HomeMy WebLinkAboutGRID-TIED SOLAR POWER SYSTEM1 .M
DIRECTORY OF PAGES
PV-1
PROJECT SUMMARY
PV-2
SITE PLAN
PV3
SINGLE -LINE DIAGRAM
PV-4
SAFETY LABELS
ELECTRICAL CALCULATIONS
MODULE DATASHEET
INVERTER DATASHEET
Zw
QMOUNTING
MOUNTING SYSTEM DATASHEET
SYSTEM ENGINEERING LETTER
UL 2703 GROUND AND BONDING CERTIFICATION
ANCHORDATASHEET
PROJECT DETAILS
PROPERTYOWNER
PROPERTY ADDRESS
3056 EAGLE'S NEST WAY, PORT ST.
LUCIE, FL 34952 US
APN
ZONING
RESIDENTIAL
USE AND OCCUPANCY
CLASSIFICATION
ONE- ORTWO-FAMILY DWELLING
GROUP (GROUP R3)
AHJ
UTILITY COMPANY
FLORIDA POWER 8 LIGHT CO
ELECTRICAL CODE
2014 NEC (NFPA 70)
FIRE CODE
2015 NFPA 1
CONTRACTOR INFORMATION
COMPANY
SOLAR HOMES
LICENSE NUMBER
EC13006510(ELECTRICAL)
ADDRESS
3180 MULFORD RO, MULBERRY, FL
33860
PHONENUMBER
CONTRACTOR
SIGNATURE
RECEIVED
SEP 17 N18
tyPermitting
��; lueie Coun,
SCOPE OF WORK
m+
THIS PROJECT INVOLVES THE INSTALLATION OF SOLAR
r d
m (
PANELS. THE SOLAR PANELS WILL BE RACKED USING A
PREENGINEERED RACKING SYSTEM. THE RACKED MODULES
-
' A S-•
- +
WILL BE ELECTRICALLY CONNECTED WITH DC TO AC POWER
INVERTERS AND INTERCONNECTED TO THE LOCAL UTILITY
'
USING MEANS AND METHODS CONSISTENT WITH THE RULES
ENFORCED BY THE LOCAL UTILITY AND PERMITTING
JURISDICTION.
zr fdap data @2018 G
1 PLOT
PV-1 SCALE: NTS
2 LOCALE
PV-1 SCALE: NITS
SYSTEM DETAILS
DESCRIPTION
NEW GRID -INTERACTIVE
PHOTOVOLTAIC SYSTEM WITH NO
BATTERY STORAGE
DC RATING OF SYSTEM
9,860W
AC RATING OF SYSTEM
7,68OW
AC OUTPUT CURRENT
32.OA
INVERTER(S)
1 X SMA SB 7.7-1SP-US-00
MODULE
SOLAR WORLD SW 290 MONO BLACK
ARRAY WIRING
€1 STRING OF 12 5PT #3
INTERCONNECTION DETAILS
POINT OF CONNECTION
NEW SUPPLY SIDE AC CONNECTION
PER NEC 705.12(A)
UTILITY SERVICE
120/240V1(
SOLAR DISCONNECT
EATON DG222NRB , 2-POLE, 60A,
240VAC
SITE DETAILS
ASHRAE EXTREME LOW
0°C (32°F)
ASHRAE2%HIGH
33-C(91-F)
CLIMATE DATA SOURCE
VERO BEACH MUNICIPAL AIRPORT
(KVRB)
WINDSPEED
RISK CATEGORY
II
WIND EXPOSURE
CATEGORY
GROUND SNOW LOAD
Me I
W
CV
Lo
U)
�
M
LLJ
U)
LLJ
p
Z
LLJ
a.
U)
U
J
—
U)
U)
LU
Lu
co
F-
[If
F-
CM
f�
0
PROJECT ' '
PV-1
GENERAL NOTES
EQUIPMENT LIKELY TO BE WORKED UPON WHILE
1
ENERGIZED SHALL BE INSTALLED IN LOCATIONS THAT
SATISFY MINIMUM WORKING CLEARANCES PER NEC
11026.
2
CONTRACTOR SHALL USE ONLY COMPONENTS LISTED
BY A NATIONALLY RECOGNIZED TESTING LABORATORY
FOR THE INTENDED USE.
CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL
3
EQUIPMENT, CABLES, ADDITIONAL CONDUITS,
RACEWAYS, AND OTHER ACCESSORIES NECESSARY
FOR A COMPLETE AND OPERATIONAL PV SYSTEM.
WHERE DC PV SOURCE OR DC PV OUTPUT CIRCUITS
ARE RUN INSIDE THE BUILDING, THEY SHALL BE
CONTAINED IN METAL RACEWAYS, TYPE MC METAL -
4
CLAD CABLE, OR METAL ENCLOSURES FROM THE POINT
OF PENETRATION INTO THE BUILDING TO THE FIRST
READILY ACCESSIBLE DISCONNECTING MEANS, PER
NEC 690.31(G).
5
ALL EMT CONDUIT FITTINGS SHALL BE LISTED AS
WEATHERPROOF FITTINGS AND INSTALLED TO ENSURE
A RAINTIGHT FIT, PER NEC 358.42.
SITE PLAN (AERIAL VIEW)
PV-2 SCALE: V = 20'
W
>-
N
Q
f�nLu
cf
/
Lu
co Ly
W
O
Z W
a
U
_U)
W Z)
J J
CA
W
F-
ui
co
M O
C7
PV-2
PM714 I ^,,••• I wuu ory ew own I m,,ry I "" I "" I B.44n I "" I 4 " I � vr°:lu.ai7w-�l I 25A
I I I 29OW INVERTERS
I I I
I I I QQ OTY MAKEANDMODEL ACVOLTAGE GROUND MAXOCPDRATWAX G RATEDPOWER MOUTPUTCURRENT MAXINPUTCURRENT MAXINPUTVCLTAGE CECWEIGHTEDEFRCIENCY
ISIRIN ISTRIM 1111N I 1 T IN
[STRING ISTRIN II 1 1 1 SMASB7.74SW540 (140VAC) 240V UNGROUNDED I 50A 1 7,680W 1 32AA I 30AA 1 600V 1 96.5%
I I I
I I I RAPID SHUTDOWN DEVICES
I I I REF, OTY. MAKEANOMODEL MAX INPUT CURRENT (CONTINUOUS) MAX. RATEOVOLTAGE
I R51 I 1 I TBO I 30A 6WVDO
DISCONNECTS OCPDS
REF 1 L - . OTY. MAKE AND MODEL RATEDCUWENi MAXRATEDVOLTAGE REF. OTY. RNTEDCURRENT MAXVOLTABE
I
1 SW7 7 EATON DG211NRB OREOUN. 6
0A 240VAC I_ F7-2 I 2 I _ _ d0A 240VAC
rRAPID SHUTDOWNEEMTED(CEC)ACPOWER
SYSTEM SUMMARY NOTES
L I DEVICE MPPT7 MPPT2 MPPf3 Q UNGROUNDED SYSTEM DCCONOUCTORS SHALL BECOLOR-CODEDAS FOLLOW& DC POSITIVE SHALL BE RED (OR MARKED RED) AND DC NEGATNESHALL BE
RS7 3 SERIES 17 11 11 BLACK (OR MARKED BLACK)
I' J 345AV 345.4V 3TK:
2 9.3A 9.3A 9.3A ®KAX DO VOLTAGE OF ARRAY IS EXPECTED TO BE 516.OV AT O°C((0-C-25-C)X-0.124VIC� 39.9V1 X 12=SI&OV). _
INVERTER VOC 473V 473Y 516V
I -- 10A IOA IOA RAPID SHUTDOWN DEVICES COMPLWWITH REQUIREMENTSAS PER NEC 6%.12. CONTRACTORSHALL WSTALLDEVICE(S) ATLOCATIONSSUCH THAT PV
I 117,680WPOWER 9,860W ASOUACE CIRCUITS CONDUCTORS MORE THAN 5 FEET INSIDE ASUILDING OR MORE THAN 10 FEET FROM AN ARRAY WILL BE LIMITED TOAMAXIMUMOF30V
1 POWER %285W ANO240WWRHIN IOSECONDSOFRANMHUTDOWN INITMTIOW
I f{f-{�}4
1 EERT T,660W 32A A INVERTER IS NON-ISOIATED.N000DEC IS REQUIRED.
I
L� EC)ACPOWER 7,68DW ®POINT-0FfANNECTI0N IS ON THE SUPPLY SIDE OF SERVICE DI3LONNECT, IN COMPLIMCEWITH NEC TOB.12(7N.
I
L__-
r7-z
40A
r--
Swt
60A
I
_1_
5
AC
GEC
SERVICE DISCONNECT
AND MAIN DIST. PANEL
1200A MSP W1200A MBR)
0
KWHR
2240111I2T0YV 1E,3W
CONDUCTOR
AND CONDUIT SCHEDULE WIELECTRICAL
CALCULATIONS
'
TYPICAL
CONDUCTOR
CONDUIT
CURRENT-0ARRYIN
DOE
GCOIT
OCPO
EGG
TEMP. CORP.
CONDUG FILL
CONT.
MAX CURRENT
EASE
DERATEo
TERM.
AMP. @TERM.
LENGTH
VOLTAG
CONDUIT
FACTOR
FACTOR
CURRENT
(125%)
AMP.
AMP.
TEMP. RATING
TEMP.RATING
DROP
1 2
70 APV WIRE,
COPPER
CO
CO
FREEAIR
WA
WA
fiAWGBARE.
COPPER
0.76(55-C)
1.0
12.48A
15.58A
55A
41.8A
75-C
S0A
72FT
0.52%
2 1
10AWGTHWN-Z
COPPER
0.75'DIA
EMT
0
WA
10AWGTKWN�,
COPPER
0.76(55-C)
Ole
72.46A
15SBA
40A
24.32A
Svc
30A
50FT
0,36%
3 1
10AWGFVWIRE,
FREE AIR
WA
WA
6AWG BARE,
0.76(55-C)
1.0 -
1246A
SEA
COPPER
COPIA
PER
15.58A
41.84
75-C
50A
79FT
0,52%
4 1
BAWGTHWN-2,
0.7FDIA
2
WA
8AWGTHWN-2,
0.96(33-C)
1.0
43A
COPPER
LFNC
COPPER
32A
55A
62.&A
60-C
1.
10FT
.1%
5 i
BAWG710vN-1,
0.7F
2
40AX2
"AWCOGPPERTHWW2,
0.96(33-C)
1.0
32A
40A
55A
62AA
COPPER
LFNG
WC
SOA
10FT
D21%
.NERAL ELECTRICAL NOTES
iAS 24-HR UNRESTRICTED ACCESS TO ALL
DLTAIC SYSTEM COMPONENTS LOCATED AT THE
ENTRANCE.
3 CONFORM TO AND ARE LISTED UNDER UL 1703.
TORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS
T RESISTANT PER NEC ARTICLE 300.6 (C) (1) AND
310.8 (D).
TORS EXPOSED TO WET LOCATIONS SHALL BE
FOR USE IN WET LOCATIONS PER NEC ARTICLE C
C
W
GROUNDING NOTES
ALL EQUIPMENT SHALL BE PROPERLY GROUNDED PER THE
1 REQUIREMENTS OF NEC ARTICLES 250 & 690
PV MODULES SHALL BE GROUNDED TO MOUNTING RAILS
USING MODULE LUGS OR RACKING INTEGRATED
2 GROUNDING CLAMPS AS ALLOWED BY LOCAL JURISDICTION.
ALL OTHER EXPOSED METAL PARTS SHALL BE GROUNDED
USING UL-LISTED LAY -IN LUGS.
INSTALLER SHALL CONFIRM THAT MOUNTING SYSTEM HAS
BEEN EVALUATED FOR COMPLIANCE WITH UL 2703
3 "GROUNDING AND BONDING'WHEN USED WITH PROPOSED
PV MODULE,
ALL GROUNDING SYSTEM COMPONENTS SHALL BE LISTED
4 FOR THEIR PURPOSE
IF THE EXISTING MAIN SERVICE PANEL DOES NOT HAVE A
5 VERIFIABLE GROUNDING ELECTRODE, IT IS THE
CONTRACTOR'S RESPONSIBILITY TO INSTALL A
SUPPLEMENTAL GROUNDING ELECTRODE.
AC SYSTEM GROUNDING ELECTRODE CONDUCTOR (GEC)
6 SHALL BE A MINIMUM SIZE 96AWG WHEN INSULATED, #6AWG
IF BARE WIRE,
EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED
ACCORDING TO NEC ARTICLE 690.45, AND BE A MINIMUM OF
7 #IOAWG WHEN NOT EXPOSED TO DAMAGE, AND #6AWG
SHALL BE USED WHEN EXPOSED TO DAMAGE
GROUNDING AND BONDING CONDUCTORS, IF INSULATED,
8 SHALL BE COLOR CODED GREEN, OR MARKED GREEN IF
#4AWG OR LARGER
N
}
CV
co
dam"
Lu
O
C)
LLI
Z
cnof
J
L.LI
U
J
LJJ
CD
W
o
N
of
O
C7
SINGLE -LINE
DIAGRAM
PROJECT ID: 96824
DATE: 09106/18
CREATED BY: D.E.
CHECKED BY:
REVISIONS
�1 SINGLE -LINE DIAGRAM
PV-3 SCALE: NTS r V n\ /-/�
3 1lOSD000MIM1u9 BFFNCRFAlEO FORIME PURPOBEOFDESCW3PIGTXEDESYN OFAPRDPOSEOFNOTOVDL7NCPOWIIV STSTEId WITHENp1GNDE1Mi0DFA10N91MTECp61N4YCf WIfHAILMRIGBtE WDESMIDREGtMi10N5.1HEODDIWFMSNOMDNOT6E REIlFDUPDNASASUBGIRUfEFOR
FOLLDNWG LLWUFACTMtFR OV3TALATX)NMWVA13MSiKIFRSHNLPSFALLNLEWPNEMWAtf/JPDPNCE WRXMM'UFPCIUPFRINST/1LAlIR1 N4WO15.N0T19NG MTM6 DOCU61EYf SHWUIBE OVTENPIffIEDINAW0.Y1H4T0VFIWDE9TXEMSIRLGIWN5Po4ANUFACNFFR P6TAl3ADONHW UAl9.
DC RACEWAYS
O
RS1- RAPID SHUTDOWN DEVICE
O SEE NOTE N0.4 (DC RACEWAYS)
WARNING
MODEL NOT SPECIFIED
POWERPHOTOVOLTAIC
OO
NEC 690.31(G)(3) AND IFC 665. 11.1
11 - INVERTER
SMASB7.7-1SP-US40
3 EACH DISCONNECTING MEANS FOR
O PHOTOVOLTAIC EQUIPMENT(RS1,11)
O OO OO OB
I WARNING I--,
SW1 - DISCONNECT
O DGO222NRBO OLOAD
? 8 9 10
ELECTRIC SHOCK HAZARD. DO NOT TOUCH
TERMINALS. TERMINALS ON BOTH LINE AND_','
SIDES MAY Y BE ENERGIZED IN THEOPEN
• POSITION;-
NEC 690.17(E)
UTILITY METER
EACH DEVICE WHERE ENERGIZED
O UNGROUNDED CIRCUITS MAY BE EXPOSED
DURING SERVICE. (RS1, 11)
OOO
I WARNING !
ELECTRIC SHOCK HAZARD THE DC,-,
CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM:
ARE UNGROUNDED AND MAY BE ENERGIZED .<
NEC 690.35(F)
ODC DISCONNECT(MPPT CHANNEL OF 11, MPPT
CHANNEL B OF 11) (11)
NEC 690.53
OB AC DISCONNECT(SW1)
NEC 690.54
OPOINT -OF -INTERCONNECTION ORAT MAIN SERVICE DISCONNECT(UTILITY METER)
AS SHOWN
x�
STOLARA
NLO M.bd(B)
DC DISCONNECT(MPPT CHANNEL C OF 11) 01) O7 SEE NOTE NO. 5(SW1)
NEC 690.63
OANY AC ELECTRICAL PANEL THAT IS FED BY
BOTH THE UTILITY AND THE PHOTOVOLTAIC
SYSTEM (SWI, UTILITY METER)
!:WARNING 1,
DUAL 'POWER SOURCE. SECOND80URCE IS`
PHOTOVOLTAIC SYSTEM.
NEC 705.12(0)(3)
NEC690.56(C) AND IFC605.11A
10 AC SOLAR DISCONNECT(SW1)
0 OVO C D4
NEC 690.13(B)
LABELING NOTES
1
ALL PLAQUES AND SIGNAGE REQUIRED BY 2014 NEC
AND 2015 NFPA 1 WILL BE INSTALLED AS REQUIRED.
LABELS, WARNING(S) AND MARKING SHALL COMPLY
WITH ANSI Z535A, WHICH REQUIRES THAT DANGER,
WARNING, AND CAUTION SIGNS USED THE STANDARD
2
HEADER COLORS, HEADER TEXT, AND SAFETY ALERT
SYMBOL ON EACH LABEL. THE ANSI STANDARD
REQUIRES A HEADING THAT IS AT LEAST 50 % TALLER
THAN THE BODY TEXT, IN ACCORDANCE WITH NEC
110.21(B).
A PERMANENT PLAQUE OR DIRECTORY SHALL BE
3
INSTALLED PROVIDING THE LOCATION OF THE SERVICE
DISCONNECTING MEANS AND THE PHOTOVOLTAIC
SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME
LOCATION IN ACCORDANCE WITH NEC 690.56(B).
LABEL(S) WITH MARKING, "WARNING PHOTOVOLTAIC
POWER SOURCE,' SHALL BE LOCATED AT EVERY 10
FEET OF EACH DC RACEWAY AND WITHIN ONE FOOT OF
4
EVERY TURN OR BEND AND WITHIN ONE FOOTABOVE
AND BELOW ALL PENETRATIONS OF ROOFICEILING
ASSEMBLIES, WALLS AND BARRIERS. THE LABEL SHALL
HAVE 3/8' TALL LETTERS AND BE REFLECTIVE WITH
WHITE TEXT ON A RED BACKGROUND
LABELS WITH MARKING, "PHOTOVOLTAIC SYSTEM
EQUIP D WITH RAPID SHUTDOWN,' SHALL BE LOCATED
5
AT POINT -OF -INTERCONNECTION ORAT MAIN SERVICE
DISCONNECT THE LABEL SHALL HAVE 318• TALL
LETTERS AND BE REFLECTIVE WITH WHITE TEXT ON A
RED BACKGROUND
W
C/)
CV
j
Lu
C/)
O
Z Lu
a
9) U
Lu
J_j J
O)
Lu
F-
0
Lu
co
L0
O
r
M
Nam_
LL
SAFETY
1 REVISIONS I
PV-4
Conductor, Conduit, and OCPD Sizing Validation 1.2. SMA Inverter w/34 SolarWorld SW 290 Mono Black (290W)a
1. Maximum System Voltage Test Array Properties NEC Code Validation Teats
1.1. SMA Inverter w/34 Solar World SW 200 Mono Black (290W)e
Array Properties
NEC Code Valldation Tests
Arta Type
String Inverter Array
NEC Code Calculations
A. Maximum Voltage of PV Source Circuit 516V
see 690.7(c)
NEC 690.7(C) requires that if the PV module manufacturer provides a
temperature coefficient of open-cimu t voltage, it must be used to
calculate the PV arrays maximum system voltage. It includes an
Information note recommending the use of the ASHRAE'Extreme Annual
Mean Minimum Design Dry Bulb Temperature' as the design low
temperature. Using these values, the module Voc (39.9V) wi0 increase to
43V at the design low temperature ( 0°C).
(0'C - 25°C) X-0.124VIC + 39.9V = 43V
The string Voc at the design low temperature is 516V.
43VX12=516V
I
Array Type
String Inverter Array
System Description
SMA inverterw/34 Solar World SW
290 Mono Black 290 s
Module
SW 290 Mono Black 290
Highest number of modules in series
in a PV Source Circuit
12
Design Low Tem.
0°C
Module Voc
39.9V
Temp. Coef dent Voc
-0.124V/C
NEC Code CaltwlaUons
A. Maximum Voltage of PV Source Circuit 516V
see 00..#Q
NEC 690.7(C) requires that if the PV module manufacturer provides a
temperature coefficient of open -circuit voltage, it must be used to
calculate the PV arrays maximum system voltage. It Includes an
Information note recommending the use of the ASHRAE'Extreme Annual
Mean Minimum Design Dry Bulb Temperature' as the design low
temperature. Using these values, the module Voc (39.9V) will increase to
43V at the design low temperature ( 0°C).
(0°C - 25°C) X-0.124VIC + 39.9V = 43V
The string Voc at the design low temperature is 516V.
43VX12=516V
PV Source Circuit maximum Voc must not exceed I PASS
600V
516V < 600V = true
I A SMA Inverter w134 Solar World SW 290 Mono Black (290W)s
Array Properties
Array Type
String Inverter Array
System Description
SMA invaderw/34 Solar World SW
290 Mono Black 290 s
Module
SW 290 Mono Black 290W
Highest number of modules in series
in a PV Source Circuit
12
Design Low Temp.
0°C
Module Vac
39.9V
Tem .Coefficient Voc
-0.124V/C
NEC Code Calculations
A. Maximum Voltage of PV Source Circuit 516V
see 69o.7(C)
NEC 690.7(C) requires that if the PV module manufacturer provides a
temperature coefficient of open-dreuit voltage, it must be used to
calculate the PV arrays maximum system voltage. It includes an
information note recommending the use of the ASHRAE'Extreme Annual
Mean Minimum Design Dry Bulb Temperature' as the design low
temperature. Using these values, the module Voc (39.9V) will increase to
43V at the design low temperature ( 0°C).
(0°C - 25°C) X-0.124VIC + 39.9V = 43V
The string Voc at the design low temperature is 516V.
43VX12=516V
NEC Code Validation Testa
PV Source Circuit maximum Voc must not exceed PASS
690V
516V <600V = We
2. Wire, Conduit, and 0CPD Code Compliance Validation
U. S1: PV Source ClrcuR : Series String Output to Rapid Shutdown Device
Circuit Section Properties
Conductor
10 AWG PV WireCopper
Equipment Ground Conductor EGC
6 AWG BareCopper
OCPD s
NIA
Raceway
Free Air
Lowest Terminal Temperature
Rating
75°C
Maximum Wire Temperature
55°C
Power Source Description
String of 11 SW 290 Mono Black
290 PV modules
Current
9.97A
Voltage
345AV
Module Series Fuse Rating
25A
Total Number of Series Strings
3
NEC Code Calculations
A. Continuous Current 12.46A
see 690.8(A)(1)
The continuous current for this PV source circuit is equal to the short
circuit current of the PV module (9.97A) multiplied by 1.25
9.97A X 1.25=12.46A
B. Ampacity of Conductor 55A
see Table 3f0. 15(B)(f7J
Ampacity (30°C) for a copper conductor with 90°C insulation in free air
Is 55A.
C. Derated Ampacity of Conductor 41.8A
see Table 310. f5(B)(2)(eJ, Table 3W.. f5(B)(3)(eJ, endAdde f00
The temperature factor for 90°C insulation at 55°C is 0.76.
The fill factor for conductors in free air is 1.
The ampadty derdted for Conditions of Use is the product of the
conductor ampacity (55A) multiplied by the temperature factor (0.76) and
by the conduit fill factor (1).
55A X 0.76 X 1 = 41.8A
D. Max Current for Terminal Temp. Rating 35A
see ff0. f4(C)
The lowest temperature limit for this conductor at any termination is
75°C.
Using the method specified in 110.14(C), the maximum current pernitied
to ensure that the device terminal temperature does not exceed its 75°C
rating would be the amount referenced in the 75°C column in Table
310.15(B)(16), which Is 35A.
E. Minimum Required EGC Size 10 AWG
see 690.45(A) and Table 250. f22
No OCPD Is used in circuit and an assumed rating of 25A has been
calculated in accordance with 690.45(A)
The smallest EGC size allowed is 10 AWG for OCPD rating 25A
according to Table 250.122.
NEC Code Validation Tests
System must meet requirements for not having
PASS
series fuse (690.9(A))
Derated Ampacity must be greater than or equal to
PASS
the Continuous Current (Article 100)
41.8A>=12.46A = true
Conductor Ampacity must be at least 125% of
PAS:,
Continuous Current (215.2(A)(1))
55A> 12AGA x 1.25 = We
Max current for terminal must be at least 125% of
PASS
the Continuous CumenL (110.14(C))
35A>=12.46AX1.25 =true
EGC must meet code requirements for minimum
PASS
size (Table 250.122)
6AWG>=10AWG=We
EGC must meet code requirements for physical
PASS
protection (690.46)
6 AWG >= 6 AWG = true
2.2. #2: PV Source CIrcuL- Rapid Shutdown Device to Inverter
Circuit Section Propertlos
Conductor
10 AWG THWN-2 Copper
Equipment Ground Conductor EGC
10 AWG THWN-2 Copper
OCPD s
WA
Raceway
0.75" dia. EMT
Lowest Terminal Temperature
Ratin
60°C
Maximum Wlre Temperature
55°C
Power Source Description
String of 11 SW 2" Mono Black
290 PV modules
Current
9.97A
voltage
345AV
Module Series Fuse Rating
25A
Total Number of Series Strings
3
NEC Code Calculations
A. Continuous Current 12.46A
sea 690.6(A)(1)
The continuous current for this PV source circuit is equal to the short
circuit anent of the PV module (9.97A) multiplied by 1.25
9.97A X 1.25=12.46A
B. Ampacity of Conductor 40A
see Table 310. f5(9)(1)
Ampacity, (30°C) for a copper conductor with 90°C insulation in conduit
Is 40A
C. Derated Ampacity of Conductor 24.32A
see Table 310 f5(B)(2)(a), Table 310, f5(B)(3)(aJ, andAlticle f00
The temperature factor for 90°C insulation at 55°C is 0.76.
The fill factor for a conduit that has 6 wires is O.B.
The ampadty derated for Conditions of Use is the product of the
conductorampacity (40A) multiplied by the temperature factor (0.76) and
by the conduit fill factor (0.8).
40A X 0.76 X 0.8 = 24.32A
D. Max Current for Terminal Temp. Rating 30A
see I f0.14(C)
The lowest temperature limit for this conductor at any termination is
60"C.
Using the method specified in 110.14(C), the maximum current permitted
to ensure that the device terminal temperature does not exceed its 60°C
rating would be the amount referenced in the 60°C column in Table
310.15(B)(16), which is 30A.
E. Minimum Required EGC Size 10 AWG
see 690.45(A) and cable 250.122
No OCPD Is used In circuit and an assumed rating of 25A has been
calculated In accordance with 690.45(A)
The smallest EGC size allowed is 10 AWG for OCPD rating 25A
according to Table 250.122.
F. Minimum Recommended Conduit Size 0.75"dia.
see 300.17
The total area of all conductors is 0.1899in2. With a maximum fill rate of
0.4, the recommended conduit diameter Is 0.75.
VConducbr
10 AWGround
0.1899irP
0.18991n210.4 = 0.4748in2 (Corresponding to a diameter of 0.751
NEC Code Validation Teats
System must meet requirements for not having
PASS
Wanes fuse (690.9(A))
Derated Ampacity must be greater than or equal to
PASS
the Continuous Current (Article 100)
24.32A-12.46A = true
Conductor Ampacity must be at least 125% of
PASS
Continuous Current (215.2(A)(1))
40A> 12.46A x 1.25 = true
Max current for terminal must be at least 125% of
PASS
the Continuous Current. (110.14(C))
30A>=1946AX1.25 =true
EGC must meet code requirements for minimum
PASS
size (Table 250.122)
10AWG >=10AWG =true
Conduit must meet code recommendation for
PASS
minimum size (300.17)
0.751n. >= 0.751n. = true
i
2.3. #3: PV Source Circuit: Soda String Output to Rapid Shutdown Device
Circuit Section Properties NEC Code Valldadon Testa
Conductor
10 AWG PV WireCopper
Equipment Ground Conductor EGC
6 AWG BareCopper
OCPD s
WA
Raceway
Free Air
Lowest Terminal Temperature
Rahn
75°C
Maximum Wire Temperature
55°C
Power Source Description
String of 12 SW 290 Mono Black
210 PVmodulas
Current
9.97A
Voltage
376.8V
Module Series Fuse Ratinp
25A
Total NumberIfSeries-n s
3
NEC Code Calculations
A. Continuous Current 12.46A
see 690.6(A)(f)
The continuous current for this PV source circuit is equal to the short
circuit current of the PV module (9.97A) multiplied by 1.25
9.97A X 1.25 =12A6A
B. Ampacity of Conductor 55A
see Table 3f0.15(B)(1;9
Ampacity (30°C) for a copper conductor with 90°C Insulation in free air
Is 55A
C. Derated Ampacity of Conductor 41.8A
see Table 3f0.15(B)(2)(aJ, Table 3f0. f5(B)(3)(aJ, andArb's/e f00
The temperature factor for 90°C insulation at 55"C is 0.76.
The fill factor for conductors in free air is 1.
The ampacity derated for Conditions of Use is the product of the
conductor ampacity, (55A) multiplied by the temperature factor (0.76) and
by the conduit fill factor (1).
55A X 0.76 X 1 = 41.8A
D. Max Current for Terminal Temp. Rating 35A
see ff0.14(C)
The lowest temperature limit for this conductor at any termination is
75"C.
Using the method specified in 110.14(C), the maximum current permitted
to ensure that the device terminal temperature does not exceed its 75°C
rating would be the amount referenced in the 75°C column in Table
310.15(B)(16), which is 35X
E. Minimum Required EGC Size 10 AWG
we 690,45(A) and Table 250.122
No OCPD Is used In circuit and an assumed rating of 25A has been
calculated In accordance with 690.45(A)
The smallest EGC size allowed is 10 AWG for OCPD rating 25A
according to Table 250.122.
System must meet requirements for not having
PASS
series fuse (690.9(A))
Derated Ampacity must be greater than or equal to
PASS
the Continuous Current (Article 100)
41.8A>=12.46A=true
Conductor Ampacity must be at least 125% of
PASS
Continuous Current (2152(A)(1))
56A > 12.46A x 125 = true
Max current for terminal must be at least 125% of
PASS'I
the Continuous Current. (110.14(C))
35A>=12.46A X 1.25 = true
EGC must meet code requirements for minimum
PASS
size (Table 250.122)
6AWG >-10AWG =true
EGC must meet code requirements for physical
PASS
protection (690.46)
6 AWG >= 6 AWG = true
2A. 94: Inverter Output: Inverter to Why Disconnect
Circuit Section Properties
Conductor
8AWG THWN-2 Copper
Equipment Ground Conductor EGC
8 AWG THWN-2 Copper
OCPD s
NIA
Raceway
0.75" dia. LFNC
Lowest Terminal Temperature
Rating
60"C
Maximum Wire Temperature
330C
Power Source Description
SMASB7.7-iSP-US-40768OW
In
In
Curtent
Volta a
240V
Inverter Max OCPD raft
150A
NEC Code Calculations
A. Continuous Current 32A
see Adele f00
Equipment maximum rated output current is 3 X 9.97A = 32A
B. Ampacity of Conductor 55A
see Table 3W.. f5(B)(f6/
Ampacity (30"C) for a copper conductor with 90"C insulation In conduit
Is 65A
C. Derated Ampacity of Conductor 52.8A
sea Table 3f0.15(B)(2)(af, Table 3f0.15(B)(3)(a),, arrorkfc/e f00
The temperature factor for 90"C insulation at 33"C is 0.96.
The fill factor fora conduit that has 2 wires is 1.
The ampadty aerated for Conditions of Use is the product of the conductor ampadty (55A) multiplied by the temperature factor (0.96) and
by the conduit fill factor (1).
55A X 0.96 X 1 = 52.8A
D. Max Current for Terminal Temp. Rating 40A
see 110.14(C)
The lowest temperature limit for this conductor at any termination is
60"C.
Using the method specified in 110.14(C), the maximum current permitted
to ensure that the device terminal temperature does not exceed its 60°C
rating would be the amount referenced in the 60"C column in Table
310.15(B)(16), which is 40A
E. Minimum Allowed OCPD Rating 40A
see 240.4
NEC 690.9(B) requires that the OCPD be rated for no less than 1.25
times the Continuous Current of the circuit.
32A X 1.25 = 40A
F. Minimum Required EGC Size 10 AWG
see Table 250.122
The smallest EGC size allowed is 10 AWG for 0CP0 rating 40A
according to Table 250.122.
G. Minimum Recommended Conduit Size 0.75"dia.
see 300..17
The total area of all conductors is 0.1309in2. With a maximum fill rate of
0.4, the recommended conduit diameter is 0.75.
a
Desdolion
Size
Tvoe
Area
Total Area
2
Conductor
8AWG
THWN-2
0.0366in'
0.0732W
1
Neutral
10AWG
THWN-2
0.02111n'
0.0211in'
1
Equipment Ground
8AWG
THWN-2
0.036&2
0.0366in'
4
0.1309W
0.13091n' / 0.4 = 0.32721n2 (Corresponding to a diameter of 0,751
NEC Code Validation Teets
OCPD rating must be at least 125% of Continuous
PASS
Current (240.4)
40A >= 32AX 1.25 = true
Derated ampacity, must exceed OCPD rating, or
PASS
rating of next smaller OCPD (240.4)
52.8A r_ 40A (OCPD Rating) = true
Derated Ampacity must be greater than or equal to
PASS
the Continuous Current (Article 100)
52.80= 32A = true
Conductor Ampacity must be at least 125% of
PASS
Continuous Current (215.2(A)(1))
55A>32Ax1.25=true
Max current for terminal must be at least 125% of
PASS
the Continuous Current. (I10.14(C))
40A>=32AX125 =We
EGC must meet code requirements for minimum
PASS
size (Table 250.122)
8AWG>=10AWG =true
Conduit must meet code recommendation for
PASS
minimum size (300.17)
0.75in. >= 0.75in. = true
2.5. 95: Utility Disconnect Output: Utility Disconnect to Point of Connection
Circuit Section Properties
Conductor
8 AWG THWN-2 Copper
Equipment Ground Conductor EGC
10 AWG THWN-2 Copper
OCPD s
40A X 2
Raceway
0.76" dia. LFNC
Lowest Terminal Temperature
Ratin
75"C
Maximum Wire Temperature
33"C
Power Source Description
SMA SB 71ASP-USZ 768OW
Inverter
Current
32A
Volta a
1240V
NEC Code Calculations
A. Continuous Current 32A
8eeAAC10100
Equipment maximum rated output current is 3 X 9.97A = 32A
B. Ampacity of Conductor 55A
see Table 3f0. f5(B)(16)
Ampacity (30"C) for a copper conductor with 90°C Insulation in conduit
Is 55A
C. Derated Ampacity of Conductor 52.8A
see Table 310.15(B)(2)(eJ, Teblo 3f0. f5(B)(3J(a). andAlkle WO
The temperature factor for 90'C insulation at 33"C is 0.96.
The fill factor for a conduit that has 2 wires is 1.
The ampadty derated for Conditions of Use is the product of the
conductor ampadty (55A) multiplied by the temperature factor (0.96) and
by the conduit fill factor (1).
55A X 0.96 X 1 = 52.8A
D. Max Current for Terminal Temp. Rating 50A
see f 10. f4(0)
The lowest temperature limit for this conductor at any termination is
75"C.
Using the method specified in 110.14(C), the maximum current permitted
to ensure that the device terminal temperature does not exceed its 75'C
rating would be the amount referenced in the 75"C column in Table
310.15(B)(16), which is 50A.
E. Minimum Allowed OCPD Rating 40A
see 240.4
NEC 690.9(B) requires that the OCPD be rated for no less than 1.25
times the Continuous Current of the circuit.
32A X 1.25 = 40A
F. Minimum Required EGC Size 10 AWG
ses Table 250. f22
The smallest EGC size allowed is 10 AWG for OCPD rating 40A
according to Table 250.122.
G. Minimum Recommended Conduit Size 0.5" dia.
see 300..17
The total area of all conductors is 0.11541n'. With a maximum fill rate of
0.4, the recommended conduit diameter is 0.5.
Description
Sae
Tvoe
Area
Total Area
2
Conductor
8AWG
THWN-2
0.0366h2
0.0732in'
1
Neutral
10AWG
THWN-2
0.02111n'
0.0211ln'
1Equipment
Gnwnd
10AW,
THIM
0.0211in'
0.0211W
4
0.1154W
0.11541n' 10.4 = 0.2885in' (Corresponding to a diameter of 0.51
NEC Code Validation Tests
OCPD rating must be at least 125% of Continuous
PASS
Current (240.4)
40A >= 32A X 125 = true
ampadty, must exceed OCPD rating, or
PASS
ting of next anOCPD (240.4)
fferated
2.BA >= 41A (OCPC Rating) = We
Derated Ampacity must be greater than or equal to
PASS
the Continuous Current (Article 100)
52.6A>= 32A = true
Conductor Ampacity must be at least 125% of
PASS
Continuous Current (2152(A)(1))
55A > 32A x 1.25 = true
Max current for terminal must be at least 125% of
PASS
the Continuous Current. (110.14(C))
50A >= 32A X 1.25 = true
EGC must meet code requirements for minimum
PASS
size (Table 250.122)
10 AWG >= 10 AWG = true
Conduit must meet code recommendation for
PASS
minimum size (300.17)
0.751n. >= 0.51n. = he
e
t
1'+, i{a• Y k'� 4 • • g
Sunmodule/ Plus
SW175,290i'MONO BLACK
TUV Power controlled:
TOvabw�d Lowest measuring tolerance in industry
Every component is tested to meet
- 3 times IEC requirements
J
Designed to withstand heavy
accumulations of snow and Ice
J
Sunmodule Plus;
Positive performance tolerance
J
25-year linear performance warranty
and 10-year product warranty
J
r"-- Glass with anti -reflective coating
J
World -class quality Lo;:r';a u"•i,m
Fully -automated production lines and seamless monitoring of the process and Dve
m'
SAo
VS��7
x'mi omwon¢iw
material ensure the quality that the company sets as its benchmark for its sites
c us
worldwide. _
UL 1703
SolarWarld Plus -Sorting •� (• pn•r
Plus -Sorting guarantees highest system efficiency. SolarWorid only delivers modules LflJ
that have greater than or equal to the nameplate rated power.
25-year linear performance guarantee and extension of product warranty to 10 year
`
SolarWorld guarantees a maximum performance digression ofO.7% p.a. in the course ✓
�i°
PJ
of 25 years, a significant added value compared to the two-phase warra nties common
in the industry, along with our ind ustry-first 10-year product warranty."
• Solar cells manufactured in U.S.A. or Germany. Modules assembled in U.S.A.
'• in accordance with the applicable SolarWorld Limited Warranty at purchase.
wwwsolarworld.com/warranty
solarworld.com MADE INaUSSAor us & Imptos
Sunmodule%Plus
.
SW 275-290 MONO BLACK
PERFORMANCE UNDER STANDARD TEST CONDITIONS (STC)'
SW 275 SW280
SW 28S SW 290
Maximum power P,,,•,
275 Wp 280 Wp
285 Wp 29OWp
Opencircuitvoltage V.
39.4V 39.SV
39.7V 39.9V
Maximum power point voltage V_
31.OV 31.2V
31,3V 31AV
Shortcircuitcurrent Ill
9.58A 9.71A
9.84A 9.97A
Maximumpowerpoiatrurrent Lf.,,
8.94A 9.07A
9.20A 9.33A
Module efflciency 9m
16.40 % 16.70 %
17.00 % 17.30 % '
'STC: 1000w/W.25•c. AM 1.5
PERFORMANCE AT 800 W/Mr, NOCT, AM 1.5
SW 275 SW 280
SW 285 SW 290
Maximumpower Pm„
203.1 Wp 2072Wp
211.1 Wp 215 Wp
Open circuit voltage V.
35.7 V 35.8 V
36.0 V 36.2 V
Maximum powerpoint voltage V_
28.1V 28.3V
28.4V 2a.5V
Short circuit current I,c
7.75A 285A
7.96A 8.06A
Maximum powerpoint current Im
7.22A 7.33A
7.43A 7.54A
Mlnor reduction In efficiency under partial load conditions at 25' Gat 200 W/m=, 100%ofthe STC efficlency (1000 W/mj Is achieved.
COMPONENT MATERIALS
I< 1000 w/rr�
Boo W/w
Wh inermodule 60
Front tow with -iron ARC(Eemperdglass
with ARC (EN 12150)
Cell type Monocrystalline
Frame Black anodized aluminum
a 6oOW/ ,
_
Celldlmenslons 6,17 inx 6.17in
(156.75 156.75
Weight 39.71bs (18.O kg)
400w/m=
x mm)
200% _
THERMAL CHARACTERISTICS
ADDITIONALDATA
loo W/m=
-
Noer aa•e
Powersonfng-owp/+swp
Va
�vuue•M
TCI„ 0.044%/'C
d-Box IP65
TC q-0.31%/'C
Connector PVwire per UL4703
378 (961)
TCP„w-0.44%/'e
with H4/UTX connectors
4.20 oo
Module fireperformance (UL7703)Type 1
006.65).. i ax1
Operating temp -40 to ♦BS'C
712 T 00.26(6.6)� -
(1806s)
PARAMETERS FOR OPTIMAL SYSTEM INTEGRATION
• 6035 (9)
Maximum system voltage SC Il/NEC
1000 V
o
Moxlmum""n current
25A
a
Numberof bypass diodes
3
51
Design loads' Two raifsystem 113 psfdownward, 64 psfupward
-
Design loads' Threemflsystem 173 psfdownward, 64 psfupward
Design loads' Edgemounting 178 psfdownward. 41 psf upward
'%ease referto the Sumnoduie Installation instructions for the details assoclated with these load cases.
onrlN
Compatible with both 'Top -Down'
• E335(9)4
and'Bottom niountingmethods
1132
• -16 Grounding Locations:
(29750)
-4loations along the length ofthe
taa or)
L
module in the extended Flange.
39.40001) �
1,30 (331
All units provided arc imperial.5i units provided In parenthese-
SalarWorid AG reservesthe rightto make speeifiation dungeswithout notice.
4..- to 1z91 ----�
SW-01-752OUS 160324
SUNNY BOY
3.0-US / 3,8-US / 5.0-US / 6.0-US / 7.0-US / 7.7-US
Value Added Improvements -R� educed Labor .Unmatched Flexibihty� j Trouble -Free Servicing Tj f
tSupenor integration with SMA's r New l st 116tion Ass slantwith d SMA s p pnetay Opt7roc,Z_ j ri encl... concept 9
r MLPE, Power+ Sol fi n : i direct accesib!. sm?nphanti -i # .. Global Peak technology mitig?tes J allows for simple, expedited
Would. firsl5ecu Powei:SuppFy nimizes tlm �'In the field.. 9 shade with ease � '.,, � } servicing _ !
nowoNmsupt 2000W Inl gmt ddsconnectsimplifies Muhpl Independent MPPTi .i Enhanced AFC! technology reduces
• Full Eric! ,ma age ant copab Imes equipment stmki g and speeds aceo modale hundreds of r False tripping while ImproNrg _
ensure o uhhiycomphant solution installation _ stnngng posi bJfies - sum!" in redfor any market
SUNNY BOY
3.0-uS / 3.8-US / 5.0-uS / 6.0-US / 7.0-US / 7.7-US
Reduce costs across your entire residential business model
The residential PV market is changing rapidly. Your bottom line matters more than ever —so we've designed o superior
residential solution to help you decrease costs at every stage of your business operations. The Sunny Boy 3.0-US/3.8-
US/5.0-US/6.0-U5/7.0-US/7,7-US join the SMA lineup of field -proven solar technology backed by the world's #1
service team, along with a wealth of improvements. Simple design, improved stocking and ordering, value -driven sales
support and streamlined installation are just some of the ways that SMA helps your business operate more efficiently.
And, Sunny Boy's superior integration with the innovative Power+Solution means installers have even more flexibility in
addressing their toughest challenges, www.SMA-Amedca.com
Jechmi,l data
,.._..,_u,_1._._Rav-_:)�..—.in
Input JDCI
100 W ',J lr , 3d50 W.,,. .5000-W r i �..5150,W� „ i 5150 W-m
480.Y_ :i _.-,.-_1.95_480V J,_r j ;;„220490V
r_w
t� MPPr paroling vdroe 9 � t 100. 550 V
DCQtO
a /tan Img '' i too V/ 125 V M
('.-hlax opera! ng pur currentper MPPf 1S- `„ ,t_—�.:.- ,10A
?.:,_N bar aF MPPT hoot/,ihing pa MPPi,hooka,_;,-,.+.,___�„_„.:____.f..___.2/I_,,,_,,,,._;,;,
OvtuatxpuA_C_AoCppI
U:AC
_....�....IlE__30JON'n7J..=„300W=4,33W. r__3_00V^1 =S0.O_ W=j ):'—_S._.OO.W
=
_000 VA3330VA_:~3800VA="5_000 VA,ai5000V_7;
'��Nanmol volrog / dfuat Gl_._�.;"";=208 V/_•__„r�`2'40V/�- ,_ 208,V,/_� usi~240_V,/i,_1[�,208 V/•,,,,,,j 40V/•_�;
_,, _ 21,126A V—; ,�„183„ 229V 21 J_ 264 V.,! 1-iM =,229 V -3 (-211 - 264 V -1
- -:
q ry l� 60 Hz/50 Hz - �
'�;M tpulnat _ �l" 14SA ii 125A —ir 160AT 160A l 240A a{�'240A---�
r `�P F d ,Icon rl 1 f 1
Efficiency
j_�Ma e8iden -. ' , 972%. .,'975-%� 972,%. ,:975%.
Protedian devices
r'~Ground fouli m ro B / Gd. on to.. B:—.w.-._.rj �,.._.._, _,„ems..-....____.._._.._.._.. _,_,_ . __ „....•._.::�• _._._.:.._._ .. _ �_:�:_...._e_:.-�_...___.„.____..,.....:a
_ .._
rrA[shunn ci�aitp tedlon;.';;,,� _,. :.,:.�._.._., �r. ..... .......__.'.., ....,....;. ,.�, , ,.,r : _.:�... ,.__,.m .....::,e•.";..».�.s.—_,.--__.__,_...:�,..,... .«.: .;_,::_a.�:..1
.. Arc fa Ise rcuB nrerrupiar�(.4KII�.,. _i 5__u� �'' _,.•„_,,,.,.,,i �.,,:_':„, _,,.
General data _
Pockog gdime
ght/packog
..'39dBJAl
assones
.� 'saeer4 6hmaIVAANankruw w ,SMA Ro•frop _ `•._77
MDSENUS4a FATAML54D .. Commrmimnm l(Ir
- ROOFCOMMIerFWS �
Tech Id to i ° -f S yBdy66U5 ] 5 yBay7t•W S yB y,77415
~�InpW (DCI
pow
270 480V
rv-_..----,_ _._.�:..- _
M DC wlt "" .J,._.___�
t - toot//126v._''
i M .Shan rc t Cp MPPr 1.: " 18A__._-_7-
11:�_5200 w,-„; ; 46000 W ;-] {, 6660 W -_� 777000_W j j 6660 V 721
M F9C_ pp tpover J %' S200 VA „j f„- 6000 VA:_, r 6660 VA ,{ s -7000 VA L 6660 VA 7680 VA. ,„?
— - _-_
r' N m'utal Itoge/adry5table _,_ ___j [��208 V/•��t4 240V/• �It 208 V/i �I L„_240 V/• �C, 208 V/�, -I, 240 V/•�1
AC vpltpge mngL- k83 229 V,,,,t _21 I 264 V_-383.,, 229 V__3 if 21 T , 264 V.-„ I E:183 - 229_YV_ { t-.. 211 264 V
ACg d,frcq ry �L _ 60H/5014I
t M uip t urc Y. 'IC__250A f 250A. t 320A f _292A a "320A I ` 320A
Efficiency
Pr fern n d
Dcd
l _i5r4men arcun inranupier.l. 1.. _._-..:_.. ._1.. :�___'....._.�_..__,�.__.....'_ • - s. --.A
ua IdW
D Irn (W/H/D)in () "� JI- S35 730x 19a t211 2[f.5 7a{..' •�)
Pack giagD .fW/H/DI, _�(tI Tt..._ �_. '� 600 800x300 (236x31S 11 g) V�
1 W ght/p <k e' gvretght �i: 26 kgj5716)/30 kg (?b lb] �
TopolaBY_ { T. fo d y
POWER+ SOLUTION
The SMA Power+ Solution combines legendary SMA
inverter performance and intelligent DC module -level
electronics in one cost-effective, comprehensive package.
This means that you can achieve maximum solar power
production for your customers while also realizing
significant installation savings.
Unlike conventional microinverter and DC optimizer
systems, Power+ is faster to install, provides more flexibility,
boasts logistical advantages, and reduces service risk.
Visit www.SMA-America.com for more information.
SUPERIOR INTEGRATION .
WITH THE
POWER+'SOLUTION
L
D
Lin SfJlA%,PI
�IA Ir5lFSEa¢4f %
#1 INVERTER
o
r..........................................................................
Speed the completion of customer proposals and maximize the efficiency of your design
team with the Sunny Boy -US series, which provides a new level of flexibility in system
design by offering:
a Hundreds of stringing configurations and multiple independent MPPTs
a SMA's proprietary OptiTrac`M Global Peak shade mitigation technology
a Diverse application options including on- and off -grid compatibility
•.
SMA wants to enable your sales team by arming them with an abundance of feature/
i benefit support. Show your customers the value of the Sunny Boy -US series by utilizing:
a Secure Power Supply, now with 2,000 W of opportunity power in the event of a grid
outage, as an increased value -add or upsell opportunity
a SMA's 35 year history and status as the #1 global inverter manufacturer instills homeowners
with peace of mind and the long-term security they demand from a PV investment
a An economical solution for shade mitigation and the challenges of complex roofs
/..............................................................................................................:
Ensure that your back office business operations run smoothly and succinctly while
mitigating potential errors. The Sunny Boy -US series can help achieve cost savings in
these areas by providing:
• An integrated DC disconnect that simplifies equipment stocking and allows for a single
inverter part number
a All communications integrated into the inverter, eliminating the need to order
S
additional equipment
STREAMLINED INSTALLATION r COMMISSIO.......................................
6
f
�t
Expedite your operations in the field by taking advantage of the new Sunny Boy's
installer -friendly feature set including:
a Direct access via smartphone and utilization of SMAs Installation Assistant, which
B f
minimizes time/labor spent in the field and speeds the path to commissioning
a Improved communication —no need to install additional equipment
a Integrated DC disconnect that simplifies onsite logistics and eliminates the need to
install a separate disconnect unit, speeding overall installation time
.............................................................................................................:
"
... Uil
�e
<fi
..................................................................... .... .. .
SMA understands the factors that contribute to lifetime PV ownership cost, that's why
Sunny Boy designed for backstopped by
the -US series was maximum reliability and an
unmatched service offering. Benefit from:
a The now Sunny Boy's two-part enclosure concept that separates the connection unit
¢
from the power unit, which allows for simple, expedited servicing
a The #1 service team in the PV industry,as recognized b IMS research, with
8 � Y
experience servicing an installed base of more than 55 GW
l............................................................................................:
S
E .
J