HomeMy WebLinkAboutPLANSDRAWING INDEX SHEET SHEET TITLE -01' -GENERAL-NOTES 02 STRUCTURE PLAN 03 SUPPLEMENTAL DETAILS 1.0 REFERENCED STANDARDS 1.1 FLORIDA BUILDING CODE, 6TH EDITION (2017) 1.2 ASCE 7-10 1.3 ASTM SPECIFICATIONS FOR CONCRETE 1.4 ACI 318-LATEST EDITION FOR STRUCTURAL CONCRETE 1.5 ADM 2015 1.6 AA ASM35, AA ADM 1 2.0 DESIGN LOADS 2.1 DEAD LOADS: MEMBER SELF -WEIGHT 2.2 LIVE LOADS: 300 LB VERT. LOAD ON PRIMARY MEMBERS 200 LB VERT LOAD ON PURLINS 2.3 DESIGN WIND SPEED PER F.B.C., CH. 16 LATEST EDITION Vult: 150 M.P.H. Vasd: 116 M.P.H. 2.4 RISK CATEGORY: 1 2.5 EXPOSURE CATEGORY: B 2.6 BUILDING TYPE: PARTIALLY ENCLOSED GCpi = +/- .55 2.7 SOLID ROOF COMPONENT & CLADDING DESIGN PRESSURES (asd): ZONE I : +16.5 / -29.8 PSF ZONE 2: +16.5 / -38.0 PSF ZONE 3: +16.5 / -45.2 PSF 2.8 WIND LOADS PER F.B.C. TABLE 2002.4 (MWFRS) FOR 20x2OxO.O13" MESH SCREEN: HOR PRESSURE ON WINDWARD SURFACES: 31 PSF HOR PRESSURE ON LEEWARD SURFACES: 22 PSF VERT PRESSURE ON SCREEN SURFACES: 09 PSF VERT PRESSURE ON SOLID SURFACES: 25 PSF 2.9 FOR 18x14x0.013" MESH SCREEN, APPLIED FACTOR: .88 2.10 FACTOR APPLIED TO ALLOWABLE STRESS DESIGN PRESSURES: .6 B. RESPONSIBILITIES 1.0 A LICENSED CONTRACTOR SHALL PERFORM ALL SITE WORK IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDINANCES, ETC. 2.0 CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL EXISITNG FIELD CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF DEMOLITION, CONSTRUCTION AND/OR FABRICATION. THE CONTRACTOR SHALL VERIFY THAT THE HOST STRUCTURE/FOUNDATION IS IN GOOD CONDITION WITH SUFFICIENT STRENGTH TO SUPPORT PROPOSED STRUCTURE. THE ENGINEER OF RECORD IS TO BE CONTACTED IN WRITING FOR CLARIFICATION IF DISCREPANCIES ARISE. 3.0 THE CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS ASSOCIATED WITH WORK TO BE COMPLETED. THIS IS TO INCLUDE ALL SHORING AND/OR BRACING REQUIRED FOR COMPLETION OF PROJECT. 4.0 THE CONTRACTOR IS RESPONSIBLE FOR PROTECTION OF COMPONENTS, FIXTURES, OPENINGS, AND LANDSCAPING ON THE SITE WHICH ARE NOT INCLUDED WITHIN THE SCOPE OF THIS PROJECT. IF DAMAGE OCCURS TO ITEMS NOT INCLUDED WITHIN THE SCOPE OF THIS PROJECT, THE CONTRACTOR IS RESPONSIBLE FOR RETURNING THAT ITEM TO ITS PREDAMAGE CONDITION. 5.0 THESE DRAWINGS AND DETAILS HAVE BEEN PREPARED AND ENGINEERED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND/OR MANUFACTURER CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD IN WRITING PRIOR TO CONSTRUCTION IF THERE ARE DISCREPANCIES WITH THE PLANS OR EXISTING SITE CONDITIONS THAT NEED TO BE ADDRESSED. ERICKSON PROPERTY 5431 PLACE I,AKE_DR., FORTT1ERCE; FL 349-5-1 C. MATERIALS 1.0 CONCRETE / FOUNDATION 1.1 SOIL 1.1.1 ASSUMED SOIL BEARING PRESSURE: 1500 PSF CI 1-21 PRIOR TO CONCRETE PLACEMENT, TREAT -EMI F.B.C. REQUIREMENTS FOR SUNROOMS. NOT REQUIRED FOR EXTERIOR SCREENED ENCLOSURES. 1. 1.3 CONCRETE PLACED OVER A POLY VAPOR SHIELD WHERE APPLICABLE. 1.2 CONCRETE 1.2.1 ALL CONCRETE SHALL BE-3-000-P§l MINIMUM. 1.2.2 CONCRETE SHALL CONFORZvI TO ASTM C94 FOR: 1.2.2.1 PORTLAND CEMENT, TYPE 1 - ASTM C150 1.2.2.2 3/4" AGGREGATE MAXIMUM - ASTM C33 1.2.2.3 AIR ENTRAINING, +/- I % - ASTM C260 1.2.2.4 WATER REDUCING AGENT - ASTM C494 1.2.2.5 CLEAN POTABLE WATER 1.2.2.6 OTHER ADMIXTURES SHALL NOT BE PERMITTED 1.2.3 ALL SLABS ON GRADE SHALL BE 4" THICK MINIMUM 1.3 REINFORCEMENT 1.3.1 FIBERMESH (3/4" PER CU. YD.) MAY BE USED IN LIEU OF WELDED WIRE MESH IF APPROPRIATE ACI AND ASTM REQUIREMENTS ARE MET. 1.3.2 METAL WELDED WIRE MESH (WWM) SHALL CONFORM TO ASTM A185. 1.3.3 STEEL REINFORCEMENT SHALL BE ASTM A615 GRADE 60 WITH Fy = 60 KSI (U.O.N.) 1.4 PREPARE AND PLACE CONCRETE IN ACCORDANCE WITH ACI MANUAL STANDARD PRACTICE PARTS 1,2 & 3 ALONG WITH HOT WEATHER CONDITION RECOMMENDATIONS. 1.5 IF UTILIZING AN EXISTING SLAB/FOOTING, CONCRETE SLAB SHALL BE A MINIMUM OF 4" THICK AND VISIBLY FREE OF DETERIORATION, SPALLING OR EXCESSIVE CRACKING. CONTRACTOR TO VERIFY THAT EXISTING FOOTING IS A MINIMUM OF 12" WIDE AND 8" DEEP BELOW EXISTING SLAB. IF NOT, SEE FOOTING DETAILS FOR FOOTING DESIGN MINIMUM REQUIREMENTS. 2.0 ALUMINUM 2.1 ALL STRUCTURAL ALUMINUM SHALL BE MIN: 2.1.1 EXTRUSIONS: 6005 T5 ALLOY 2.1.2 TUBES: 6063 T6 ALLOY 2.2 STRUCTURAL ALUMINUM DESIGN SHALL CONFORM TO 'PART 1-A - SPECIFICATIONS FOR ALUMINUM STRUCTURES - ALLOWABLE STRESS DESIGN' OR "PART 1-B - SPECIFICATIONS FOR ALUMINUM STRUCTURES - BUILDING LOAD AND RESISTANCE FACTOR DESIGN' OF THE LATEST ALUMINUM DESIGN MANUAL. 2.3 PROVIDE DIELECTRIC SEPARATION WHERE ALUMINUM COMES IN CONTACT WITH STEEL OR PRESSURE TREATED LUMBER 2.4 ACTUAL WALL THICKNESS OF EXTRUDED ALUMINUM MEMBERS SHALL NOT BE LESS THAN 0.040 INCH 2.5 SELF -MATING BEAM SECTIONS TO BE STITCHED WITH #12 SMS SPACED AT 6" ON -CENTER FROM THE ENDS AND 24" ON -CENTER THROUGHOUT THE REMAINDER. 2.6 MINIMUM THICKNESS FOR FORMED SHEET ALUMINUM STRUCTURAL WALL PANELS (KICK -PLATES) SHALL BE 0.024". 2.7 18x14x0.013" MESH SCREEN SHALL BE USED UNLESS APPROVED BY THE ENGINEER OF RECORD. 2.8 ROOF BRACING SHALL BE A MINIMUM OF 2"x2"x0.050" 2.9 DOOR LOCATIONS MAY BE DETERMINED IN THE FIELD BY CONTRACTOR. 2.10 FOR PICTURE WINDOW MODIFICATIONS TO EXISTING SCREEN ENCLOSURES, THE CONTRACTOR SHALL VERIFY THE EXISTING SCREEN ENCLOSURE IS IN STRUCTURALLY SOUND CONDITION AND MEETS THE REQUIREMENTS OF THE DETAILS WITHIN THESE PLANS. 2.11 IF ENCLOSURE CONTAINS A SWIMMING POOL OR SPA, THE ENCLOSURE SHALL MEET THE FLORIDA BUILDING CODE, RESIDENTIAL SECTION R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS IN ITS ENTIRETY. FILET. - LUCIE .---Co F � __EVIEWED REVIEWED 8 DATE U G PLANS AND F SITE OR NO ] 6166 MUST BE KEPT TION(S) WILL E 140, 2.12 SCREEN ROOM ALUMINUM ROOF SECTIONS ( ` OR PAN) SHALL BE SELECTED/DESIGNED FOR PRESSURE STATED WITHIN THE WIND LOAD= "ft 0 p THESE GENERAL NOTES. THE SELECTION OF $ of * SECTIONS WAS BASED ON THE SPAN TABLE�re Vo.; iL Q 0 AND CERTIFIED BY INDEPENDENT FLORIDA I 4 coENGINEERS WITH THE UP-TO-DATE N.O.A. �;�\. .� 3.0 FASTENERS //' 3.1 ALL FASTENERS SHALL COMPLY WITH ASTM Aldf. 0 3.2 ALL CONCRETE SCEWS SHALL BE TAPCON, SIMPS>i�TIkI, OVED EQUAL. 3.3 ALREDHEAD LAG BOLTS SHALL HAVE A MIN. EMBED OF 8x BOLT�If� INTO STRUCTURAL FRAMING. 3.4 USE STAINLESS STEEL TYPE 300 18-8 FOR FASTENERS CONNECTING ALUMINUM COMPONENTS OR PRESSURE TREATED LUMBER, UNLESS OTHERWISE NOTED ON PLANS OR MANUFACTURER OF GALVANIZED BOLTS SPECIFIES FOR USE WITH ACE PRESSURE TREATED WOOD. 3.5 THE MIN CENTER TO CENTER SPACING FOR SMS SHALL BE 3/4" AND THE MIN CENTER TO EDGE DISTANCE SHALL BE 1/2" UNLESS OTHERWISE NOTED. 3.6 FOR 1x2 MEMBERS TO MASONRY/CONCRETE USE GALVANIZED I/4"x2-3/4" TAPCONS OR SIMILAR AT 18" O.C. 3.7 FOR lx2 MEMBERS TO WOOD FRAME USE #14x2-3/4" WOOD SCREW AT 18" O.C. (TYP.) 3.8 FOR lx2 MEMBERS TO ALUMINUM USE #10xl-1/2" SMS OR TEK SCREWS AT 18" O.C. (TYP.) 3.9 FOR lx2 MEMBERS INSTALLED THROUGHOUT AN "OPEN VIEW" OR "PICTURE WINDOW' ASSEMBLY, THE FASTENER SPACING SHALL BE REDUCED TO 12" O.C. MAX. ALUMINUM EXTRUSION DIMENSIONS HOLLOW SECTIONS 2x2 2"x2"x0.050" 2 x 3 2"x3"x0.050" 3 x 3 3"x3"x0.070" 3 x 3 3" x 3" x 0.093" OPEN -BACK SECTIONS lx2 1"x2"x0.044" Ix3 1"x3"x0.045" SNAP SECTIONS 2 x 2 2"x2"x0.045" 2 x 3 2"x3"x0.050" 2x4 2"x4"x0.045" SELF -MATING SECTIONS (SMB) 2x4 2" x 4" x 0.044" x 0.100" 2 x 5 2" x 5" x 0.050" x 0.118" 2 x 6 2" x 6" x 0.050" x 0.120" 2x7 2" x 7" x 0.057" x 0.120" 2 x 8 2" x 8" x 0.072" x 0.224" 2 x 9 2" x 9" x0.082" x 0.224" 2 x 10 2" x 10" x 0.092" x 0.374" wa 0 P. v O w z 00 o U zu F-� WOO wHd�C7 � xHzwoz UuQmwwY`i9� w 0 pp�� ��rr�� LU �H3c xw RIV W N H � M V1 Z �W H H wO 7 � V 1 ZEi F� � P4 WelO Na p: (941)456-7535 e: admin@southsunengineering.com w: www.southsunengineering.com CONTRACTOR: TREASURE COAST HOME IMPROVEMENTS, INC. PROPERTY ADDRESS: 5431 PLACE LAKE DR., FORT PIERCE, FL 34951 DATE: 5/7/2018 PROJECT NO: A18-041914 _ SHEET: Sol FOR NEW FDN/SLAB TO EXISTING FDN/SLAB, DRILL A 1/2' DIA HOLE TO A DEPTH OF 6" INTO EXISTING CONCRETE. PROPERLY CLEAN HOLE AND ENSURE CONCRETE SURFACE IS FREE FROM LOOSE AGGREGATE. FILL DRILLED CAVITY W/ STRUCTURAL EPDXY TO PROVIDE A MIN BOND STRENGTH OF 4000 PSI. EMBED A 12" #3 BAR 6' INTO EXISTING CONCRETE. #3 BAR TO iX2 2X4SMB 55" N N N O/C N N N 2X4SMB 1X2 3X3X.093 [— 8 -6 ---I w H Q 0 ''� HOST 1 , 3-1/2"-SLAB MIN.—W/-6x6--W-1.4xW1-.4V-WR-(OR — -- 11 x ¢ _ _ •a_•a FIBERMESH) ATOP 6MM POLY VAPOR SHIELD AND \�` JR * �j�/i/ z w 04 a k PROPERLY COMPACTED FILL TREATED AGAINST\� •••-.�� Q o TERMITES AND FREE OR ORGANIC MATTER 14 -0 `� v �� w w o 1/8' PER I'SLOPE MIN. `i/�= y�•• z w H � x„ I P- U • ��• F W Oi cnc�Hw W � V U crj ��ad3H 3 �a 12" X 12" MONO FOOTING W a O 'Z' 3 U ��— -- —-- .• C. y a Z w � • w F" as /� i cn0p E-q 38'-0" PHFx��q x U� a CONCRETE PLAN //J� illl��� H V4 z / t3X3X.093 " HOST PANELS FASTENED BELOW O/H TO HOST — — — — I MB I I I I 3" X 0.024 X 1.51b COMPOSITE PANELS 3105 - H14 13'-9"114'-9"MB 62.5" [MIN. 1/4" PER 1'SLOPE] 1 O/C 2 L------------------------------------- 6 12" O/H (�) 38'-0" 16" - 3X3X.093 2X2 CN M x N N N N N N X M 2X2 56" 40" 72" O/C NOTE: • COMP. ROOF PANELS FL #2291-R10 -COMP. ROOF PANELS W/ SKYLIGHT FL #10013-R6 '-- .024 ALUM. KICK PLATE W N aw V1 Z �W H H P 4 H V 1 ZFi Fi �a- W�O is p: (941) 456-7535 e: admin@southsunengineering.com w: www.southsunengineering.com CONTRACTOR: TREASURE COAST HOME IMPROVEMENTS, INC. PROPERTY ADDRESS: 5431 PLACE LAKE DR.; FORT PIERCE, FL 34951 1M:N1:4 5/7/2018 PROJECT NO: A18-041914 STRUCTURE PLAN ET: t SCALE: 1/8" = F-0" S02 COLUMN VARIES. SEE SHEET SECONDARY ANGLE MIN. 1/8" 02 FOR SIZING. OPTION I OPTION 2 w THICK W/ (2) #12 SMS INTO COLUMN E. SIDE (TYP.) 2"x2"x]/8" ANGLE W/ (2) #12x3/4" FAUPRIGHT OR BEAM (HOLLOW, Q 104" CONZ RefE ANCHOR (TAPCON SMS EA. SIDE (TYP.) SNAP, OR SELF -MATING) XL OR EQUAL) AT EACH ANGLE EA. 1/16"_ALUilllNUM.INTERNAL.OR - - - - SIDE W/MiN. 2-3/4" EMBEDMENT— o o - - -- - - - INTO FOOTING (TYP.) I "x2" OPEN -BACK BASE PLATE (4) #1 Oxl-1/2" SMS I I EXTERNAL RECEIVING CHANNEL (TYP.) EXISTING MASONRY WALLrTIE BEAM I�• FOR WOOD: USE 1/4" LAG BOLT IN o (TYP. EA. SIDE) INTO SCREW BOSSES (0.062" ANGLE CLIPS MAY BE USED W/ O LIEU OF TAPCON W/ MIN 2-3/4 EMBED.(2) #12x3l4" SMS EA. LEG) EXISTING WOOD TRUSS -FASCIA 3" MIN. COVER — — — — = 3" COMPOSITE PANELS (TYP.) _ _ — _ _ .045X3.25" CHANNEL (EXTRUDED FADER). IFFF�YYYy+++ 2-1/2" MIN. SPACING 2x2 / 2x3 MEMBER. = I = FASTEN TO MASONRY W/ 3/8"X3" TAPCON OR EQUAL TYP.) SEE PLAN ON SHEET (4) #100/4" INTO BEAM OR AT 12" O/C -STAGGERED Z d ^ ( I UPRIGHT (TYP.) SUBSTRATE 1'j COLUMN VARIES. SEE SHEET 02 (�.) (2) #12x3/4" EA. LEG INTO FASTEN CHANNEL TO BOTTOM OF PANEL o t 02 FOR SIZING. I GIRT OR PURLIN (TYP.) W/#12X5/8" SMS 8" O/C ---- — --------SID VIE as I--- \x�/ Q W MN 2"x2"x1/8" ANGLE W/ 2 #120/4" ��` J� Q qs� CLw 0 a � \0 I) •eeeee• 4 0 O �o xD SMS EA. SIDE (TYP.) 1/4" CONCRETE ANCHOR (TAPCON • ! O o0 XL OR EQUAL) AT EACH ANGLE EA. N. GJ� eft I j V. O �+ I t� M SIDE W/ MIN. 2-3/4" EMBEDMENT 5 PANEL ROOF TO HOST ATTACHMENTS v, x -- w < SECONDARY ANGLE MIN. 1/8" IN'CO FOOTING (TYP.) • ! - H Q. U THICK W/ (2) #12 SMS INTO • W COLUMN EA. SIDE (TYP.) FOR WOOD: USE 1/4" LAG BOLT IN 03 SCALE: N.T.S. 3 �_ x w U j LIEU OF TAPCON W/ MIN 2-3/4" EMBED. 3 BEAM/POST TO GIRT/PURLIN CONNECTION : m ,� �c {�/ - F' x ` j a 1 "x2" OPEN -BACK BASE PLATE � - ANCHORED TO FTG W/ 1/4" CONC 03 SCALE: N.T.S. r ♦ Q Z - w `O SCREW (TAPCON XL OR EQUAL) W/ U A E~ MIN. 2-3/4" EMBED. CONC SCREW TO O � O BE INSTALLED 6" MAX. FROM COLUMN � �. F: C) w AND SPACED AT 24" O.C. MAX. O PQ 6" MAX. i * PRO z 0 w U Q SUBSTRATE ) I I 6X6 WIAXW1.4 WWF o . F� 10" FRONT VIEW �{ OR FIBERMESH IF ALLOWED .. E• 3 va to COLUMN TO FOUNDATION CONNECTION FOR 2x4 OR LARGER 4 03 SCALE: N.T.S. FASTEN COMPOSITE PANEL TO FRAMING W - WITH.#14x4" SMS W/1-I/2" NEO-WASHER a 12" O/C 4"1Fy M P-0" — 1--1 F-+ M EAVE RAIL PER PLAN 4- 4" FASTEN JAMB TO INTERSECTING MEMBER W/# 10 SMS TO LENGTH TO ENSURE 1-1/2" PENETRATION INTO SCREW 3X3 EAVE RAIL FASTENED BOSS OF JAMB (TYR) INTERNALLY M UPRIGHT PVC DECK DRAIN EACH SIDE SMS 1_0�� EACH SIDE 4000 PSI 12"x10 W - ALTERNATE: FASTEN.0441tECEIVING CHANNEL 3" MIN COVER MONO FOOTING W/ TO INTERSECTING MEMBER W/ 4 #]0 SMS- (2) #5 BAR CONT 7 FASTEN JAMB TO RECEIVING CHANNEL W! OVER STEEL ON 3" CHAIR (TYP.) (2) #1..x5l8" SMS EA SIDE (TYP.) COLUMN PER PLAN SEE DETAIL 3103 T / I u 6 MONOLITHIC FOOTING DETAIL HEADER - a 1 03 SCALE: N.T.S. FASTEN HEADER AT EA END W/ (4) #100" SMS THRU / WIRE KICK PLATE IS INDICATED FASTEN w N PLO JAMB INTO SCREW BOSS OF HEADER (TYP.) .024 ALUMINUM SHEET W /#10xl/2" SMS 8" O.C. AROUND THE PERIMETER SEE DETAIL 1/03 p: (941) 456-7535 FASTEN ANGLE TOCONC W/(1)1/4"x3-1/2" — �� e: admin@southsunengineering.com TAPCON. WHERE APCARE PRESENT INCREASE LENGTHF TO TO O ENSURE 1 w: www.southsunengineering.com PENETRATION INTO FND MIN 2-1/4". z Z WHEN FASTENING TO WOOD USE 1/4" aaJ GALV. LAG SCREW IN LIEU OF CONC. a 25" LAP MIN- CONTRACTOR: d ANCHORS AND ENSURE PENETRATION MIN w 2-1/4" INTO STRUCTURAL FRAMING BENEATH. a #5 REINFORCING BAR TREASURE COAST HOME (TYP.) FASTEN ANGLE TO JAMB 4 END WALL SECTION TO COMPOSITE PANEL ROOF #5 LAP SPLICE #5REINFORCINGBAR FVIPROVEMENTS, INC. W/ (2) 912x5/8"SMS (TYP.) 1x2OPEN BACK pLTERNATE:FASTEN 1x2TOBTMOF O OJ PROPERTY ADDRESS: o BTMPLATE(TYP) SCALE: N.T.S. O� JAMB VERT W/ (2) #]Oxl-1/2" SMS O (INTERNAL) INTO SCREW BOSS OF JAMB FASTEN DOOR JAMB TO Ix2 BASE PLATE W/ (2) R'''/$" 5431 PLACE LAKE DR., #10 SMS THROUGH JAMBINTO SCREW BOSS OF Ix2 (ENSURE PENETRATION INTO Ix2 MIN I") FORT PIERCE, FL 34951 CONIC000 FTG/S AB WIOx 10 I O" DATE: CONC FTG/SLAB WITH W. W.M. OR FIBERMESH (TYP.) 5/7/2018 #5 STD. 90' HOOK PROJECT NO: A18-041914 7 2 TYPICAL DOOR JAMB/HEAD DETAIL LAP SPLICING DETAIL SHEET:03 SCALE: N.T.S. 03 SCALE: N.T.S. S03__j