HomeMy WebLinkAboutEVALUATION REPORT - UNDERLAYMENTSi
CREEK
TECHNICAL SERVICES, LLC
Manufacturer:
Quality Assurance:
SCOPE
Category:
Subcategory:
Code Sections:
Properties:
REFERENCES
DREXEL METALS, INC.
1234 Gardiner Lane
Louisville, KY 40213
(502) 716-7143
www.drexmet.com
UL LLC (QUA9625)
oofing _
Unde[layments
1507:11; 1'507:2:4.
Physical properties
Certificate of Authorization No. 29824
17520 Edinburgh Drive
Tampa, FL 33647
(813) 480-3421
FLORIDA BUILDING CODE, 6Te EDITION (2017)
Issued September 14, 2017
SCANNED,
at
Enti Report No. Standard Year
TrinityJERD (TST6049) C41280.10.12 ASTM D 1970 2015a
ICC-ES (EVL2396) ESR-2206 ASTM D 1970 2015a
PRODUCT DESCRIPTION AND APPLICATION
MetShield MetShield is a coated-polyolefin-composite film surfaced, self -adhered ASTM D 1970
underlayment for use on steep slope roofs.
Deck Type: Solid or closely fitted plywood sheathing for new or existing
construction. Plywood deck shall be installed in accordance
with FBC requirements. Roof decks shall have no more than
'/a° gap at abutting joints.
Min. slope: In accordance with FBC requirements
Attachment method: Underlayment shall be attached in accordance with the FBC
Table 1507.1.1 and manufacturer's installation instructions.
Min. application temperature: 40°F. Contact the manufacturer when installing at temperatures
below 40°F. '
Allowable roof coverings: Permitted to be used as prescribed' in FBC Table 1507.1.1 with
mechanically fastened roof coverings.
DRX13004.2 FL16342-R2 Page 1 of 2
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
i
CREEK DREXEL METALS,MetSh ® d
TECHNICAL SERVICES, LLC
LIMITATIONS
1) This evaluation report is not use in the HVHZ.
2) Fire Classification is not within the scope of this evaluation.
3) Wind uplift resistance in not within scope of this evaluation.
4) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturers published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
6) MetShield may be used as described in other current FBC product approval documents.
7) MetShield shall not be used with adhered tile roof coverings nor installed over existing roof coverings.
8) MetShield shall be exposed on the roof deck for a maximum duration of 30 days.
9) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 6t' Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer.
,t'�RY IR I�p,04'ei
%
......
�.
No 74021
-
00.
STATE OF :�[u
.�,,n"1,.N� O R 1 Q Q•,: N.
��'�SSi�NALE?���
�flllltii
CERTIFICATION OF INDEPENDENCE
2017.09.14
.16:26:20
04'00'
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
• DRX13004.2 FL16342-R2 Page 2 of 2
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
Certificate of Authorization No. 29824
17520 Edinburgh Drive
Tampa, FL 33647
j TECHNICAL SERVICES, LLC
(813) 480-3421
EVALUATION REPORT
FLORIDA BUILDING CODE, 6T"EDITION (2017)
Manufacturer: DREXEL METALS, INC.
Issued September 14, 2017
1234 Gardiner Lane
Louisville, KY 40213
(502)716-7143
www.drexr6et.com
Quality Assurance: UL LLC (QUA9625)
SCOPE
Category: Roofing
Subcategory: Underlayments
Code Sections: 1507.1.1, 1507.2.4
Properties: Physical properties
REFERENCES
Enti Report No.
Standard Year
TdnitylERD (17ST6049) C41280.10.12
ASTM D 1970 2015a
ICC-ES (EVL2396) ESR-2206
ASTM D 1970 2015a
PRODUCT DESCRIPTION AND APPLICATION
MetShield MetShield is a coated-polyolefin-composite film surfaced, self -adhered ASTM D 1970
underlayment for use on steep slope roofs.
Deck Type: Solid or closely fitted plywood sheathing for new or existing
construction. Plywood deck shall be installed in accordance
with FBC requirements. Roof decks shall have no more than
'/a" gap at abutting joints.
Min. slope: In accordance with FBC requirements
Attachment method: Underlayment shall be attached in accordance with the FBC
Table 1507.1.1 and manufacturer's installation instructions.
Min. application temperature: 40°F. Contact the manufacturer when installing at temperatures
below 40°F.
Allowable roof coverings: Permitted to be used as prescribed in FBC Table 1507.1.1 with
mechanically fastened roof coverings.
DRX13004.2 FL16342-R2 Page 1 of 2
This evaluation report Is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
j
CREEK DREXEL METALS, INC.
MetShield
TECHNICAL SERVICES, LLC
j LIMITATIONS
1) This evaluation report is not use in the HVHZ.
2) Fire Classification is not within the scope of this evaluation.
3) Wind uplift resistance in not within scope of this evaluation.
4) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturer's published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
6) MetShield may be used as described in other current FBC product approval documents.
7) MetShield shall not be used with adhered tile roof coverings. nor installed over existing roof coverings.
8) MetShield shall be exposed on the roof deck fora maximum duration of 30 days.
9) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 6t' Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer.
-.0" VkY IR 11p���,',
E
.���tiP' �'� C •NSF •' `��' ���
No 74021
:p0:• STATE OF •:��
ess;O
CERTIFICATION OF INDEPENDENCE
_....._ 2017.09.14
t�5--' 16:26:20
..a,-041001
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved In the approval process of the
product.
END OF REPORT
DRX13004.2 FL16342-R2 _ Page 2 of 2
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
EVALUATION REPORT
I
Manufacturer:
Quality Assurance:
SCOPE
DREXEL METALS, INC.
1234 Gardiner Lane
Louisville, KY 40213
(502)716-7143
www.drexmet.com
UL LLC (QUA9625)
Certificate of Authorization No. 29824
17520 Edinburgh Drive
Tampa, FL 33647
(813)480-3421
FLORIDA BUILDING CODE, ST" EDITION (2017)
Issued September 14, 2017
Category:
Roofing
Subcategory:
Underlayments
Code Sections:
1507.1.1. 1507.2.4
Properties:
Physical properties
REFERENCES
Enti
TrinityJERD (TST6049)
ICC-ES (EVL2396)
PRODUCT DESCRIPTION AND APPLICATION
Report No. Standard Year
C41280.10.12 ASTM D 1970 2015a
ESR-2206 ASTM D 1970 2015a
MetShield
MetShield is a coated-polyolefin-composite film surfaced, self -adhered ASTM D 1970
underayment for use on steep
slope roofs.
Deck Type:
Solid or closely fitted plywood sheathing for new or existing
construction. Plywood deck shall be installed in accordance
with FBC requirements. Roof decks shall have no more than
'/a" gap at abutting joints.
Min. slope:
In accordance with FBC requirements
Attachment method:
Underlayment shall be attached in accordance with the FBC
Table 1507.1.1 and manufacturer's installation instructions.
Min. application temperature:
40"F. Contact the manufacturer when installing at temperatures
below 40°F.
Allowable roof coverings:
Permitted to be used as prescribed in FBC Table 1507.1.1 with
mechanically fastened roof coverings.
DRX7 3004.2 FL16342-R2 Page 1 of 2
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
l
C R E E K DREXEL METALS, INC.
MetShield
TECHNICAL SERVICES, LLC
LIMITATIONS
I
1) This evaluation report is not use in the HVHZ.
2) Fire Classification is not within the scope of this evaluation.
3) Wind uplift resistance in not within scope of this evaluation.
4) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturers published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
6) MetShield may be used as described in other current FBC product approval documents.
7) MetShield shall not be used with adhered the roof coverings nor installed over existing roof coverings.
8) MetShield shall be exposed on the roof deck for a maximum duration of 30 days.
9) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 6t' Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer.
%%--\. . R. p. -1
2017.09.14
Q. •' \ c E N s ,• �.�,��
ti �•''•'"- 16:26:20
No 74021
04'00'
1):.• STATE OF it/ Zachary R. Priest, P.E.
•'O� N�,�� Florida Registration No. 74021
Organization No. ANE9641
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
DRX13004.2 FL16342-R2 _ Page 2 of 2
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.