HomeMy WebLinkAboutEVALUATION REPORT - METAL ROOFINGEVALUATION REPORT OF UNION CORRUGATING COMPANY `26 GA. 5V PANEL' FLORIDA BUILDING CODE 6TH EDITION (2017) FLORIDA PRODUCT APPROVAL FL 20484.1-111 ROOFING METAL ROOFING Prepared For: Union Corrugating Company 701 S. King St. Fayetteville, NC 28301 Telephone: (910) 483-0479 Fax: (910) 483-1091 Prepared By: Bala Sockalingam, Ph.D., P.E. Florida Professional Engineer #62240 1216 N Lansing Ave., Suite C Tulsa, OK 74106 Telephone: (918) 492-5992 FAX: (866) 366-1543 . This report consists of Evaluation Report (3 Pages including cover) Installation Details (1 Page) Load Span Table (1 Page) Report No. C2175-1 Date: 8.23.2017 $QANtVED at Lucie County, i FL 20484.1-R1 C2175-1 8.23.2017 Page 2 of 3 'Manufacturer: Union Corrugating Company (Product Name: 5V Panel {Panel Description: 24" wide coverage with (5) 1/2" high ribs Materials: Minimum 26 ga., 80 ksi steel: Galvanized coated steel (ASTM A653) or Galvalume coated steel (ASTM A792) or painted steel (ASTM A755). Deck Description: Min. 15/32" thick APA rated plywood or min. V thick wood plank (min SG of 0.42) for new and existing constructions. Designed by others and installed as per FBC 2017. New Underlayment: Minimum underlayment as per FBC 2017 Section 1507.4.5.1. Required for new construction. Existing Underlayment: One layer of asphalt shingles over one layer of #30 felt. For reroofing (Optional) construction only. Slope: 1/2:12 or greater in accordance with FBC 2017 Section 1507.4.2 Design Uplift Pressure: 71.0 psf @ fastener spacing of 24" o.c. (Factor of Safety = 2) 169.0 psf @ fastener spacing of 6" o.c. Panel Attachment: #10-15 x 2" long wood screw with washer At interior @ max 12" o.c. across panel width through panel rib At panel ends @ max 6" o.c. across panel width through panel flat and rib Test Standards: Roof assembly tested in accordance with UL580-06 `Uplift Resistance of Roof Assemblies' & UL 1897-04 `Uplift Tests for Roof Covering Systems'. Test Equivalency: The test procedures in UL 1897-04 comply with test procedures prescribed in UL 1897-12. Code Compliance: The product described herein has demonstrated compliance with FBC 2017 Section 1507.4. Product Limitations: Design wind loads shall be determined for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress design. The maximum fastener spacing listed herein ' shall not be exceeded. The design pressure for reduced fastener spacing may be computed using rational analysis prepared by a Florida Professional Engineer or based on Union load span table. This evaluation report is FL 20484.1-R1 C2175-1 8.23.2017 Page 3 of 3 not applicable in High Velocity Hurricane Zone. Refer to current NOA for use of this product in High Velocity Hurricane Zone. Fire classification is not within scope of this Evaluation Report. Refer to FBC 2017 Section 1505 and current approved roofing materials directory or ASTM E108AM790 report from an accredited laboratory for fire ratings of this product. Supporting Documents: UL580 & UL1897 Test Reports Farabaugh Engineering and Testing Inc. Project No. T197-16; Reporting Date 5/12/16 PANEL OVER NEW UNDERLAYMENT ROOF PANEL SEE DETAIL 2 SEE DETAIL 1 PANEL FASTENER SPACING PER ALLOWABLE UPLIFT LOAD TABLE u u V EXISTING UNDERLAYMENT EXISTING SHINGLES (OPTIONAL) (OPTIONAL) n I V DECK ATTACHMENT AND PLYWOOD SUPPORTS MUST BE 15/32" THICK (MIN.) DESIGNED AND INSTALLED n u BY OTHERS -NIIIV. LA_ YYUUU mAr ILR/JVI>I/ TRUSS AT MAX. 24" O.C. #10-15 X 2" LONG WOOD SCREW WITH WASHER NEW UNDERLAYMENT DETAIL 1 #10-15 X 2" LONG WOOD SCREW WITH WASHER NEW UNDERLAYMENT —\ EXISTING UNDERLAYMENT V (OPTIONAL) DETAIL 2 TYPICAL PANEL INSTALLATION X-SECTION MIN 26 GA. PANEL ` EXISTING SHINGLES 17 (OPTIONAL) PLYWOOD 15/32" THICK (MIN.) MIN 26 GA. PANEL EXISTING SHINGLES (OPTIONAL) PLYWOOD 15/32" THICK (MIN.) U M CJ N n Z �wrn Q u)0N r,�Zl ZWM Y-m U UI o Z o° 4i d w a IL GENERAL NOTES: 1. ARCHITECTURAL ROOF PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH LO Z �y�� zxa THE FLORIDA BUILDING CODE (FBC). U �� 2. ROOF PANELS SHALL BE MINIMUM 26 GA. EFFECTIVE COVERING WIDTH OF En N PANEL = 24". 3. THE ROOF PANELS SHALL BE INSTALLED OVER SHEATHING & STRUCTURE AS z SPECIFIED ON THIS DRAWING. u 4. REQUIRED DESIGN WIND LOADS SHALL BE DETERMINED FOR EACH PROJECT. THIS PANEL SYSTEM MAY NOT BE INSTALLED WHEN THE REQUIRED DESIGN WIND LOADS ARE GREATER THAN THE ALLOWABLE WIND LOAD TABLE. 5. ALL FASTENERS MUST BE IN ACCORDANCE WITH THIS DRAWING & THE FLORIDA BUILDING CODE. IF A DIFFERENCE OCCURS BETWEEN THE MINIMUM REQUIREMENTS OF THIS DRAWING & THE CODE, THE CODE SHALL CONTROL. 6. RAFTERS/JOISTS/TRUSSES MUST BE DESIGNED TO WITHSTAND WIND LOADS AS REQUIRED FOR EACH APPLICATION AND ARE THE RESPONSIBILITY OF OTHERS. OF UNION CORRUGATING COMPANY 5V Panel, Uplift Loads (Min 26 ga.) Description Fastener Spacing along Panel Length (in) Allowable Uplift Load (psfl Coverage width: 24" Panel Fasteners #10-15 hex head screws with sealed washer Panel fasteners spaced at 12" o.c.,across panel width through ribs. 6 169.0 8 158.1 10 147.2 12 136.3 14 121.7 16 106.5 18 94.7 20 85.2 22 77.5 24 71.0 Notes: 1. The bold numbers indicate design loads calculated from test data with safety factor of 2. 2. Panels must be installed as per Evaluation Report FL 20484.1 and Union current installation procedure. 12 6 N Lansing Ave., Suite.0 Tu a, Ok 74106 91 4925992 oeteeee�are0 �ALINC,q°° O o®•••M. ooe g .•�N S E •'•. o® 4 Q. 0 w co• \lO • w� ® ' 4( • W z. S 4D ey0 m�,S�'••• O, R L O ��,• � ego S 1 e ' ®e Bala Sockalingam, Ph.D., P.E. FL 62240