airflow: 440 CFM
C:\ ... + ENAR CAYMAN 1763.rh9 Thursday, August 23, 2018, 1:12 PM