HomeMy WebLinkAboutEVALUATION REPORT - UNDERLAYMENTSCREEK
TECHNICAL SERVICES, LLC
ALUATION REPORT
rer: TAMKO BUILDING PRODUCTS, INC.
P.O. Box 1404
Joplin, MO 64802
(417) 624-6644
http://www.iamko.com
ity Assurance:
COPE
UL LLC (QUA9625)
Certificate' --of Authorization No. 29824
17520 Edinburgh Drive
Tampa, FL 33647
(813) 480-3421
FLORIDA BUILDING CODE, 6T" EDITION (2017)
Issued October 19, 2017
SCANN90,
BY
"St Lucie Counjy
subcategory:
)ubcat
:ode Sections:
properties:
"RODUCT DESCRIPTION
Roofing FILE
Underlayments COPY
1507.1.1
Physical properties
FAMKO® ASTM Slate
ASTM D 6380, Class M, Type II underlayment constructed from organic felt saturated
surfaced Roll Roofing
with asphalt and coated on both sides with asphalt and surfaced with granules.
rAMKO® ASTM Tile
ASTM D 6380, Class M, Type II underlayment constructed from an organic felt saturated
Jnderlayment
with asphalt then coated on both sides with asphalt and surfaced with granules.
rAMKO® Master
ASTM D 6380, Class S, Type IV underlayment constructed from an organic felt saturated
smooth
with asphalt then coated on both sides with asphalt and surfaced with a fine mineral. For
use in non-HVHZ only.
fAMKO® Moisture
Self -adhered, ASTM D 1970, fiberglass reinforced, modified bitumen sheet membrane
3uard®
with a mineral surfacing and a removable release film on the adhesive side and
removable selvedge release tape.
rAMKO® No. 15 ASTM
ASTM D 226, Type I underlayment constructed from a non -perforated organic felt that is
%sphalt Saturated
saturated with asphalt.
)rganic Felt
rAMKO® No. 15 UL
ASTM D 226, Type I underlayment constructed from a non -perforated organic felt that is
ksphalt Saturated
saturated with asphalt.
)rganic Felt
�A O®o 36'ASTM
D 226, n erlayment constructed rom af- p Mora edrorganic feit-that is
�sRhalt Saturated
saSurathypphalt
AMKO® No. 30 UL ASTM D 226, Type II underlayment constructed from a non -perforated organic felt that is
Lsphalt Saturated saturated with asphalt.
)rganic Felt
AMKO® TW Metal and Self -adhered, flexible, ASTM D 1970 and TAS 103, rubberized asphalt sheet membrane
'ile Underlayment with a polymer film on the surface and a removable release film on the adhesive side.
AMKO® TW Self -adhered, flexible, ASTM D 1970, rubberized asphalt sheet membrane with a
Inderlayment polymer film on the surface and a removable release film on the adhesive side.
14001.4 FL12328-R8 Page 1 of 4
evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
nical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
ifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
THmKO BUILDING PRODCUTS, INC.
TAMKO Underlayments
I
TAMKOO TAM -FELT Alternate to ASTM D 226, Type I and Type II underlayment constructed from a non -
I perforated organic felt that is saturated with asphalt.
APPLICATION METHOD
Installation shall be in accordance with the published manufacturer's installation instructions, the FBC, and the
requirements below.
Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck shall be
checked for protrusion and corrected prior to underlayment application.
The roof deck shall be constructed of closely fitted plywood sheathing for new or existing construction. Plywood deck
shall be installed in accordance with FBC requirements. Roof decks shall have no more than 1/8" gap at abutting
lints.
The minimum application temperature shall be 50°F except as follows:
a) The minimum application temperature of TAMKOO TW Metal and Tile Underlayment and TAMKOO TW
Underlayment shall be 40°F.
b) The minimum application temperature of TAMKOO Moisture Guard@ shall be 35°F.
Tihe minimum roof slope shall be in accordance with FBC requirements except as follows:
a) The minimum slope of TAMKOO ASTM Slate Surfaced Roll Roofing shall be 2:12.
Underlayments shall be exposed in accordance with the manufacturer's recommendations, but in no case shall
exposure exceed 30 days.
Exception: TAMKOO TW Metal and Tile Underlayment may be exposed for a maximum 90 days.
Self -adhering underlayments may be adhered to primed or unprimed plywood substrates in the non-HVHZ.
All roof coverings shall be mechanically fastened through the underlayment to the roof deck.
Allowable Rnnf Coverings -
Metal Roof
Mineral
Wood
Asphalt
Panels and
Surfaced Roll
Shingles and
Slate
Clay and
Underlayment
Shingles
Shingles
Roofing
Shakes
Shingles
Concrete Tile
TAMKOO ASTM Slate
Y1
N
N
N
N
Y
Surfaced Roll Roofing
TAMKOO ASTM Tile
N
N
N
N
N
Y
Underlayment
TAMKOO Master Smooth
Y'
N
N
N
N
N
TAMKOO Moisture Guard@
Y
N
N
N
N
N
TAMKOO No. 15 ASTM
Asphalt Saturated Organic
Y
Y
Y
YZ
N
N
Felt
TAMKO@ No. 15 UL Asphalt
Y
Y
Y
YZ
Y
N
Saturated Organic Felt
TAMKOO No. 30 ASTM
Asphalt Saturated Organic
Y
Y
Y
Y
Y
Y
Felt
TAMKO@ No. 30 UL Asphalt
Y
Y
Y
N
Y
N
Saturated Organic Felt
TAMKOO TW Metal and Tile
Y
Y
N
N
N
Y
Underlayment
TAMKOO TW Underlayment
Y
Y
N
N
N
N
TAMKOO TAM -FELT
Y
N
N
N
N
N
Notes: 1) Open valley applications per 1507.2.9.2
2) Wood shingles only
TBP14001.4 FL12328-R8 Page 2 of 4
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
i
y �
CREAK TAMKO BUILDING PRODCUTS, INC.
TAMKO Underlayments
TECHNICAL SERVICES, LLC
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) Wind uplift resistance in not within scope of this evaluation.
3) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturer's published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
4) Contact the manufacturer when installing at temperatures below the minimum application temperature.
5) Unless otherwise stated, the minimum roof slope shall be in accordance with FBC requirements.
6) All underlayments shall be installed with the roll length parallel to the eave, starting at the eave, and lapped
in successive courses installed up the deck in a manner that effectively sheds water from the deck. End
laps shall be staggered between courses in accordance with the manufacturer's application instructions.
7) The underlayment may be used as described in other current FBC product approval documents.
8) The underlayment shall not be installed over existing roof coverings.
9) Contact the manufacturer regarding specific exposure limits for each underlayment.
10) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
REFERENCES
Entity
Report No.
Standard
Year
PRI Construction
Materials
Technologies (TST6049)
TAP-192-02-01
ASTM
D 1970
2015a
PRI Construction
Materials
Technologies (TST6049)
TAP-193-02-01
ASTM
D 1970
2015a
PRI Construction
Materials
Technologies (TST6049)
TAP-214-02-01
ASTM
D 4869
2016
PRI Construction
Materials
Technologies (TST6049)
TAP-215-02-01
ASTM
D 226
2009
PRI Construction
Materials
Technologies (TST6049)
TAP-216-02-03
ASTM
D 6380
2003(2013)
PRI Construction
Materials
Technologies (TST6049)
TAP-217-02-01 REV
ASTM
D 6380
2003(2013)
RI Construction
Materials
Technologies (TST6049)
TAP-218-02-01
ASTM
D 226
2009
Construction
Materials
Technologies (TST6049)
TAP-219-02-01
ASTM
D 226
2009
'Z
PRI Construction
Materials
Technologies (TST6049)
TAP-220-02-01
ASTM
D 6380
2003(2013)
PRI Construction
Materials
Technologies (TST6049)
TAP-222-02-01
ASTM
D 4869
2016
PRI Construction
Materials
Technologies (TST6049)
TAP-245-02-01
TAS 103
1995
ASTM
D 4798
2011
PRI Construction
Materials
Technologies (TST6049)
TAP-311-02-01
ASTM
D 1970
2015a
PRI Construction
Materials
Technologies (TST6049)
TAP-319-02-01.1
ACC 188
2012
PRI Construction
Materials
Technologies (TST6049)
TAP-387-02-01
ASTM
D 1970
2015a
PRI Construction
Materials
Technologies (TST6049)
TAP-388-02-01
ASTM
D 1970
2015a
;UL LLC (TST9628)
13CA12269
ASTM
D 226
2009
i
-TBP14001.4
FL12328-R8
3 of 4
evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
nical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
ifically addressed herein.
L
� r
w CREEK
TECHNICAL SERVICES, LLC
E STATEMENT
TA—MKO BUILDING PRODCUTS, INC.
TAMKO Underlayments
products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
6'h Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer.
PRY R.
.�`
�� '\LENS .•cS� �i
No 74021
?� STATE OF
f111111
OFINDEPENDENCE
2017.10.19
12:15:58
-04'00'
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing products under this
Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under this evaluation.
R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products under this evaluation.
R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product.
END OF REPORT
P14001.4 FL12328-R8 Page 4 of 4
is evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
chnical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
is evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
acifically addressed herein.