HomeMy WebLinkAboutEVALUATION REPORT - MODIFIED BITUMENEXTERIOR RESEARCH & DESIGN, LLC. ' Certificate of Authorization #9503 \J TRI Fry I ERD 353 Christian Street Oxford, CT 06478 (203)262-9245 !EVALUATION'REPORT TRI-BUILT Materials Group, LLC I(CAJYNEL, Evaluation Report A42970.10.12-R2 'PO Box 70 BY FL16027-R2 Rutherford, NJ 07070 39 Lucie coUn Date of issuance: 20/23/2012 1(800) 516-1485 Revision 2: 09/25/2017 'SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, 'P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for compliance with the 6th Edition (2017) Florida Building Code sections noted herein. IDESCRIPTION: TRI-BUILT Modified Bitumen Roof Systems iLABELING: Labeling shall be in accordance with the requirements the. Accredited Quality Assurance Agency noted ,herein. (CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. Trinity.1 ERD_ requires a complete :review of this !Evaluation Rep.ort.relative.to=updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words `Trinity I ERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall. be provided to the..user by the manufacturer or its distributors and shall be available for inspection at the job site at the. request of the Building Official. This Evaluation Report consists of pages 1 through 4, plus a 26-page Appendix. 'Prepared by: ,Robert J.M. Nieminen, P.E.. Florida Registration No. 59166, Florida DCAANE1983 The facsimile seal appearing was authorized by Robert Nieminen, P.E. on 09/25/2017. This does not serve as aneiectmnlcally signed document. (CERTIFICATION OF INDEPENDENCE: 1. Exterior Research & Design, LLC. d/b/a Trinity I ERD does nothave, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates: 2. Exterior Research & Design, LLC. d/b/a Trinity 'I ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. i4. Robert Nieminen, P.E: does not have, nor will acquire,.a financial interest in any other entity involved in the approval processof the product. ,5. This is a building code evaluation. Neither Trinity ERD nor Robert Nieminen, P.E. are, in any way, the Designer of. Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or.design guidance unless retained specifically for that purpose. QOTRINITYIERD ROOFING SYSTEMS EVALUATION: I. SCOPE: Product Category: Roofing Sub -Category: Modified' Bitumen Roof Systems-. Compliance Statement: TRI-BUILT Modified Bitumen Roof Systems, as -produced; by TRI=BUILT Materials Group, LLC, have demonstrated compliance with the'foliowing sections of the • 6'h Edition (2017) Florida Building Code through, testing" in accordance with the following Standards.. Compliance is subject to the Installation Requirements and Limitations / Conditions of Useset forth herein. 2.. STANDARDS: Section ProperLV Standard Year 1504.3.1 Wind FM 4474 2011 1504.7 Impact Fm 4470 2012 1507.11.2 Physical Properties ASTIVI D6163 2008 1507:11.2 Physical-Properties ASTM D6164 2011 1507:11.2 Physical Properties ASTM 156222 2011 3. REFERENCES: kn2tf Examination Reference Date ERD (TST6049) Physical. Properties P10490.10.08-2 10/30/2008 ERD (TST6049) FM4470/4474 013760.09.09 09/10/2009- ERD (TST6049) FM 4470/4474 P13770.09.09 09/10/2009 ERD (TST6049). FM 447014474 P30540.1109-R1 11/30/2009 ERD;(TST6049) FM 4470/4474 P30550.12:09 12/02/2009 ERD (TST6049) Physical. Properties 1333960.12.10 12/30/2010 f RD' (TST6049) FM 44710/4474 P33970.03.11 03/15/2011 ERD (TST6049) Physical Properties P37590.03.13-3A 03/06/2013 ERD (TST6049) FM 4470/4474 P39680.03.13 03/04/2013 ERD (TST6049) Physical Properties P37590.0313-1-R1 06/26/2013 ERD (TST6049). Physical Properties 087590.03:13-2-R1 07/01/2013 ERD..(TST6049) Physical Properties P37590.07.13=2 07/01/2013 ERD (TST6049) Physical Properties P37590.03.13-5-R1 07/0l/2013 ERD (TST6049). Physical Properties P37590.07.13-1 07/02/2013 ERD (TST6049) Physical Properties 045§40.09.13 09/04/2013 ERD.(TST6049) Physical Properties P44370.10.13 10104/2013 FM Approvals (TST1867) FM 4470 2W7A7.Am 08/04/1994 FM Approvals (TST1867) FM 4470 0D3A3.AM 04/04/1997 FM Approvals (TST1867) FM 4470 2D0A0.AM 12/23/1998 FM.Approvals.(TST1867) FM 4470 2D5A9.AM 06/22/1999 FM Approvals (TST1867) FM 4470 3006646' 01/04/2000. FM Approvals (TST1867)' FM 4470 .3001334 01/25/2000 FM Approvals (TST1867)' FM 4470 3001334 02/15/2000 FM Approvals.(TST1867) FM.4470 3000857 01/12/2000 FM Approvals:(TST1867) FM 4470 3004091 01/1212000 FM Approvals (TST1867) FM 4470 3006115 05/02/2001 FM Approvals (TST1867) FM 4470 3012321 .07/29/2002 FM Approvals (TST1867) FM 4470 .3614692 08%05/2003 FM Approvals (TST1867) FM 44:70 ' 3014751 08/27/2003 FM Approvals(TST1867) FM 4470 3007170 01/13/2004 FM Approvals (TST1867) FM 4470 .3019317 06/30/2004 FM, Approvals(TST1867) FM 4470 3020703 07/30/2004 FM Approvals (TST1867) f 1VI 4470/4474 3018332 01/31/2006 FM Approvals (TST1861) FM.4470/4474 3023368 03/20/2006 FM Approvals (TST1867) FM 4470/4474 3024594 05/23/2006 Exterior Research and Design, L-C. Evaluation Report A42970.10.12-RZ C f' Af lcate of quthorkation #9503 e. EDITION (2017) FBC NON-HVHZ EVALUATION FL16027-R2 TRI-BUILT Modified Bitumen Roof Systems; (800),51&1485 Revision 2: M/25/2017 Page 2 of 4 111�/TRINo'Pl(I ERD Entity Examination Reference Date FM Approvals(TST1867) FM 4470/4474 3023458 07/1812006 FM Approvals(TSI1867) FM 4470/4474 3030668 09/12/2007 FM Approvals(TST1867) FM 4470/4474 3632172 06/12/2009 PRI.(TST5878) Physical Properties PUSA-06,2-02-01 12/04/2007 PRI(TST5878) Physical Properties PUSA-061-02=02 01/28/2008 iPRI ,(TST5878) Physical: Properties PUSA-064-02-02 o2j27/2008 PRI (TST5878)_ Physical, Properties PUSA-062-W-62 .12/64/2008 Miami -Dade (UR1592) HVHZ Compliance Various NOAs Various Miami-Dade(CER1592) ProposalforReview .10-0823 10/12/2010 UL LLC (QUA9625) Quality.Control MI -Agreement 02/27/2012 UL LLC (QUA9.625) Quality Control ML Correlation,. R27202 08/20/2012 UL LLC (QUA9625) Quality Control Service Confirmation, R14571 Exp.'10/06/2018 4. 'PRODUCT DESCRIPTION' This Evaluation Report covers TRI-BUILT Modified Bitumen Roof -Systgmsl installed in accordance with TRI-BUILT Materials Group; LLC published installation instructions and :the Limitations / Conditions of Use herein: The following membranes make up -the subject systems. 5. Table 1 Roll -Goods for TRLBUILT Modrfled Bitumen Roof Systems Type Product Specification Reference Grade Type SBS Membranes TriBuilt ;SA SBS Base ASTM D6163, Table 2 S 1 TriBuiltSBS Granular- ASTM D6164 G I TriBuilt SA SBS Cap ASTM D6164 G I APP Membranes TriBuilt ARP Smooth ASTM D6222 S I TriBuilt APP'Granular ASTM D6222 G 1 Tribuilt SA APP Cap ASTM D6222 G :I LIMITATIONS: 5.1 This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions,thereof, is/was used for permitting or design guidance unless retained specifically for that,purpose. 5.2 This Evaluation Report is'not for use in. FBC HVHZ jurisdictions. 5.3 Refer to a current Approved. Roofing Materials Directory for fireratingsofthis, product . 5.4 For steel deck installations, foam plastic: insulation shall be,separated from the building interior in. accordance with FBC 2609.4 unless the exceptions stated in FBC 2603.4.1 and 2603.6 apply., 5.5 The roof .system evaluation herein pertains to above -deck roof components. Roof decks, and structural members shall be in accordance with FBC requirements to. the satisfaction of the Authority Having Jurisdiction. Load resistance .of :the roof deck shall be documented. through proper codified and/or FBC Approval documentation. 5.6 For recover installations, the existing, roof shall be examined in -accordance with FBC 1511. 5.7 For rnechariically attached insulation .or membrane orstfip-bonded;.insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1.design pressure determined in accordance with FBC Chapter .16. Zones. 2 and. 3 shall employ an attachment density designed by a .qualified` design professional to. resist the: elevated pressure criteria.. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention: Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked; with :an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention DataSheet 1-29,(January.2016)1orZone 2/3 enhancements. Exterior Research and Design, LLC: Certificate of Authorization #9503 e, EDITION (2017) FBC NON-HVHZ EVALUATION TRI-BUILT Modlfied.'eirumen Roof Systems; (800) 516-1485 Evaluation Report A42970.10.12-RZ FL16027=R2 Revision 2: 09/25/2017 Page 3 of 4 ' e TRINITYJERD 5.8 For assemblies with all components fully bonded :in place, the maximum design pressure for the selected. assembly.shall meet or exceed r critical design pressure determined in accordance with FBC Chapter 16. No rationalanalysis is permitted for these systems. 5.9 For mechanically attached insulation; or membrane over existing roof decks; fasteners shall. be tested in the existing deck for withdrawal -resistance. A qualified design professional shall review the data for comparison to -the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105. 5.10 For bonded.insulation or membrane over existing substrates in a re -roof (tear off.) or recover installation, the existirig'clkk or existing roof surface shall be.examined for compatibility with the. adhesive to: be installed'. if any surface conditions exist that bring system performance into. question, field uplift testing.in accordance with ANSI/SPRI IA-1,, ASTM. E907, FM Loss. Prevention. Data Sheet 1-52 or Testing Application Standard TAS 124 shall be conducted on mock-ups, of the proposed new roof assembly. 5.11 For bonded insulation or membrane over existing substrates in a recover installation, the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having.Jurisdiction, as documented;through field uplift'testing.in accordance with ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing, Application Standard TAS 124. 5.12 Metal edge attachment (except gutters), shall be<designed and installed for wind loads in accordance with FBC Chapter 16' and tested for resistance.in a ccorda rice, with ANSI/SPRI ES-1.or Roofing: Application, Standard RAS: 111, except the basic wind speed shall be .determined from FBC Figure 1609.3(1); 1609.3(2) or 160.9.3(3). 5.13 All products in the .roofassembly shall`have quality assurance in accordance'with FAC Rule.61620-3. 6. INSTALLATION: 6.1 TRI-BUILT Modified Bitumen RoofSystems shall be installed in ;accordance with TRI-BUILT Materials Group, LLC-published', installation instructions; subject to the [imitations/ Conditions:of Use noted below. 6.2 System attachment requirements for wind load resistance are -set forth in Appendix 1. "MDP" = Maximum Design Pressure is the .result of testing for wind load resistance.based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the .2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to. FBC 1609 for determination of design wind loads. I7. BUILDING. PERMIT REQUIREMENTS: As required by the Building' Official or Authority Having Jurisdiction: in order to properly -evaluate the installation of this product. 8. MANUFACTURING PLANTS: Contact the noted QA ;agency for information on product locations 'covered. for 'F.A.C. Rule 61G20-3 QA requirements. �9. QUAdf i ASSURANCE ENTITY: ULLLG QUA9625; (314) 578w3406i 'k.chancellor@us.ul.com - THE 26=PAGES THAT FOLLOW FORM PART OF THIS EVALUAnON REPORT - E�Wior Research and Design, .C. Evaluation Report A42970.A0.12-112 Certificate ofAutfiorization 0503 6T" EDITION (1017) FBC NOWkVHZ EVALUATION F1.16027-112 TRI-BUILT Modified Bitumen koof Systems; (800) 516-1485 \ Revision 2: 09/25/2017 Page 4 of 4 TRINITYIERD APPENDIX 1:'ATTACHMENT REQUIREMENTS FUR WIND UPLIFT RESISTANCE Table Deck Application Type Description, Page 1A-1 Wood. New Or Reroof (Tear -Off) A-2 Mech. Attached,AnchorSheet, Bonded Insulation, Bonded Roof Cover A 1A-2 Wood New;. Reroof (Fear-Off)or-Recover A-2 Mech. Attached Anchor.Sheet, Bonded Insulation, Bonded Roof Cover" 5 18' Wood New, Reroof (Tear -Off) or Recover. 8 Mech: Attached Base Insulation, Bonded Top Insulation; Bonded Roof Cover 5 1C Wood New, Reroof.(Tear--Off or Recover C Mech..Attached Insulation,,BondedRoof Cover 6 1D Wood New, Reroof (Tear -Off) or Recover D. Prelim: Attached Insulation, Mech. Attached Base.Sheet,.Bonded Roof Cover 6 1Er1. Wood New or Reroof (Tear -Off) E Non -insulated, Mech. Attached Base Sheet, Bonded Roof Cover 7 lE-2 Wood New, Reroof (Tear=Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 8 SF ` Wood New or Reroof (Tear=Off) F , Non -Insulated Bonded Roof.Cover 24 Steel or Structural concrete New; Reroof (Tear -Off) or Recover e. Mech. Attached Base Insulation; Bonded Top Insulation, Bonded Roof Cover 9 2B Steel or Structural concrete* New, Reroof(Tear-Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 9 2C Steei orSt_ructural concreteNew, Reroof (Tear -Off) or Recover D Prelim, Attached Insulation, Mech. Attached. Base Sheet, Bonded Roof Cover 10 3A Structural concrete New or Reroof'(Tearv(jff), A-1 Bonded Insulation, Bonded Roof Cover 11-14 3B; Structural concrete New or Reroof (T.ear--Off) F Non -Insulated, Bonded. Roof Cover 14 4A LWIC, New or Reroof (Tear -Off) A-1, Bonded Insulation, Bonded Roof Cover '15-16 48 LWIC New or Reroof (Tear -Off) A-2 Mech, Attached Anchor Sheet;, Bonded Insulation, Bonded Roof Cover 16 4C LWIC New be Reroof (Tear-O.ff) E Non -Insulated, Mech, Attached Base.Sheet, Bonded Roof Cover 17=19 5A CWF New or Reroof (Tear -Off) A-1 Bonded Insulation; Bonded Roof Cover 20 5B. CWF New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded insulation; Bonded Roof'Cover 21 5C CWF New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 22 SD CWF New, Reroof (Tear-Off)°or Recover C Mech. Attached Insulation, Bonded Roof Cover 22 SE CWF New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 22 6A „Gypsum New or Reroof (Tear -Off) A-1 Bonded Insulation,, Bonded Roof Cover- 23 60 Gypsum New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded insulation, Bonded Roof Cover 24. 6C G,ypsum New, Reroof (Tear -'Off) or Recover C Mech. Attached Insulation; Bonded Roof Cover 24 6D Gypsum,' New; Reroof (Tear -Off) or Recover E Non-Insulated,Mech. Attached Base Sheet, Bonded Roof Cover 24 7A Various Recover A-1 Bonded Insulation, Bonded Roof Cover 25-26 78 Various Recover F Non -Insulated, Bonded Base Sheet, Bonded Roof Cover 26 The following.notes.apply to the systems outlined herein: 1. The roof system evaluation herein pertains to above -deck roof,components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction -of the Author ity- Having ,Jurisdiction. Load -resistance of the roof deck, shall be documented through proper codified and/or.FBCApproval documentation. 2, Insulation /"base sheet fasteners shall be of sufficient length forthe following deck engagement: D Wood;. Minimum 0.75-incfipenetration.. Steel: Minimum 0.75.-inch penetration and engagethe top.flute, of the steel deck.- > Structural concrete; Minimum,l-inch embedment into pilot hole in accordance with fastener manufacturer's published installation instructions[ 3: Unless otherwise noted, insulation may be any one layer or combination of polyisocyanurate, polystyrene, wood fiberboard, perlite; gypsum -based roof board or mineral -wool roof board that meets the QA requirements of F.A.C. Rule 61G20-3 and.'is documented as meeting FBC,1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover. Exterior Research and Design, I.I.C. d/b/a Trinity( ERD Evaluation Report A42970.10s12-R2 for FL16027-R2 Certificate, of Authorization #9503 6'" EDITION'(2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen; PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 1 of 26 TRINITY I ERD Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D (mechanically.attached base sheet, bonded. roof cover), whereby the base sheet fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be.of equal or greater configuration to the steel and concrete deck listings. Roof decks and structural members shall be in accordance with FBC requirements to the. satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shali be documented through proper codified and/or FBC Approval documentation. S. Preliminaryinsulation attachmentfor System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 bf'FM Loss Prevention Data Sheet 1-29 (January 2016). Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width' is at the time of application; the ribbons/beads shall expand as noted in the manufacturer's published instructions. ➢ HA (HA): Full coverage at 25-30 lbs/square. ➢ Dow INSTA STIK-Quik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1-inch wide "ribbons, 12-inch o:c. Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-Inch wide ribbons, 12-inch-6.c. D OMG OlyBond 500 (013500): Continuous 0.75 to 1-Inch wide ribbons, 12-inch o.c. (PaceCart or SpotShot). Note: OlyBond Green maybe used where OlyBond 500 is referenced. OlyBond. Classic (08 Classic): Full coverage at 1 gal/square. ➢ ICP Adhesive &Sealants CR40: Continuous 2.5-3.5-inch wide ribbons,,l2-inch o.c. ➢ Note: When,multlple loyers(s) of insulation and/or coverboard are installed in ribbon -applied adhesive, adhesive ribbons shrillbe staggered from layer -to -layer a distance of one -hot theribbon spacing. Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the speclfled ribbons spacing: Unless otherwise noted, allinsulations are flat stock or taper board ofthe minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substitutedwith the following Maximum Design Pressure (MDP) limitations. In no case shall these values be used to 'Increase' the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then the thinner board listed below may be used as.a drop -In for the equivalent thicker material listed In the table: Millennium One Step.Foamable Adhesive'(M-OSFA): MDP -157.5 psf (Min. 0.5-inch thick) OMG-OlyBond 500 (013500): MDP -45.0 psf (Min.0.5-inch thick Multi -Max FA-3) ➢ OMG OlyBond 500 (013500): MDP -187.5 psf '(Min. 0.5-Inch thick ISO 95+ GL) OMG OlyBond 500 (08500): MDP -315.0 psf (Min. 0.5-inch thick ENRGY 3) OMG OlyBond 500 (OB500): MDP -487.5 psf (Min. 0.5-inch thick ACFoam II) ➢ ICP Adhesive & Sealants CR-20 MDP -117.5 psf (Min.1.0=Inch thick) 8. Bonded polyisocyan u rate insulation boards shall be maximum 4 x 4 ft. 9. For mechanically attached'components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the'Zone.1 design pressure determined in accordance with FBC Chapter 16, and Zones 2 and..3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention.Data Sheet 1-29; Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137._Assemblies marked with•an asterisk* carry the limitations set forth In Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 213 enhancements. 10. For fully bonded assemblies, the maximum design pressure for the selected assembly shall meet or exceed, critical design pressure determined in accordance with FBC Chapter 16, and no. rational analysis is permitted. 11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105. 12. For existing substrates in a bonded'reco'vee or ee-roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and band.performance with the selected adhesive, and the existing roof system (for recover) shall be -capable of.resisting project design pressures on its own merit'to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with ANSI/SPRI IA-1, ASTM E907, FM Loss. Prevention Data Sheet 1-52 or Testing Application Standard TAS 124. 13. For Recover Applications using System Type D, the insulation is optional; however, the existing roof system shall be suitable for a recover application. 14, Lightweight Insulating Concrete (LWC) shall be cast in accordance'with, FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced, refer to current LWC Product. Approval for specific deck construction and limitations. For systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat thickness is 2-inches. For LWCover structural concrete; reference Is'made to FBC Section 1917.4.1, Point 1. Exterior Research and Design, LLC. d/b/a Trinityl ERD Evaluation Report A42970.10.12-R2 for FL16027-R2 Certificate of Authorization H9503 6711 EDITION (Z017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems, (800) 526-1485 Appendix 1, Page 2 of 26 15. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications. TAsl:e1 TRI BUILT RooF,CovERs`, a z Reference Layer Material Application BP=AA (Base and Ply sheets, Asphalt -Applied) Base Ply FBC Approved ASTM D4601, Type II HA at 20-40 Ibs/square Ply FBC Approved ASTM D2178, Type IV or VI SBS-AA (SBS, Asphalt -Applied) Cap Ply TrIBUIit SBS Granular HA at 2040 Ibs/square SBS-TA. (SBS, Torch -Applied) Cap Ply TriBuilt SBS Granular Torch -Applied SBS-SA (SBS, Self -Adhering) Base Ply TriBuilt SA SBS Base Self -Adhering 'Cap Ply TriBuilt SA SBS Cap APP-TA APP, Torch A Iled ( pp ) Base Ply or Ply TriBuIlt APP Smooth Torch -Applied Cap Ply TriBuilt APP Smooth, TriBuilt APP Granular APP-SA. (APP, Self -Adhering) Cap Ply y Tr1BulItSA APP Cap Self -Adhering 16. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following. Maximum Design Pressure (MDP) limitations, The lesser of the. MDP listings below vs. those in Table 3A applies: ,VAP611 BARRIER QPT16N5 i Tni6 URAL;CONCRETE DECif, ADHERED INSULATION PER TABLE 3A' '' - `•'. . ` �: - v `' a '- Option # Primer Vapor Barrier Insulation Adhesive, M(pDP s fl Type Attach VB-1. ASTM D41 TriBuilt SA SBS Base Self -Adhering. Inta-Stik or CR-20,12-inch o.c. -60.0 VB-2. ASTM D41 TriBuiltSA SBS Cap Self -Adhering Insta-Stik,12-inch o.c. -75.0 VB-3. ASTM' D41 TriBui(t.SA SBS Cap Self -Adhering Millennium One Step Foamable Adhesive, 12-inch o.c. -157.5 VB-4. ASTM D41 TriBuilt SA SBS Cap Self -Adhering CR-20,12-inch o.c. -270.0 VB-5. ASTM D41 TriBuilt 5ASB5 Base Self -Adhering Millennium One Step Foamable Adhesive, Millennium PG-1 Pump Grade Adhesive, OlyBond 500 or CR-2Q 12-inch. o.c. -290.0 17. Dens Deck shall be field -primed with. P6100 prior to self -adhering membrane application. Refer to tables herein for other priming requirements. 18. "MDP Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of designwind.loads. Exterior Research and Design, U.C. d/b/a Trinity( ERD - Evaluation Report A42970.10.12-R2 for FL16027-RZ Certificate of Authorization #9503 6M EDITION (2011) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared' bya Robert Nieminen; PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 3 of 26 i t �JTRINITY I ERD TABLE 1A 1 WOOD DECKS NEW CONSTRUCTION oR R.gROOF (TOO-OeF) a 'A SYSTEIyi TYPE -A 2 M,ECHANICALLY ATTACHED ANCHOR SHEET BONDED INSULATION BONDED ROOFCOVER System Deck Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP No. (Note'1) Type Fasteners Attach Type Attach Type Attach Base Ply Ply Cap Ply (psf) Min. A.25-inch Dens Polyglass G2 Base, 8-Inch o.c. in 4- Deck, Dens Deck Prime, Min. 19/32- CertainTeed Glasbase, 32 ga.,1-5/8- Inch lap and 8- (Optional) FBC SECUROCK ,Gypsum - Inch yw I ood p Firestone MB Base, JM inch diameter inch o.c. in Approved, Fiber Roof Board, Min. (Optional) SOS -AA, W=1 acmax. 24- Perma-Ply 28, Tamko tin caps with 11 three; equally ASTM C1289, HA 0.75-inch FescoBoard HA BP -AA BP-AA SBS-TA, -60.0 inch spans Glass Base or ga. annular ring spaced, type II polylso- (homogeneous) or min, APP-TA GAFGLAS #i75 shank nails staggered cyanurate 0.5-Inch Structodek center -rows High Density Fiberboard Roof Insulation Polyglass G2 Base, 84nch o.c. in 4-- Min.19/32- CertainTeed Glasbase` 32 ga.,1-5/8- Inch lap and 8- (Optional): FBC . Min0:25-inch Dens (Optional) SBS-SA ' inch plywood Firestone MB Base, JM inch diameter inch o.c. in Approved; Deck, Dens Deck Prime, One or APP-SA, W-2 at max: 24- Perma-Ply 28,-Tamko tin caps with 11 three; equally ASTM C1289, HA SECUROCK Gypsum- HA 585-SA more 5B5- SBS-TA or 60.0 inch spans Glass Base or ga. annular ring spaced, type 11 polyiso- Flber Roof Board SA or APPTA GAFGLAS V5 shank nails staggered cyanurate APP-TA center rows 6-Inch c.c. In 4- Min 2 inch D-IS, 08500, Min. 19/32- 32 ga.,1-5/8- inch lap and 6- ACFoam Ii, III, CR-20 or M- Min. 0:25-inch Dens D-IS, Inch plywood Polyglass Elastobase inch diameter inch o.c: in H-Shield, H- OSFA, atop Deck, Dens Deck Prime OB500, (Optional) SBS-AA, W-3 at max. 24- or Polyglass tin capswithl2 four, equally Shield CG, fastener or SECUROCK Gypsum- CR-20 or BP -AA BP -AA SBS-TA, -60.0* Inch spans Elastobase Poly Sq. annular ring spaced, Multi -Max FA3 rows; 7-inch Fiber Roof Board M-OSFA APP TA shank nails staggered center rows or ENRGY-3 cc 6-inch o.c. in 4- Min.2 inch D IS OB500, Min.19/32- 32 ga.,1-5/8- inch lap and 6-(Optional) ACFoam li III, CR 20 or M- D-15, SBS-SA, Inch plywood Polyglass Elastobase inch diameter inch o.c. in H-Shield, H- OSFA, atop (Optional) Additional OB500, One or APP-SA, W-4 at max. 24- or Polyglass tin caps with 12 four, equally Shield CG, fastener layers of base insulation CR-20 or SBS-SA more SBS- SBS-TA or -60.0* inch,spans- Elastobase Poly ga.. annular ring spaced, Multi -Max FA3 rows,.7-inch M-OSFA SA or APP-TA shank nails staggered or E,NRG,Y.-3 oc APP-TA center rows Exterior Research and Design, I.I.C. d/b/a Trinity( ERD Evaluation Report A42970.10.12-R2 for FL16027-R2 Certificate of Authorization 99503 6'H EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 4 of26 TRINITY11 ERD F) 6 R Il t qpV,E)R HEEI�130NDEDJNSUAA SYSTEM ,TYPE ,A ?MECHANIC-ALLYATTACHED ANCHDR SLTION,WN EUROOF COVER ;" System Deck Anchor Sheet Base Insulation Top Insulation Roof Cover (NoteIS) MDP No. (Note 1) Type Fasteners Attach Type Attach Type Attach Base Ply Ply rap Ply (Psf) 12-inch o:c. in 4- 25-i 0.nc Min. �.. h Dens Deck, Mim 19/32- Polyglass OMG Flat Inch lap and 12- (optional) FBC Dens Deck Prime, SECUROCK W-5. inch.plywood Elastobase or Polyglass Bottom Plates Inch o.c. in two, Approved, ASTM Gypsum -Fiber Roof Board, . (Optional) 5BS-AA, SBS- at max. 24- (square) with equ0yspaced, C1289, , HA Min. 0.75 inc h FescoBoard HA BP -AA BP -AA TA, APP-TA -60.0 inch spans Elastobase Roofgrip #12 staggered center type 11 poly iso- (homogeneous) or m In. 0.5- Poly cyanurate inch Structodek High Density I rows Fiberboard Roof Insulation Min. 19/32- Polyglass OMG Flat 12-inch o.c. in.4- inch lap and'I . 2- (Optional) FBC (optional) Inch plywood Elastobase:or Bottom Plates Inch 6,c. in two, . Approved, Min. 0.25-inch Dens Deck, One,or SBS-SA, APP- W-. 6 at max. 24- Polyglass (square) with equally spaced, ASTM C1289, HA Dens Deck Prime. SECUROCK HA SBS-SA more SBSz SA, SB5­TA -60.0 Inch spans Elastobase Roofgrig#12 staggered center type 11 polylso- Gypsum -Fiber Roof Board SA or ARP- or APP-TA Poly cyanurate TA I I rows TABLE,113:,W WOOD DECKS -'NEW NlSTk1U&lOINl­R'EF SYSTEM .TYPE,B:'MECHANICALLYAfTACHEIBASE INSULATION, BONDEDT RINSULATION,'BONDEqR00F!q0V9 System Deck (Note 1) Base Insulation Laver Top Insulation Layer Roof Cover (Note 15) M DO No. Type Fasteners Attach- Type Attach Base Ply Ply Cap Ply (Psi '— Min. 19/32-Inch Min. 1.5-Inch Dekfast Hex with Min. 0.75-Inch Fescogoard (Optional If (Optional if using W-7 plywood at max. 24-inch ENRGY 3� HrShleld Dekfafst #12 or TruFas t 1 per ft2 (homogeneous) or min. 0.5-inch HA using AA Ply) AA Base) One or SBS-AA, 5BS-TA, -60.0 spans or Polytherrn MP-3 with TruFa-st DP 1. 33 Structodek High Density Fiberboard BP -AA more BP -AA or APP-TA Roof Insulation APP-TA Exterior Research and Design, LLC. d/b/a Trinityl ERD Evaluation Report A42970.10.12-R2 for FL16027.R2 Certificate of Authorization U9503 C"EDITIQN (2017) FBC NON-HVHZ EVALUATION Revision 2:09/25/2017 Prepared by: Robert Nie'minen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-14.85 Appendix 1, Page 5 of 26 TRINITYIERD TABLE TC - 0D DECKS 7 plIC: kHAMCALLYAft ACHE)f S, LATION, B91SIDERROQFWVER` System Base Insulation Top Insulation Layer Roof Cover (Note 15) MDP No. Deck (Note 1) Layer (psfi type Fasteners Attach Base Ply Ply Cap Ply; Min. 19/32-Inch (Optional) Min. 0.5-Inch Structodek High Density DeVot Galvalume (Optional if (Optional If using AA W-8 plywood at Max. One or more layers, Fiberboard Roof Insulation or min. 0.25- Steel Hex with 1 per 1.33 2 using AA Ply) Base) One,or more BP -AA SBSrAA, SBS-TA, APP- -82.5 24 -inch spans any combination, inch Dens Deck, Dens Deck Prime or #12 DP ft BP -AA or AP PJA TA loose laid SECURO.CK.Gypsum-Fibe'r Roof Board:Dekfast (Optional) Dektast'Galvalume W-9 Mim 19/32-inch plywood at max. One or more layers, Min. 1.5-inch ENRGY 3, H-Shield or -Steel Hex with Dekfast #12 DP or 1 per 1.33 SBS-SA (Optional) One or more SBS-SA, APP-SA, SBS- -82.5 24rinch spans any combination, Polytherm TruFast MP-3 with ft2 SBS, SA or AP07TA TA or APP-TA loose laid TruFast DP °' TABLE;ID WOOD DECKS -;NEW CONSTRUCTION, REROOF (TEAe OFF) 611 RECOVER �IMEC ANICALLYATTACHkp,BASESHEET;BO DIED-RPPFCODER SYSTEM TYPE D:-PRELIMWAMILYATT HEDINSULATION,H .System Deck (Note 1) Insulation Layer(s) Base Sheet Roof Cover (Note 15) MDP Type Attach Base Fasteners Attach Base Ply Cap Ply No. "(psf) Polygless Elastobase, Polyglass OMG Flat Bottom Plates Min.19/32-Inch One or more layers, Prelim. Elastobase Poly, Polyglass G2 Base, (square) with Rbofgrip. 12-inch o.c. in 4-inch lip and 12- (Optional) One -,SBS-AA,. W-10 plywood at max.. any combination, Attached CertaInTeed Glasbase, Firestone MB #14, DekfastHex with Inch o.c. In two, equally spaced, or more BP -AA S13S-TA; -52.5 24-Inch spans Base, JM Perma-Ply 28, Tamko Glass Dekfast #14 or TruFast staggered center rows orAPP-TA APO -TA Base or GAFGLAS #75 MP-3 with TruFast HD Min. 19/32-Inch One,or more layers, Prellm. Oolyglass Elastobase or Polyglass Dekfast Hex with Dekfast 12-Inch o,c. In 4-Inch Jap,and 12- One or more SBS-SA, APP-SA, W-11 plywoodatmax. 24-inch-spans any combination Attached Elastobase Poly with poly top surface 414 orTruFast MP-3 with Inch o.c. in two, equally spaced, center SBS­5A SBS-T . A or -52.5* TruFast HD staggered rows APP-TA Min; 19/32-Inch One or more layers, Prelim. Polyglass Elastobase or Polyglass OMG Flat Bottom Plates 12-inch o.c. In 4-Inch NO and 12- (Optional) One SBS-AA, W-12 plywood at max. any combination Attached Elastobase Poly (square) with Roofgrip.#12 Inch o.c. in two, equally spaced, or more BP -AA SBS=TA, -60.0 �4-Inch spans staggered center rows or.APP-TA APP-TA Min. 19/32-Inch One or more layers, Prelim. Polyglass Elastobase or Polyglass OMG Flat Bottom Plates 12-inch o.c. in 4-inch lap and 12- One or more SBS-SA, APP-SA, W-13 plywood at max 24-Inch spans any combination Attached Elastobase Poly with poly top surface (square) with Rooferlp #12 Inch o.c. in two, equally spaced, SBS_SA SBS=TA or -60.0* staggered center rows APP-TA Exterior Research and Design, I.I.C. d/b/a TrifiltylERD r Evaluation Report A42970.10.12-R2'for FL16027-112 Certificate of Authorization 49503 e"EDITION (2017) FBC NON-HVHZ EVALUATION. Revision 1: 09/25/2017 Prepared by: Robert Nieminen,PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 5164485 Appendix 1, Page 6 of 26 �IjllI1'0( IERD (TEAR STEIVIT S A YPE:E!:NON-IN U TED,MECH S _N, kD BA ESHtET,'IBONCiE System Deck (Note 1) Base.Sheet Roof Cover (Note 15). IVIDP No. Base Fasteners Attach Base Ply Cap Ply (Psf) Mim 15/82Anch W-14 plywood at max, 24- Polyglass Elastobase -Simplex MAXX Cap 9-inch o.c. at 2-Inch lap and 18-inch o.c. in two, (Optional) BP -AA or 5121SAA, SEIS-TA -45.0* Inch spans equally spaced, staggered center rows APP-TA orAPP-TA 'Min. 15/32-inch W-15 plywood at max. 24. Polyglass Elastobase Simplex MAXX Cap 9-Inch o.c. at 2-inch lap and. 12-inch o.c. in two, (Optional) BP -AA or SBS-AA, SBS-TA -52.5 inch spans equally spaced, staggered center rows APP-TA or APP-TA Min. 19/32-inch Polyglass Elastobase, Polyglass Elastobase (Optional) One or W-16 plywood at max. Poly, Polyglass G2 Base, CertainTeed 32 ga., 1-5/8-Inch diameter tin caps &ihch o.c, in 4-inch lap and 8-Inch o.c. In three, SBS-AA, SBS- 24-inch spans Glasbase, Firestone MB Base, JM Perma- . with 11 ga. annular ring shank nails equally spaced, staggered center rows more,BP-AAor TA, APP-TA -60.0 Ply 28, Tamko G lass Base or GAFGLAS #75 APP-TA W-17 Min. 19/32-Inch plywood at max. Polyglass Elastobase or Polyglass . 32 ga., 1-5/8-Inch diameter tin caps 8-inch o.c. in 4-inch lap and 8-inch o.c. In three, (Optional) One or SBS-SA, APP- 24-Inch Elastobase base Poly with poly top surface with 11 ga. annular ring shank nails equally spaced, staggered center rows more,SBS-SA or SA; SBS-TA or -60.0 spans APP-TA .APP-TA Min, inch' W-18 at plywood at max. 24- Polyglass Elastobase Simplex MAXX Cap 6-Inch o.c. at 2-inch lap and 6-inch o.c. in two, (Optional) BP -AA or SBS-AA, SBS-TA -90.0 .inch spans equally spaced, staggered center -rows APP-TA orAPP-TA W-19 Min. 19/32-Inch plywood at max. Polyglass Elastobase or Polyglass 32 ga., 1-5/8-inch diameter tin caps 4-inch o.c. in 4-inch lap and 4-inch o.c. in four, (Optional) One or SBS-SA, APP- 24-inch Elastobase Poly with poly top surface with 11 ga. annular Ong shanknalls. - equally spaced, staggered center rows More SBS-SA or SA, SBS-TA or -97.5 spans APP-TA APP-TA Min. 15/32-Inch W�20 plywood at max. 24- Polyglass Elastdbase Simplex MAXX Cap 6-Inch o.c. at2-inch lapand 6-Inch o.c. In three, (Optio nal).SP-AAor SBS-AA, SEIS-TA _105.0 inch spans equally spaced, staggered center rows APP-TA o r A P P-TA W-21 Min. 19/32-Inch plywood at max. Polyglass Elastobase or Polyglass 32 ga., 1-5/8-inch diamer tin caps et 6-Inc . h 4-inch ld 6 o.c. in 4-ncap and o.c. infour, (Optional) one or SBS-AA,*SBS- 24-inch Elastobase Poly� with 11 ga. annular ring shank nails equally spaced, staggered center rows more BP -AA or TA, APP-TA -112.5 spans APP-TA Min. 19/32-Inch 32 ga., lm5/8-lnch diameter tin caps SSS-SA, APP- W-22plywood at max. Polyglass. Elastobase or Polyglass with 11 ga. annular ring shank nails. 6-Inch o.c. in 4-Inch lap and 6-Inch o.c. In four, (Optional) One or 24-inch spans Elastobase Poly with poly top surface Note: Tin caps are to be iidm6cl with equally spaced, staggered center rows more APP-TA SA, SBS-TA or -112.5 ASTIVI D41 primer. APP-TA Exterior Research and Design, LLC. d/b/a TrinityjERD Evaluation Report A42970.10.12-R2 for FI-16027-112 Certificate of Authorization #9503 6'"EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by; Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 7 of 26 QTRINITYIERD TABLE lE 2 WOOD DECKS NEW,CONSTRLICTION, REROOF (Teas OFF)`oR Recovee J SYSTENI'TYPE E NO INSULATED,•MECHANICALLYATTACHED BASE SHEET, BONDED RQOF COVER System Deck Base Sheet Roof Cover (Note 15) MOP No. (Note.l) Base Fasteners Attach Base Ply Cap Ply (Ps?) Min. 19/32-inch Polyglass Elastobase, Polyglass Elastobase OMG Flat Bottom Plates (square) with 12-inch o.c. in 4-inch lap and 12-Inch (Optional) One or W-1 plywood at max. Poly, Polyglass G2 Base, CertalnTeed Glastiase, Firestone MB Base, JM Perma- Roofgrip #14, Dekfast Hex with Dekfast #14 o.c: in two, equally spaced, staggered more BP -AA or SBS-AASBS , TA, APP-TA 52.5 24-inch spans Ply 28, Tamko Glass Base or GAFGLAS #75 orTruFast MP3 with TruFastHD center rows APP-TA Min. 19/32-inch Polyglass Elastobase or Polyglass Dekfast Hex with Dekfast #14 or TruFast MP- 12-inch o.c. In 4-inch lap and 12-inch One or more SBS- SBS-SA, APP- W-2 plywood at max. Elastobase Poly with poly top surface 3 with TruFast HD o.c. in two, equally spaced, staggered SA SA, SBS-TA or -52.5* 24-Inch spans center rows APP-TA Min. 19/32-inch Polyglass Elastobase or Polyglass OMG Flat Bottom Plates (square) 12-Inch o.c. In 4-Inch lap and 12--inch (Optional) One or SBS-AA,-TA SBS W-3 plywood at max, Elastobase Poly Roofgrip #12 o.c. in two, equally spaced, staggered more BP -AA or TA., APP- -60.0 24-Inch spans centerrows APP-TA Min. 19/32-inch Rolyglass.Elastobase or Polyglass OMG Flat Bottom Plates (square} with c .. 12-Inch oin 4-Inch lap and 12-Inch One or more SBS= SBS=SA, APP- W-4 plywood.at max. Elasfobase Poly with poly top surface Roofgrip #12 o.c, in two, equally spaced, staggered SA SA, SBS-TA or 60:0* 24-inch spans center rows APP-TA TABLE IF WOOD DECKS —NEW CONSTRUCTION oa REROOF (TEaa OFF) SYSTEM TYPE F NON=INSULATED, BONDED CIOF COVER'; . ?' System Deck Primer Roof Cover (Note 15) MDP Joint Treatment Base Ply Ply Cap Ply No. (Psfl 1N`5 Min. 15/32-lnWpiywood - (Optional) ASTM'D41 None, ', SBS-SA (0pti6nal) SBS-SA or, SBS-SA, APP-SA, SBS=TX -90:0 ,at max. 24-inch spans ;ARR-TA. or AP.P:T& W 6 Min.15/32-Inch plywood ptional) ASTM D41 (Optional) Plywood joints are covered with 4-inch wide strips,of TriBuilt SA TriBuilt•SA SB Base (Optional).SBS-SA or SBS-SA, APP-SA; SBS-TAB -9.7.5 at max. 24-incfi spans SBS Base, rolled into place to create continuous bond. APP-TA or APP-TA Exterior Research and Design, LLC, d/b/a Trinity IERD' Certificate of Authorization #9503 Prepared by: Robert Nieminen, PE-59166 bTM EDITION (2017) FBC NON-HVHZ EVALUATION TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Evaluation Report A42970.10.12-R2 for F1.16027-112 -Revision 2: 09/25/2017 Appendix 1, Page 8 of 26 y