HomeMy WebLinkAboutREVISION - EVALUATION REPORT - UNDERLAYMENTS 11-1-18s-__iVED
'IOCT 3 0 2010 EXTERIOR RESEARCH & DESIGN, I.I.C.
Certificate of Authorization #9503
RINITY f ERD Permitting Iaepartment SCE�� 353 CHRISTIAN STREET, UNIT#13
ucle County � OXFORD, CT 06478
EVALUATION REPORT T �f LucieU c0 (203) 262-9245
Polygla s USA, Inc. Evaluation Report P12060.02.09-R23
150 Lyon DriveF1
FL5259-R27
Fernleyl�1 NV 98408 L0 P� Date of Issuance: 02/24/2009
(570) 3E -1230 FAQt ER5 OR ATl I�CH,°�,E,.� S
ARE THE RESPONSIBILITY OF THE Revision 23: 09/14/2017
SCOPE: CONTRACTOR OR RECORD
This Evaluation Report is issued under Rule 611320-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert. Nieminen, P.E.
for use jof the .product under the Florida Building Code and Florida Building Code, Residential Volume. The products
-described herein have been evaluated for compliance with the Sth Edition (2017) Florida Building Code sections noted
herein. I�
DESCRIP'ON: Polyglass'RoofIII nderlayments
LABELING I' Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CONTINU D COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality 'I�ssurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the
referenced Quality Assurance documentation changes. Trinity IERD requires a complete review of this Evaluation Report
relative o updated Code requirements with each Code Cycle.
ADVERTISIMENT: The Evaluation Report number preceded by the words "TrinitylERD Evaluated" may be displayed in
advertisi' g literature. If any -portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be available for inspection at the job site at the request of the Building Official.
This Eval II ation Report consists of pages 1 through 14,
Prepared
Robert J:
Florida Re.
CERTIFICATI
1. Trinity
distriE
2. Trinity
3. Rober
- which)
4. Rober
by:
The facsimile seal appearing was authorized by Robert Nieminen,
P.E. on 09/14/2017. This does not serve as an electronically
signed document.
N OF INDEPENDENCE:
ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
iting products it evaluates.
ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
Nieminen, P.E. does not have nor will acquire; a financial interest in any company manufacturing or distributing products for
he evaluation reports are being issued.
Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
I
Nieminen, P.E.
ration No. 59166, Florida DCA ANE1983
S. This isla building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
projectlon which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifl pally for that purpose.
c)�
d-1
Sl . LUCIE I0l7fV'i Y gU� NG DIV 0 \
REVIEWEDIFOR MPLIANCEREVIE THESE PLANS AND ALL PROPOSED WORK
DATE Y ARE SUBJECT TO ANY CORRECTIONS
REQUIRED BY FIELD INSPECTORS THAT
PLANS AN ''PER IT MUST BE KEPT O B MAY BE NECESSARY IN ORDER TO
SITE OR NO��i INSPECTIONS) WILL B AIDE C oMpLY WITH ALL APPLICABLE CODES.
ROOFING'tOMPONENT EVALUATION:
II;
1. SCOPE:
2.
3.
F)o
,I TRINITY I ERD
uct Category: Roofing
Category: Underlayment
pliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the
wing sections of the 5ei Edition (2014) Florida Building Code through testing in accordance with the following Standards.
pliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein.
.jectlon
1904.3.1
Property
Standard
Year
Wind Uplift
FM 4474
2011
1§04.3.1
Wind Uplift
UL 1897
2012
1 ,07.2.3 / 1507.1.1
Physical Properties
ASTM D226
2009
1507.2.4 / 1507.1.1, 1507.2.9:2
Physical Properties
ASTM D1970
2015
175107.3.3
Physical Properties
FRSA/TRI April 2012
2012
1507.11.2
Physical Properties
ASTM D6164
2011
1 07.11.2
Physical Properties
ASTM D6222
2011
1123.6.5.2.1
Physical Properties
TAS 103
1995
TAS no
Accelerated Weathering
TAS 110
2000
Examination
Reference
Date
Approvals (TST 1867)
Wind Uplift
3004091
01/12/2000
(TST 5878)
Physical Properties
PRIO1111
04/08/2002
(TST 5878)
Physical Properties
PUSA-005-02-01
01/31/2002
(TST 5878)
Physical Properties
PUSA-013-02-01
12/23/2002
(TST 5878)
Physical Properties
PUSA-013-02-02
12/23/2002
(TST 5878)
Physical Properties
PUSA-013-02-03
12/23/2002
(TST 5878)
Physical Properties
PUSA-018-02-01
07/14/2003
(TST 5878)
Physical Properties
PUSA-028-02-01
07/13/2005
(TST 5878)
Physical Properties
PUSA-033-02-01
01/12/2006
(TST 5878)
Physical Properties
PUSA-035-02-01
09/29/2006
(TST 5878)
Physical Properties
PUSA-055-02-02
12/10/2007
(TST 5878)
Physical Properties
PUSA-061-02-02
01/28/2008
(TST 5878)
Physical Properties
PUSA-076-02-01
02/22/2008
(TST 5878)
Physical Properties
PUSA-083-02-01
04/14/2008
(TST 5878)
Physical Properties
PUSA-088-02-01
07/29/2009
(TST 2508)
Physical Properties
JX201-17A
04/01/2008
(TST 2508)
Physical Properties
RX14E8A
01/29/2009
(TST 6049)
Physical Properties
11752.09.99-1
02/08/2000
(TST 6049)
Wind Uplift
11757.08.01-1
08/13/2001
(TST 6049)
Wind Uplift
11776.06.02
01/16/2003
(TST 6049)
Physical Properties
02200.07.03
07/14/2003
(TST 6049)
Wind Uplift
P1740.01.07
01/04/2007
(TST 6049)
Physical Properties
P5110.04.07-1
04/11/2007
(TST 6049)
Wind Uplift
P9260.03.08
03/21/2008
(TST 6049)
Physical Properties
P13450.08.09
08/13/2009
(TST 6049)
(TST 6049)
Wind Uplift
Physical Properties
P30540.11.09-111
11/30/2009
P11030.11.09-1
11/30/2009
(TST 6049)
Wind Uplift
P11030.11.09-2
11/30/2009
,(TST 60491,
!(TST 6049)
Physical Properties
P11030.11.09-3
11/30/2009
(TST 6049)
Physical Properties
P33360.06.10
06/25/2010
Physical Properties
P33370.03.11
03/02/2011
(TST 6049)
Physical Properties
P33370.04.11
04/26/2011
(TST 6049)
Physical Properties
P37300.10.11
10/19/2011
tesearch and Design, LLC.
of Authorization #9503
6n' EDITION (2017) FBC NON-HVHZ EVALUATION
Evaluation Report P12060.02.09-R23
Polyglass Roof Underlayments; (570) 384-1230
FL5259 R27
Revision 23: 09/14/2017
Page 2 of 14
4.
",4TRININIERD
r'�C
Examination
Reference
Date
) (TST 6049)
Physical Properties
P40390.08.12-1
08/06/2012
) (TST 6049)
Physical Properties
P40390.08.12-2
08/07/2012
) (TST 6049)
Physical Properties
C41420.09.12-3
09/11/2012
) (TST 6049)
Wind Uplift
P39680.03.13
03/04/2013
) (TST 6049)
Physical Properties
P45370.04.13
04/26/2013
) (TST 6049)
Wind Uplift
P1738.02.07-R2
04/29/2013
) (TST 6049)
Wind Uplift
11757.04.01-1-R1
04/30/2013
) (TST 6049)
Wind Uplift
P41630.08.13
08/06/2013
) (TST 6049)
Wind Uplift
P11751.05.03-Ri
11/26/2013
) (TST 6049)
Wind Uplift
P11781.11.03-R1
11/26/2013
) (TST 6049)
Physical Properties
P45270.05.14
05/12/2014
) (TST 6049)
Physical Properties
6020.07.14-1
09/08/2014
(TST 6049)
Physical Properties
6020.09.14-2
09/08/2014
I (TST 6049)
Physical Properties
6020.09.14-3
09/08/2014
(TST 6049)
Physical Properties
6020.09.14-4
09/08/2014
(TST 6049)
Physical Properties
6020.09.14-5
09/08/2014
(TST 6049)
Physical Properties
6020.09.14-6
09/08/2014
f (TST 6049)
Physical Properties
P46520.10.14
10/03/2014
1 (TST 6049)
Physical Properties
P44360.10.14
10/07/2014
i (TST 6049)
Physical Properties
P43290.10.14
10/17/2014
(TST 6049)
Physical Properties
PLYG-SC7550.03.15
03/24/2015
i (TST 6049)
Physical Properties
P40390.04.15
04/03/2015
i (TST 6049)
Physical Properties
PLYG-SC8080.05.15-1
05/20/2015
i (TST 6049)
Wind Uplift
PLYG-SC8905.05.16-1
05/17/2016
i (TST 6049)
Physical Properties
PLYG-SC8080.07.16
07/16/2016
1 (TST 6049)
Wind Uplift
PLYG-SC12025.10.16
10/12/2016
(TST 6049)
Physical Properties
PLYG-SC13040.12.16
12/27/2016
(TST 6049)
Physical Properties
PLYG-SC11900.03.17
03/10/2017
(TST 6049)
Physical Properties
PLYG-SC12115.08.17
08/08/2017
ES (EVL 2396)
IBC Compliance
ESR-1697
11/01/2014
mi-Dade (CER 1592)
HVHZ Compliance
NOA 14-0717.08
01/22/2015
rglass USA
Manufacturing Affidavit
Products Current
02/18/2009
rglass USA
P/L Affidavit
Mule -Hide Cross Ltg
03/01/2008
rglass USA
Materials Affidavit
Polystick SA Compound
08/18/2011
LLC. (QUA9625)
Quality Control
Service Confirmation
Exp.10/05/2018
)DUCT DESCRIPTION:
Fastene&IJ nderlayments;
4.1.1 Elastobase is a fiberglass reinforced, SBS modified bitumen base sheet.
4.1! 2 Elastobase P is a polyester -reinforced, SBS modified bitumen base sheet.
4.13 Polyglass G2 Base is a fiberglass -reinforced, asphaltic base sheet.
Polyglass APP Base is a fiberglass -reinforced, APP modified bitumen base sheet.
Polystick MTS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, surfaced
with polyolefinic film surface; meets TAS 103.
4.21,2 Polystick IR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an
I! aggregate surface; meets ASTM D1970.
Exterior esearch and Design, LLC Evaluation Report P12060.02.09-R23
CeKlficat ,of Authorization #9503 em EDITION (2017) FBC NON-HVHz EVALUATION F15259-R27
Polyglass, Roof Underlayments; (570) 384-1230 Revision 23: 09/14/2017
II Page 3 of 14
5.
TI$ rrY I ERD
Polystick TU P is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester
reinforced, with a granular surface; meets ASTM D1970 and TAS 103.
2.5 Polystick TU Max is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/M2 polyester
fabric surface; meets ASTM D1970 and TAS 103.
2.6 Polyflex SAP, Polyflex SAP FIR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FIR) are polyester
reinforced, APP modified bitumen cap sheets; meet FRSA/TRI April 2012.
2.7 Polystick Dual ProTM' is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polyester fabric surface; meets ASTM D1970.
2.8 Polystick Tile Pro' is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polyester fabric surface; meets ASTM D197O and TAS 103.
2.9 Polystick MU-X is a nominal 54-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D197O (See Section
5.8).
4'3 Mechanica_IIy Fastened'and/or Bonded'U'nderlayments:
413.1 Elastoflex G TU is a polyester reinforced, modified bitumen tile underlayment composed of a sand -surfaced SBS
modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU is for use as an
1. alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April
I� 2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet" in the "Two Ply
li System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered the roof systems.
4 II.2 Elastoflex S6 G and Elastoflex S6 G FR are polyester reinforced, SBS modified bitumen cap sheets; meet ASTM D6164.
Elastoflex S6 G and Elastoflex S6 G FIR are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D638O,
Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened the roof systems.
Elastoflex S6 G is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI
April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastoflex S6 G FIR is for use as an
alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath
ii mechanically fastened tile roof systems.
4.3.3 Polyflex G and Polyflex G FIR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222.
Ij Polyflex G is for use as an alternate to Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012
(04-12) beneath mechanically fastened or adhered tile roof systems. Polyflex G FIR is for use as an alternate to Heat
Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile
roof systems.
5.1' This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the Designer of
I1 Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or
design guidance unless retained specifically for that purpose.
5. I! This Evaluation Report is not for use in the HVHZ.
5.3ii Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire
ratings of this product.
5. �I Polyglass Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced
I within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for
approval based on this evaluation combined with supporting data for the prepared roof covering.
Exterior Research and Design, LLC Evaluation Report P12060.02.09-R23
Certifcate li f Authorization #9503 6T" EDITION 12017) FBC NO1N-HVHZ EVALUATION FL5259-R27
Polyglass Roof Underlayments; (570) 384-1230 Revision 23: 09/14/2017
I� Page 4 of 14
- I
I
I,
i
I 'I
I 'I
TRINITYERD
�5 Allowable Roof Covers:
TABLE 1: ROOF COVER OPTIONS
1
-
Waod Shakes
rderlayment
I"
Asphalt Shingles
Nail -On Tile
Foam -On Tile
Metal
Slate
& Shingles
ElaIli
Yes .,
Yes
(Base Sheet In 2-ply system)
Yesstobase
(Base Sheet in 2-piv system)
Yes
Yes
Yes
Ell1 obase P
Yes
Yes
II
Yes
(Base Sheet In 2-ply system)
(Base Sheet in 2-ply system)
Yes
Yes
Yes
P�lyglass G2 Base
No
Yes
Yes
No
I(Base
Sheet in 2-ply system)
(Base Sheet in 2-ply system)
No
No
P 'llyglass APP Base
No
Yes
Yes
No
(Base Sheet in 2-ply system)
(Base Sheet in 2-ply system)
No
No
Polystick
MTS
Yes
Yes
No
Yes
Yes
Yes
Polystick IR-Xe
Yes
No
No
No
Yes
Yes
Polystick TU P
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
(Polystick TU-PIus1
Yes
Yes
Yes (See 5.5.1)
Yes
Yes
Yes
P o,Iystl&TU Max
No
Yes
Yes (See 5.5.1)
Yes
No
No
Polystick Dual Pro
Yes
No
No
Yes
Yes
Yes
Pdlystick Tile Pro
Yes
Yes
Yes (See 5.5.1)
Yes
Yes
Yes
Pglystick MU-X
Yes
No
No
Yes
Yes
Yes
El ,.stoflex S6 G
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
EI stoflex S6 G FR
Yes
Yes
No
No
Yes
Yes
Elastoflex G TU
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Po yflex G
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Polyflex G FR
Yes
Yes
No
No
Yes
Yes
Polyflex SAP or SAP FR
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Mule -Hide SA-APP Cap Sheet
or 5A-APP Cap Sheet (FR)
'UI
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations.
� TABLE
lk ALLOWABLE T LE'ADHESIVU UNDERLAYMENT COMBINATIONS'
_ -
II
Adhesive
Florida Product
Approval
- -
Underlayments
DP1p
Foam Touch `n Seal Storm Bond Roof
Tile'
Adhesive
FL14506
Polystick TU Plus, Polystick TU Max
Do!
ni TileBondT"
FL22525
Polystick TU P, Polystick TU Plus, Polyflex SAP or Tile Pro
I4
Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile.Pro,
ICF
iAdhesives Polyset® AH-160
FL6332
Elastoflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR,
II
Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR)
Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro,
ICF
III
Adhesives Polyset® RTA-1
FL6276
Elastoflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR,
Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR)
Polyglass
PolyLok Roof Tile Adhesive
m
FL17855
Polystick TU Plus orPolystick TU Max
1 Refer "a Me Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
Exterior;(tesearch and Design, LLC. Evaluation Report P12060.02.09-R23
certificatedi f Authorization #9503 6T" EDITION (2017) F13C NON HVHZ EVALUATION FL5259-RZ7
Polyglass Roof Underlayments; (570) 384-1230 Revision 23; 09/14/2017
I�
I, Page 5 of 14
�/ � RWI"jYJERD
Allowable Substrates:
iDirect-Bon tclDeck:
Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet
(FR) self -adhered to:
➢ New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing
plywood; _New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed
Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels
(designed and installed to meet wind loads for project).
lwac. ruryyruoatuut� uvi±R' u9 itelprming rrnew(orexist 9;jd!yw.00d(or40SB s e tof 74:�{I�ew or existing�,plywo- od ocl .
si sheafhing should be cleaned oftallitlirfcand ebrisfprior to ap_plication�of,Po[ystic'k membranes.
Elastoflex G TU; Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: .
➢ ASTM D41 primed structural concrete.
i
Polyflex G or Polyflex G FR torch -applied to:
➢ ASTM D41 primed structural concrete.
5; I.2 Bond -to -Insulation:
Polystick (all variations); Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered
to:
➢ ASTM C1289 Type II Class 1 of Isoc anurate or Type V of isoc anurate-com -composite insulation, � Yp � p Y Y Yp P Y Y p insulation; Dens Deck
DuraGuard; Dens Deck Prime; or SECUROCK Gypsum -Fiber Roof Board.
Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to:
➢ Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
it II Polyflex G or Polyflex G FR torch -applied to:
➢ ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum
II requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile
systems, insulation attachment shall be designed by a qualified design professional and installed based on testing of
the insulation/underlayment system in accordance with FBC Section 1504.3.1.
5: IL3 Bond to Mechanically Attached Base Laver:
Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or
Tile Pro self -adhered to:
➢ ASTM D226, Type l or II felt; Elastobase; Elastobase P or Mule -Hide Nail Base.
Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to:
j! ➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base.
�i Polyflex G or Polyflex G FR torch -applied to:
➢ Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum
codified requirements. For installations under foam -on the systems, base layer shall be attached per minimum
requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in
accordance with FBC Section 1504.3.1.
search and Design, U.C. Evaluation Report P12060.02.09-R23
Authorization #9503 6T" EDMON (2017) FBC NON-H VHZ EVALUATION F.L5259-1127
Polyglass Roof Underlayments; IWO) 384-1230 Revision 23: 09/14/2017
Page 6 of 14
#81,
�I 1 RINI7Y I ERD
Wind Resistance for Underlayment Systems in Foam -On Tile Applications:. FRSA/TRI April 2012 (04-12) does not
address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment
forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not
addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure is the
result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure
divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-
12), Appendix A, Table 1A or FBC 1609 for determination of design wind loads.
Maximum Design Pressure = -90 Dsf:
Deck:, Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: None
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP. Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
Maximum Design Pressure = -97 5 Dsf•
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: PG100orASTM D41
'Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet,(FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x
1'/<" ring shank nails through 32 ga.,1-5/8" diameter tin caps spaced 12-inch o.c.
Maximum Design Pressure = -105 osf•
:Deck: Min.15/32-inch plywood to meet project requirements: to satisfaction of Authority Having Jurisdiction.
Primer: WB-3000
Underlayment: Polystick TU P, Polystick TU Plus,Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x
1'/<" ring shank nails through 32 ga.,1-5/8" diameter tin caps spaced 12-inch o.c.
Maximum Design Pressure = -135 Dsf:
Deck:. Min.15/32-inch plywood to meet.projectrequirements to satisfaction of Authority Having Jurisdiction.
Primer: (Optional) PG100 or ASTM D41
Joints: Min. 4-inch wide strips of Elastoflex SA-V over all plywood joints.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule-Hide,SA-APP Cap Sheet (FR), self -adhered.
Maximum Design .Pressure = -315 Dsf:
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: PG100 or ASTM D41
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Tile Pro; Polyflex SAP, Polyflex SAP-FR, Mule -Hide SA-APP Cap
Sheet and Mule -Hide SA=APP Cap Sheet (FR), self -adhered.
Maximum Design Pressure = -622 5 Dsf:
Deck: Structural concrete to, meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: PG100 or ASTM D41
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
Maximum Design. Pressure = -30 0 Dsf*:
Deck: Min.15/32-inch OSB to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: 11 ga. x 1.25-inch long x 1-inch head diameter round metal cap nails
Spacing: 6-inch o.c. at the 3-inch wide side laps and 6-Inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet.(FR), self -adhered.
Maximum Design Pressure = -37 5 Dsf*:
Deck: Min.15/32-inch plywood to meet -project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: 11.ga. x 1.25-inch long x 1-inch head diameter round metal cap nails
Spacing; 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered'.
Exterior I tesearch and Design, LLG Evaluation Report P12060.02.09-R23
Certificate Authorization f Authorization 1t9503 6'N EDITION (2017) FBC NON-HVHZ EVAWAIR019 FL5259 R27
Polyglass Roof Underlayments; (570) 384-1230 Revision 23: 09/14/2017
Page 7 of 14
�( 1 ItINITi I ERD
19 Maximum Design Pressure = -373-Dsf*:
Deck: Min.19/32-inch plywood•to meet project requirements to satisfaction of Authority Having. Jurisdiction.
i Base Sheet: One (1) or two (2) layers ASTM D226, Type II felt
Fasteners: 11 ga. x 1.25-inch long x 1-inch head diameter round metal cap nails
Spacing: 6-inch o.c. at the 3-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt.
10 Maximum Design Pressure = -45 Dsf*:
Deck:. - Min.19/32-inch plywood to meet.project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: One (1) layer ASTM D226, Type II'felt
Fasteners: 11 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
Spacing: 4-Inch o.c. at the 2-inch wide side laps and 4-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP. Cap Sheet.and
Mule -Hide SA-APP Cap Sheet. (FR), self -adhered or Elastoflex G TU, applied in.full.mopping of hot asphalt.
1 Maximum Design Pressure = -45 Dsf*:
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Two (2) layers ASTM D226, Type IGfelt
Fasteners:' 11 ga. x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
Spacing: 9-inch o.c. at the 2-inch wide side laps and-9-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex.SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap. Sheet 'and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot
asphalt.
2 _Maximum Design Pressure = -45 Dsf:
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap.or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 9-inch o:c. at the 2-inch wide side laps and 18-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
3 Maximum Design Pressure = -52 5 Dsf:
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 9-inch o.c. at the 2-inch wide side laps and 12-inch o.c. at two (2) equally spaced. staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch=appiled.
L Maximum Design Pressure = -52 5 Dsf:
Deck: Min. 15/.32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet. Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: Simplex Original Cap Nails
Spacing: 6-inch o.c, at the 3-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
L Maximum Design Pressure = -52 5 Dsf:
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex Original Cap Nails
Spacing: 6-inch o.c. at the 3-inch wide side.laps and 6-inch o.c, at four (4) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
Exterior
Maximum Design Pressure = -60 Dsf:
Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet:. Elastobase (sanded top surface for hot -asphalt or torch:applied cap.or poly -film surface for torch-applied.cap)
Fasteners: 11 ga. x 1.25-inch long x 3/8-inch head.diameter annular ring -shank roofing nails at 1-5/8-inch diameter tin caps
Spacing: 8-inch o.c. at the 4-inch wide side laps and 8-inch o.c. at three (3).equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex56 G, applied 'infull mopping of hot asphalt or Polyflex G, torch -applied.
search and Design, U.C. Evaluation Report P12060.02.09-R23
Authorization #9503 EDITION (2U7) F13C NON4111VH2 EVALUATION F11.5259-11127
Polyglass Roof Underlayments; (570)�384-1230 . Revision 23: 09/14/3017
Page 8 of 14
no
,l :I RINITi I ERD
Maximum Design Pressure = -60 Dsf:
Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: OMG #12 Standard Roofgrip with OMG Flat Bottom Metal Plates
Spacing: 12-inch o.c. at the 4-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
Maximum Design Pressure = -67 5 Dsf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment)
Fasteners: 12 ga. x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
Spacing: 8-inch o.c. at the 4-inch wide side laps and 8-inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
Maximum Design Pressure = -75 Dsf:
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment)
Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with
OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAXX Cap
Fasteners
Spacing: 10-inch o.c. at the 4-inch wide side laps and 10-inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
Maximum Design Pressure = -90 Dsf:
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 6-inch o.c. at the 2-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
Maximum Design Pressure = -90 Dsf:
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with CMG 3" Round Metal Plates or OMG Flat Bottom Metal
Plates
Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
Maximum Design Pressure = -90 Dsf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface)
Fasteners: Trufast #12 DP or Trufast #14 HD with Trufast 3 Metal Insulation Plates
Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt.
Maximum Design Pressure = -90 Dsf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base. Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment)
Fasteners: Dekfast #14 with Dekfast Hex plates, CMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with
OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAXX Cap
Fasteners
Spacing: 9-inch o.c. at the 4-inch wide side laps and 9-inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Elastoflex G'TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
search and Design, LLC. Evaluation Report P12060.02.09-R23
Authorization #9503 EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-RZ7
Polyglass Roof Underlayments; (570) 384-1230 Revision 23: 09/14/2017
Page 9 of 14
O
TRINITY I ERD
iZ4 Maximum Design Pressure =-97 5 psf:
II Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
i
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: 11 ga. x 1.25-inch x 3/8-inch head.diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
Spacing: 4-inch o.c. at the 4-inch wide side laps and 4-inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
fi' S Maximum Design Pressure = -105 psf:
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 6-inch o.c. at the 2-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G applied in full mopping Aping of hot asphalt or Polyflex G, torch -applied.
k 6 Maximum Design Pressure =-120psfPressure = -120 psf:
�
Deck: Min. 15 32-inch I / plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: CMG #12 Standard Roofgrip or CMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal
Plates
Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows.
Underlayment- Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
27 MaximumMaximum Design Pressure = -120 psf:
= -120 psf:
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface)
Fasteners: Trufast #12 DP or Trufast #14 HD with Trufast 3" Metal Insulation Plates
II Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt.
.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on tile systems carry a Maximum
Design Pressure of-45 psf.
.5.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed
that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design
pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density
designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are
�I ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked
�i with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January
2016) for Zone 2/3 enhancements.
Exposure Limitations:
Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days
after installation.
Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after installation.
Polystick MTS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastoflex G TU shall not be left exposed for longer than
180-days after installation.
Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet; or SA-APP Cap Sheet (FR) does not have an exposure
limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30
days.
I� Elastoflex S6 G or Elastoflex S6 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the
I prepared roof covering is to be adhesive -set tile (Elastoflex S6 G or Polyflex G only), in which case the maximum
exposure is 180 days.
Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226
1, roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as
set forth in Section 4.3, Note 1 of ASTM D1970-15, should be established as to slip resistance.
.I
r Research and ' �Desig n U.C.!I Evaluation Report P12060.02.09-R23
t@IofAuthorization #9503 6m EDMON(2017jFBCNON,HVHZEVAWATION FL5Z59-R27
Polyglass Roof Underlayments; (570) 384-1230 Revision 23: 09/14/2017
Page 1'0 of 14
6.
li4 1
I
TRINITY ERD
:9 Tile Slippage Limitations (TAS 103 per FRSA/TRI April 2012 (04-12))•
it When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall be as
follows. These slope limitations can only be exceeded, by using battens during loading of the roof tiles.
TABLE 2: TILE SLIPPAGE:LIM_ ITATIONSFOR DIRECT=DECK TILE INSTALLATIONS_
Underlayment
Tile Profile
Staging Method
Maximum Slope
E
astoflex G TU
II
Flat
10 the stack
7:12
Lugged
8-tile stack '(6 over 2)
6:12
E,
astoflex 56 G or S6 G FR
Flat or Lugged
6-tile stack (4 over 2)
4:12
Polystick MTS
Polystick Tile Pro
Flat or Lugged
Flat or Lugged
Prohibited without battens
6-tile stack (4 over 2)
N/A
7:12
li
P lilystick TU Max
Flat
6-tile stack (4.over 2) or 10-tile stack
7:12
Lugged .
6-tile stack (4 over 2)
7:12
Lugged
10-tile stack
6:12
Polystick
TU P
ii
Flat
.6-tile stack (4 over 2)
6:12
Lugged
6-tile stack (4 over 2)
4:12
PT�lystickTU
u
Plus
III
Flat or Lugged
6-tile stack (4 over 2)
7:12
Flat or Lugged
10-tile stack
6:12
P$.,Iyflex
G or G FR
Flat or Lugged
6-tile stack (4 over 2)
4:12
Polyflex
SA P or SA P FR
V
Flat or Lugged
6-tile stack (4 over 2)
4:12
6.1 Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements
it subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove
an dust and debris prior to a lication and rime the substrate if applicable).
Y p • pp • p • (
y
6a3:. Elastobase; Elastobase, P or, Mule -Hide Nail Base:.
6.1 1 Non -Tile Applications:
Shall be installed in compliance with the codified requirements for ASTM D226, Type II underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polystick, Polyflex SAP, Polyflex SA
P FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastoflex G TU, Elastoflex S6 G or
Elastoflex S6 G FR in hot asphalt or Polyflex G or Polyflex G FR, torch applied. Roof cover limitations are those are
those associated with the top -layer underlayment, as set forth in Table 1.
6.3.2 Tile Applications:
Elastobase, Elastobase P or Mule -Hide Nail Base are limited to use as a mechanically attached base sheet in the "Two
Ply System" from FRSA/TRI April 2012 (04-12). Reference is made to Table 1 and Section 5.6.4 herein, coupled with
FRSA/TRI April 2012 (04-12) Installation Manual.
tesearch and Design, LLC.
of Authorization #9503 e" EDITION (2017) FBC NON>HVFIZ EVALUATION
Polyglass Roof Underlayments; (570) 384-1230
Evaluation Report P12060.02.09-R23
FL5259-RZ7
Revision 23: 09/14/2017
Page 11 of 14
III
I, (PTRIN'ITYIERD
�A'' Polystick MTS, IR-Xe, TU P 'TU Plus, tU Max, Dual Pro, Tile Pro or MU-Xor Polyflex SAP,, Polyflex SAP'FR, Mule -Hide
SA=APP Cap.Sheet or Mule -Hide SA-APP Cap Sheet (FR):
614.1 Shall be installed in compliance with the codified requirements for ASTM D1970 underlayment in FBC table 1507.1.1
for the type of prepared roof covering to be installed.
4.2 (Direct-to=Deck\withlMeehanicall�FastenedFRoofi Covers
Hide Back Nailing Guide. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 1-inch diameter
metal disk or Simplex -type metal cap nail; at a minimum rate of 12" o.c.. Polystick TU Plus should be back -nailed
using the above noted fasteners and spacing, in area marked "nail area, area para clavar" on the face of membrane.
The head lap membrane is to cover the area being back -nailed.
All seal -lap seams (selvage laps) must b
firmly rolled with a minimum 28 lb. han
roller to ensure full contact and adhesion.
For Dual Pro and Tile Pro, align the edge c
the top sheet to the end of the glue patter
(the sheet will overlap the fabric).
View of Ovelap Seam of Dual Pro and Tile Pro
All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus 50 Premium Modified
Wet/Dry Cement or Polyglass PG500 Modified Cement applied in between the application of the lap.
Polystick TU Plus, Dual Pro and Tile Pro may. not be used in any exposed application such as crickets, exposed valleys,
or exposed roof to wall details
Repair of Polystick membranes is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or
Polyglass PG500 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 inch patch of the
Polystick material of like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be
installed in a water shedding manner.
All Polystick membranes shall be installed to ensure full contact with .approved substrates., Polyglass requires a
minimum of 40'-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 407lbs of load applied
for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28 lb roller) or small areas of the
roof that are not accessible to a large roller or broom.
-.3 Tile Anplications (not allowed for Polystick Dual Pro IR Xe or Polystick MU X)
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions
noted above as a guideline.
For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base
Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table 1.
For adhesive -set tile applications, refer to Section 5.6.4 herein.
For nail -on tile systems over Polystick MTS, battens are required for loading / staging of the tile.
.4 Two (2) Ply Underlayment Systems:
Polystick.MTS followed by Polystick MTS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Polyflex SAP is allowable for use
under mechanically attached prepared roof systems. Limits of use are those associated with the top -layer material.
This is not a requirement, but is allowable if a 2-ply underlayment system is desired.
Research and Design, U.C. Evaluation Report P12060.02.09-R23
of Authorization #9503 EDITION (2017) FBC NCAT-HVHz EVALUATION FL5259-R27
Polyglass Roof Underlayments; (570) 384-1230 Revision 23: 09/14/2017
Page 12 of 14
(_)O
v TRINITY I ERD
6.5 Elastoflex G TU Elastoflex S6 G or Elastoflex S6 G FR:
6'.5.1 Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be installed in compliance with current Polyglass published
installation requirements. For use in tile applications:
✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single
'j Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or
adhered tile roof systems.
✓ Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply
System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheet" in the `Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or
adhered the roof systems.
I� ✓ Elastoflex S6 G FR is for use as an alternate. to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the"Single
Ply System" from FRSA/TRI April 2012 (04-12), beneath mechanically fastened tile roof systems or the Hot Asphalt
I applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile
roof systems.
I5.2 For hot -asphalt -applications, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be fully asphalt -applied to the
substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-inch wide, off -set
I� minimum 3 feet from course to course. Side and end laps shall be full adhered in a complete mopping
P Y p Aping of hot asphalt
with asphalt extending approximately 3/8-inch beyond the lap edge.
6 6 _- Polyflex G or-Polyflex-G FR:
Ei'6.1 Polyflex G or Polyflex G FR shall be installed in compliance with current Polyglass published installationrequirements.
4 For use in tile applications:
✓ Polyflex G is for use as an alternate to the Heat Applied "Cap. Sheet" in the "Two Ply System" from FRSA/TRI April
2012 (04-12) beneath mechanically fastened or adhered tile roof systems (Base Sheet Limited per 5.6.3).
✓ Polyflex G FR is for use as an alternate to the Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI
April 2012 (04-12) beneath mechanically fastened tile roof systems (Base Sheet Limited per 5:6.3).
6.116.2 Polyflex G or Polyflex G FR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall be
II minimum 3-inch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course. Side and end
laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap
edge.
6b7 Tile Staeine:
G!,7.1 Tile shall be loaded and staged in a manner that prevents the slippage and/or damage to the underlayment. Refer to
I' Table 2 herein, and Polyglass published requirements for tile staging.
67.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used
on all roof slopes greater than 7:12. _Precautions should be taken as needed, such as the use of battens or nail -
boards, to prevent tile sliding and/or damage to the underlayment during the loading process.
6II7.3 Polyglass specifies the minimum cure time after installation of self -adhering membranes and before loading of
roofing tiles is forty-eight (48) hours.
i'Ir Research and Design, LLC.
m Evaluation Report P12060.02.097R23
:nte ofAuthorizotion M03 6T" EDMON (2017) FBC NON-HVHZ EVAWATION FL5259-R27
11 Polyglass Roof Underlayments; (570) 384-1230 Revision 23: 09/14/2017
Page 13 of 14
I � �
7.
8.
9.
\,,JTRINITYI ERD
RMIT REQUIREMENTS:
)y the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product.
RING PLANTS:
noted QA agency for information on product locations covered for F.A.C. 61G20-3 QA requirements. The following
qualified products under their respective physical properties specifications.
plant
Specification,
Product s
';ernley, NV, Hazleton, PA & Winter Haven, FL
ASTM D1970
Polystick MU-X
azleton, PA
M-D 13-0004
Elastoflex G TU
azleton, PA & Winter Haven, FL
ASTM D1970
Polystick IR-Xe
ASTM D1970 & TAS 103
Polystick TU Plus
ASTM D1970 &TAS 103
Polystick TU Max
uscaioosa, AL
ASTM D4601, Type II
Polyglass G2 Base
Winter Haven, FL
I�
ASTMD226.(physicals)
Elastobase, Elastobase P
ASTM D6509
Polyglass APP Base
TAS 103
Polystick MTS
ASTM D1970 & TAS 103
Polystick TU P
FRSA/TRI April 2012
Polyflex SAP, Polyflex SA P FR
ASTM D1970
Polystick Dual Pro
ASTM D1970 & TAS 103
Polystick Tile Pro
ASTM D6164
Elastoflex S6, Elastoflex S6 G FR
ASTM D6222 I
Polyflex G, Polyflex G FR
ALI I Y AJSUKANU CNTITY:
LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com
- END OF EVALUATION REPORT -
Research and Design, LLC. Evaluation Report P12060.02.09-R23
! o/Authorizotion #9503 GP EDITION (2017) FSC NON-HVHZ EVALUATION FL5259-RZ7
Polyglass Roof Underlayments; (570) 384-1230 Revision 23: 09/14/2017
Page 14 of 14