Re:. Roofing specification prepared.for the St. Lucie County Building Dept. for the structure
located at 8101 Coquina Avenue, Saint Lucie County, Florida
anufacturer: Polyglass USA.
ofiles; Modified Bitumen Roof System, FL #1654-R22
de: FBC 2017; Section 1507
ind Speed: 160 MPH; Ultimate Design Wind Speeds
posure; C
Ban Roof Height: 30' Maximum
;ch: 2/12 Minimum
quired Design Pressure: Zone1: -31.46 Zone 2: -49.61 Zone3: -68.97
Rximum Uplift Pressure: -90 psf
se: SBS-SA (self- adhering)
r Sheet: (Optional) One or more SBS-SA, (self -adhering) SBS-TA, APP-TA
p: SBS-SA, APP-SA, SBS-TA, APP-TA
of Decking: Existing 5/8" plywood sheathing to be nailed w/8d x 2" ring shank
@ 6" O.C., thru out zone 1, 4" O.C. perimeter, and 6" O.C. field zone 2,
and 4" O.C. thru out zone 3.
The above approved, as per Florida Building Code Compliance acceptances, 2017 Florida Building Code,
and the Manufacturer's recommendations.
�. ......'