FL # FL16027-R2 RECEIVED
Application Type Revision
Code Version 2017 Application Status Approved OCT 0 5 2018�
Comments
ST, Lucie County, Permitting m
Archived ❑
Product Manufacturer Tri-Built Materials Group, LLC
Address/Phone/Email PO Box 70
Rutherford, NJ 07070
david 516-1485 / O/O
david.ruiz@tribuiltmg.con�T LUCIE COUNTY BUILDING
RREVIEWED FOR COMPLI ON
Authorized Signature David Ruiz REVIEWED BY
david.ruiz@tri builtmg.corbATE
PLANS AND PERMIT MUST KEPT ON ]OB
Technical Representative David Ruiz SITE OR NO INSPECTION( ) WILL BE MADE
Address/Phone/Email 250 Route 17 North
East Rutherford, NJ 07073
(201)842-2449
david.ruiz@tribuiltmaterialsgroup.com
Quality Assurance Representative
Address/Phone/Email
Category
Subcategory
Compliance Method
Florida Engineer or Architect Name who developed
the Evaluation Report
Florida License
Quality Assurance Entity
Quality Assurance Contract Expiration Date
Validated By
Certificate of Independence
Referenced Standard and Year (of Standard)
C Richard Schurman
9050 Louisiana Street
Merrillville, IN 46410
rich.schurman@alliedbuilding.com
Roofing
Modified Bitumen Roof System
Evaluation Report from a Florida Registered Architect or a Licensed Florida
Professional Engineer
❑ Evaluation Report - Hardcopy Received
Robert Nieminen
THESE PLANS AND ALL PROPOSED WOplt
ARE SUBJECT TO ANY COPRECTIONS
PE-59166 REQUIRED BY FIELD INSPECTORS THAT
LIL LLC MAY BE NECESSARY im ORDER TO
06/2018
CM01PLY WITH AL_ APPLICABLE CODES,
John W. Knezevich, PE I �+
L✓7 Validation Checklist - Hardcopy Received
FL16027 R2 COI 2017 01 COI Nieminen.odf
Standard Year
ASTM D6163 2008
ASTM D6164 2011
ASTM D6222 2011
FM 4470 2012
FM 4474 2011
Equivalence of Product Standards
https://wv, w.floddabuilding.org/pr/pr app_dtl.aspx?param=wGEVXQwtDgtFPmdYiNDWrxtft9YUwv%2fLXRbpak6f2jJGiyowhtbu4Q%3dp/o3d 1/2
1/15/2018
r
Certified By
Florida Building Code Online
Sections from the Code
Product Approval Method
Date Submitted
Date Validated
Date Pending FBC Approval
Date Approved
Summary of Products
FIL
Method 1 Option D ;.Vop
09/25/2017
09/30/2017
10/08/2017
12/12/2017
FL #
Model, Number or Name
Description
16027.1
TRI-BUILT Modified Bitumen Roof
SBS and APP modified bitumen roof systems
Systems
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL16027 R2 II 2017 09 FINAL Al ER TRI-
Approved for use outside HVHZ: Yes
BUILT MODBIT FL16027-R2.odf
Impact Resistant: N/A
Verified By: Robert Nieminen PE-59166
Design Pressure: +N/A/-622.5
Created by Independent Third Party: Yes
Other: 1.) The Design Pressure noted in this application
Evaluation Reports
refers to one system. Refer to ER Appendix for all systems and
FL16027 R2 AE 2017 09 FINAL ER TRI-
max. design pressures. 2.) Refer to ER Section 5 for Limits of
BUILT MODBIT FL16027-R2.Ddf
Use.
Created by Independent Third Party: Yes
Back Next
Contact Us :: 2601 Blair Stone Road, Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida.:: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a public -records request, do not send electronic
mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. *Pursuant to Section
455.275(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address if they have
one. The emails provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to supply a personal
address, please provide the Department with an email address which can be made available to the public. To determine if you are a licensee under Chapter 455, F.S.,
please click here .
Product Approval Accepts:
® ow", � eC6sk
Credit Card
j Safe
i
https://www.floddabuilding.org/pr/pr app_dtl.aspx?param=wGEVXQwtDgtFPmdYiNDWrxtft9YUwv*/g2fLXRbpak6f2jJGiyowhtbu4Qg/g3dg/o3d
I
2/2
QTU,,�I_NITi ERD - - -- -
APPENDIX 1: ATT' MENT REQUIREMENTS F.OR.V IND.UPLIFT RES,ISTAN[E 'Al
Table Deck Application Type Description Page
IA-1 Wood New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 4
IA-2 Wood New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 5
iB Wood New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 5
1C Wood New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 6
1D Wood New, Reroof (Tear -Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover 6
1E-1 Wood New or Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 7
lE-2 Wood New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet,_ Bonded Roof Cover 8
1F Wood New or Reroof (Tear -Off) F Non -Insulated Bonded Roof Cover 8
2A Stee'-dFStr'ructural concrete New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 9
2B Steel or Structural concrete New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 9
2C Steel or Structural concrete New, Reroof (Tear -Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover 10
3A Structural concrete New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 11-14
3B Structural concrete New or Reroof (Tear -Off) F Non -Insulated, Bonded Roof Cover 14
4A LWIC New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 15-16
4B LWIC New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 16
4C LWIC New or Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 17-19
5A CWF New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 20
5B CWF New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 21
5C
CWF
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
22
5D
CWF
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
22
5E
CWF
New, Reroof (Tear -Off) or Recover
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
22
6A
Gypsum
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover,
23
6B
Gypsum
New, Reroof. (Tea r-Off) or Recover
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
24
6C
Gypsum
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
24
6D
Gypsum
New, Reroof (Tear -Off) or Recover
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
24
7A
Various
Recover
A-1
Bonded Insulation, Bonded Roof Cover
25-26
7B
Various
Recover
F
Non -Insulated, Bonded Base Sheet, Bonded Roof Cover
26
The following notes apply to the systems outlined herein:
1. The roof system evaluation herein pertains to above -deck roof components; Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
2. Insulation / base sheet fasteners shall be of sufficient length for the following deck engagement:
114—
➢ Wood: Minimum 0.75-inch penetration. P am
➢ Steel: Minimum 0.75-inch penetration and engage the top flute of the steel deck. '� � � m I L&" M"" COP"'
➢ Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturers published installation instructions.
3. Unless otherwise noted, insulation may be any one layer or combination of polyisocyanurate, polystyrene, wood fiberboard, perlite, gypsum -based roof board or mineral -wool roof board that meets the OA
requirements of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover.
Exterior Research and Design, I.I.C. d/b/a Trinity( ERD Evaluation Report A42970.10.12-R2 for FL16027-112
Certificate of Authorization #9503 6T"EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 1 of 26
--- ---- -- --- -- - - - -- - -- - -- TRIJfYTERD
4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover), whereby the base
sheet fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and
structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC
Approval documentation.
5. Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016).
6. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer's published instructions.
➢ HA (HA): Full coverage at 25-30lbs/square.
➢ Dow INSTA STIK Quik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c.
➢ Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c.
➢ OMG OlyBond 500 (OB500): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c. (PaceCart or SpotShot). Note: OlyBond Green may be used where OlyBond 500 is referenced.
➢ OlyBond Classic (OB Classic): Full coverage at 1 gal/square.
➢ ICP Adhesive & Sealants CR-20: Continuous 2.5-3.5-inch wide ribbons, 12-inch o.c.
➢ Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon -applied adhesive, adhesive ribbons shall be staggered from layer -to -layer a distance of one-half the ribbon spacing.
Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
7. Unless otherwise noted, all insulations are flat stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations maybe substituted with the following Maximum
Design Pressure (MDP) limitations. In no case shall these values be used to 'increase' the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then
the thinner board listed below may be used as a drop -in for the equivalent thicker material listed in the table:
➢ Millennium One Step Foamable Adhesive (M-OSFA): MDP -157.5 psf (Min. 0.5-inch thick)
➢ OMG OlyBond 500 (OB500): MDP -45.0 psf (Min. 0.5-inch thick Multi -Max FA-3)
➢ OMG OlyBond 500 (OB500): MDP -187.5 psf (Min. 0.5-inch thick ISO 95+ GL) F
➢ OMG OlyBond 500 (OB500): MDP -315.0 psf (Min. 0.5-inch thick ENRGY 3)
➢ OMG OlyBond 500 (OB500): MDP -487.5 psf (Min. 0.5-inch thick ACFoam II)
➢ ICP Adhesive & Sealants CR-20: MDP -117.5 psf (Min. 1.0-inch thick) -E
8. Bonded po lyisocya nu rate insulation boards shall be maximum 4 x 4 ft.
9. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC
Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD3, FM Loss
Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk" carry the limitations set forth in Section 2.2.10.1 of FM Loss
Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
10. For fully bonded assemblies, the maximum design pressure for the selected assembly shall meet -or exceed critical design pressure determined in accordance with FBC Chapter 16, and no rational analysis is permitted.
11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the
minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105.
12. For existing substrates in a bonded recover or re -roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the existing
roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with
ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13. For Recover Applications using System Type D, the insulation is optional; however, the existing roof system shall be suitable for a recover application.
14. Lightweight Insulating Concrete (LWC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction For systems where specific LWC is referenced, refer to current LWC
Product Approval for specific deck construction and limitations. For systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat thickness is 2-inches.
For LWC over structural concrete, reference is made to FBC Section 1917.4-1, Point 1.
Exterior Research and Design, LLC. d/b/a Trinity( ERD Evaluation Report A42970.10.12-R2 for FL36027-R2
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION- Revision 2: 09/25/2017
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 2 of 26
I
15. Unless of herwise noted, refer to the following references for bonded base, ply or cap sheet applications.
".Ta8LE1TRl•BUILT.RooK'CovEgs
Reference
Layer
Material
Application
BP -AA
I
Base Ply
FBC Approved ASTM D4601, Type II
HA at 20-40 Ibs/square
Ply
FBC Approved ASTM D2178, Type IV or VI
(Base
nd Ply sheets, Asphalt -Applied)
SBS-AA'Cap
(SBS,
Ply
TriBuilt SBS Granular
HA at 20-40 Ibs/square
SBS-TAI
(SBS, TI
rch-Applied)
Cap Ply
TriBuilt5B5 Granular
Torch -Applied
CSB$ SA'.=
--^—Base•PIyP
TriBDi1CS1C5 _S Base II
(BS'SIeIYAdhering)1r
rC_apLPly„aTriBtiiltSASBSCap-'
f
-Self-Adhering
APP-TjI
Base Ply Or Ply
TriBuilt APP Smooth
(APP, Torch
-Applied)
Cap Ply
TriBuilt APP Smooth, TriBuilt APP Granular
Torch -Applied
APP-SA
(APP, Seelf-Adhering)
Cap Ply
TriBuilt SA APP Cap
Self -Adhering
16. Vapor bdrrier options for use over structural concrete deck followed by adhered Insulation carry the following Maximum Design Pressure (MDP) limitations. The lesser of the MDP listings below vs. those in Table 3A
applies:
VAPOR
BARRIER OPTION$; STRUCTURAL CONCRETEDECK; ADHERED INSULATION PER TABIE3A . ., .:..
Option#
Primer
I
Vapor Barrier
Insulation Adhesive
MDP (psFl
Type
YP
Attach
VB-1
ASTM D41
TriBuilt SA SBS Base
Self -Adhering
Inta-Stik or CR-20, 12-inch o.c.
-60.0
VB-2.
ASTM D41
TdBuilt SA SBS Cap
Self -Adhering
Insta-Stik, 12-inch o.c.
-75.0
VB-3.
ASTM D41
TriBuilt SA 585 Cap
Self -Adhering
Millennium One Step Foamable Adhesive, 12-inch o.c.
-157.5
VB-4.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
CR-20, 12-inch o.c.
-270.0
VB-5.
ASTM D41
TriBuilt SA SBS Base
Self -Adhering
Millennium One Step Foamable Adhesive, Millennium PG-1 Pump Grade
Adhesive, OlyBond 500 or CR-20, 12-inch o.c.
_yg0.0
17. Dens De k shall be field -primed with PG300 prior to self -adhering membrane application. Refer to tables herein for other priming requirements.
18. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads.
Exterior Research and Design, U.C. d/b/a Trinity( ERD Evaluation Report A42970.10.12-R2 for FL36027-R2
Certificate of �{Iuthorization #9503 rEDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017
Prepared by: Robert Nleminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516.1485 Appendix 1, Page 3 of 26
TRINITY J ERD
TABLE 1E-2. WOOD DECKS —NEW CONSTRUCTION, REROOF (TEAR -OFF) oR REEOVER
;. SYSTEM TYPE E:NON-INSULATED ; MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER ,
System
Base Sheet
Roof Cover (Note 15)
MDP
No.
Deck (Note 1)
Base
Fasteners
Attach
Base Ply
Cap Ply
(Psf)
In. 19/32-inch
4n. 19/32-inch
Elastobase, Polyglass Elastobase
OMG Flat Bottom Plates (square) with
12-inch o.c. In 4-inch lap and 12-inch
(Optional) One or
W-1
plywood at max.
Poly, Polyglass G2 Base, CertainTeed
Roofgrip #14, Dekfast Hex with Dekfast #14
o.c, in two, equally spaced, staggered
more BP -AA or
SBS-AA, SBS-
-52.5
21-Inch spans
MB Base,AF Perma-
or TruFast MP-3 with TruFast HD
center rows
APP-TA
TA, AP; -;A
II
Pl 28,T, ko Glass
Ply 28, Tamko Glass Base or GAFGLAS #75
Min. 19/32-Inch
Polyglass Elastobase or Polyglass
Hex with Dekfast #14 or TruFast MP-
12-inch o.c. in 4-inch lap and 12-inch
One or more SBS-
SBS-SA, APP-
W-2
pl�wood at max.
Elastobase Poly with poly top surface
3 withDekfast
3 with TruFast HD
o.c. In two, equally spaced, staggered
SA
SA, SBS-TA or
-52.5•
2 inch spans
center rows
APP-TA
MP`Pn. 19/32•inch
Polyglass Elastobase or Polyglass
OMG Flat Bottom Plates (square) with
12-inch o.c. in 4-inch lap and 12-Inch
(Optional) One or
SBS-AA, SBS-
W-3
pl{rwood at max.
Elastobase Poly
Roofgrlp #12
o.c. in two, equally spaced, staggered
more BP -AA or
TA, APP-TA
-60.0
24-inch spans
center rows
APPTA
M�n. 19/32-inch
Polyglass Elastobase or Polyglass
OMG Flat Bottom Plates (square) with
12-Inch o.c. in 4-Inch lap and 12-Inch
One or more SBS-
SBS-SA, APP-
W-4
plywood at max.
Elastobase Poly with poly top surface
Roofgrfp #12
o.c. in two, equally spaced, staggered
SA
SA, SBS TA or
-60.0-
24-Inch spans
center rows
APP-TA
TABLE IF: WOOD DECKS- NEW CONSTRUCTIONDRREROOF.(TEAR-OFF)
(,
'SYSTEM TYPE F: NON -INSULATED, BONDED ROOF COVER
System
Deck
Primer
Roof Cover (Note 15)
MDP
Joint Treatment
Base Ply
Ply
Cap Ply
No.
(Psf)
5..
fMlir15j32=inc Iyw`9od�j
(Optional ASThA D41_
-
SBSSA-90:0t
�Optional)585-SA SBS-SA-or—
^SBS-SA; APP-S/C,3BS _BST
at max'24�inch^spans7
_Non
APP TA
or APP-LAr•',q
W-6
Min. 15/32-inch plywood
max.
(Optional) ASTM D41
Plywood joints are covered with 4-Inch wide strips of TriBuilt SA
TriBuilt SA SBS Base
(Optional) SBS-SA or''
-SBS-SA, APP-SA, SBS-TA
-97.5
at 24-inch spans
SBS Base, rolled into place to create continuous bond.
APP-TA
or APP-TA
i
I
Exterior Researcand Design, I.I.C. d/b/a Trinity( ERD
Certificate of Authorization #9503
Prepared by: Roil ert Nleminen, PE-59166
Evaluation Report A42970.10.12-R2 for FL16027-R2
e EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017
TRI-BUILT Modified Bitumen Roof Systems; (800) 516.1495 Appendix 1, Page 8 of 26