To whom it may concern,
We have been informed that the submitted plans for the aforementioned project have not met the
code compliance requirements necessary for approval. Please find our responses to the areas of
deficiencies or corrections required to achieve compliance.
Comment: Please note that the comments are for the clarification or correction of the
submitted documents. Additional review may be required after submitting
corrected documents.
Response: Noted
2. Comment: Please provide on the documents R values for the insulation and material be used
Chapter 1, Section 107 Subsection 107.1 of the 2017 Florida Building Code Sixth
Edition.
Response: The construction is 4' x 8' x 3/4" rigid board on inside of block, V x 2" PT over
that @ 24" O.C. and then 1/2" drywall. Also, the builder is using R30 batt
insulation.
3. Comment: Submitted energy calcs documents must be in duplicate with both the preparer
and builder's original signatures. See Section 107.1 of the 2017 Florida Building
Code.
Response: To be provided by Builder.
4. Comment: Please add the cubic volume of the conditioned space to information block -
containing the square foot information. See Chapter 1, S,eatiabp,7, of the 2017
Florida Building Code Sixth Edition. �: f`�VID PA.$�j�
Response: Cubic volume of conditioned space is 11,835 C.F,;�pet=.eneg'�•'s. �/!r �.�
2
s
October 1, 2018 ny• NO 821fstA 1,1018
s.*
s
j Carl A. Brown, P.E ',, PBoRF
FLPE# 56126 N�'�a
ae� �gb AI
If Seal and Signature are not blue or can't be smudged contact FOR for authorization
"Doing Business with a Service Mindset and an Eye for Detail"
I
4A P
ENGINEERING ASSOCIATES
249 Maitland Ave, Suite 3000 1 Altamonte Springs, Florida 32701
P: (321)972-0491 1 F: (321)972-0484 1 E: info@fdseng.com
Website: www.fdseng.com
5. Comment: Please show flame spread index and smoke developed index for wall and ceiling
finishes in accordance with Section 302.9 of the 2017 Florida Residential Code.
Response: The flame spread index and smoke -developed index for wall and ceiling finishes
shall meet the requirements of R302.9.
I 14302.9 Flame spread index and smoke -developed index for wall and ceiling finishes.
Flame spread and smoke developed indexes for %gall and ceiling finishes shall be in accordance with Sections R302.9.1 through R302.9.4_
R302.9.1 Flame spread index.
Wall and ceiling finishes shall have a flame spread index of not greater than 200.
Exception: Flame spread index requirements for finishes shall not apply to trim defined as picture molds, chair rails, baseboards and handrails; to
doors and windows or their frames; or to materials that are less than 1128 inch (0.91 mm) in thickness cemented to the surface of walls or ceilings If
these materials exhibit flame spread index values not greater than those of paper of this thickness cemented to a noncombustible backing.
R302.9.2 Smoke -developed index.
Wall and ceiling finishes shall have a smoke -developed index of not greater than 450.
R302.9.3 Testing.
Tests shall be made in accordance with ASTM E84 or UL 723.
R302.9.4 Alternative test method.
As an alternative to having a flame spread index of not greater than 200 and a smoke -developed index of not greater than 450 where tested in
accordance with ASTM E84 or UL 723, wall and ceiling finishes shall be permitted to be tested in accordance with NFPA 286. Materials tested in
accordance with NFPA 286 shall meet the following criteria:
The interior finish shall comply with the following:
1. During the 40 kW exposure, flames shall not spread to the ceiling.
2. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.
3. Flashover, as defined in NFPA 286, shall not occur.
4. The peak heat release rate throughout the test shall not exceed 800 kW.
5. The total smoke released throughout the test shall not exceed 1,000 m2.
6. Comment: Please show the flame spread and smoke developed index for the insulation as
required in Section 3 02. 10 of the 2014 Florida Residential Code.
Response: The flame spread index and smoke -developed index for insulation shall meet the
requirements of R302.10. u o A o e e
u6��a egsoe
000 80
'�,
o�.•L�CEIyS
l
October 1, 2018 s' N0 821260etobe1l, 2018
Carl A. Brown P.E :• d d.dorn Z
FLPE# 56126 PE# 82V6: ��;
~�9 ILA If Seal and Signature are not blue or cant be smudged contact FOR for authorization d��i 777
"Doing Business with a Service Mindset and an Eye for Detail"
i
249 Maitland Ave, Suite 3000 1 Altamonte Springs, Florida 32701
_ P: (321)972-0491 1 F: (321)972-0484 1 E: info@fdseng.com
Website: www.fdseng.com
ENGINEERING ASSOCIATES
R302.10 Flame spread index and smoke -developed index for insulation.
Flame spread and smoke -developed index for insulation shall be in accordance with Sections R302.10.1 through R302.10.5.
R302.10.1 Insulation.
Insulation materials, including facings, such as vapor retarders and vapor -permeable membranes installed within floor -ceiling assemblies, roof -ceiling
assemblies, wall assemblies, crawl spaces and allics shall have a flame spread index not to exceed 25 with an accompanying smoke -developed index
not to exceed 450 where tested in accordance with ASTM E84 or UL 723.
Exceptions:
1. Where such materials are installed in concealed spaces, the flame spread index and smoke -developed index limitations do not apply to the
facings, provided that the facing is installed in substantial contact with the unexposed surface of the ceiling, floor or wall finish.
2. Cellulose fiber loose -fill insulation, that is not spray applied, complying with the requirements of Section R302.10.3, shall not be required to
meet a flame spread index requirement but shall be required to meet a smoke -developed index of not more than 450 where tested in
accordance with CAN/ULC S102.2.
3. Foam plastic insulation shall comply with Section R316.
R302.10.2 Loose -fill insulation.
Loose -fill insulation materials that cannot be mounted in the ASTM E84 or UL 723 apparatus without a screen or artificial supports shall comply with the
flame spread and smoke -developed limits of Section R302.10.1 where tested in accordance with CANlULC S102.2.
Exception: Cellulosic fiber loose -fill insulation shall not be required to be tested in accordance with CAN/ULC S102.2, provided such insulation
complies with the requirements of Sections R302.10.1 and R302.10.3.
R302.10.3 Cellulosic fiber loose -fill insulation.
Cellulosic fiber loose -fill insulation shall comply with CPSC 16 CFR, Parts 1209 and 1404. Each package of such insulating material shall be clearly
labeled in accordance with CPSC 16 CFR, Parts 1209 and 1404.
R302.10.4 Exposed attic insulation.
Exposed insulation materials installed on allic floors shall have a critical radiant flux not less than 0.12 matt per square centimeter.
R302.10.5 Testing.
Tests for critical radiant flux shall be made in accordance with ASTM E970.
7. Comment: Please provide the foundation support per R403.1 2017 FBC-R 6`h Edition.
Response: The foundation was designed based on an allowable soil bearing pressure of
2,000 PSF. Please accept the note block below as being included in the
Construction Document.
°pt1111IAps
♦°°° #J's
00o dpD M. 80 41,0
October 1, 2018; ° C E MSF o�er 1, 2018
No 82126
Carl A. Brown, P.Eodd*1. Born ,F
FLPE# 56126:: 82126
OF ' �=
If Seal and Signature are not blue or can't be smudged contact FOR for authoratiyi ....
J41�.�i L �*,1ao
"Doing Business with a Service Mindset and an Eye to �etail"
1 s
249 Maitland Ave, Suite 3000 1 Altamonte Springs, Florida 32701
P: (321)972-0491 1 F: (321)972-0484 E: info@fdseng.com
Website: www.fdseng.com
ENGINEERING ASSOCIATES
GENERAL FOUNDATION NOTES
1 PROVIDE MIN. B MIL. APPROVED VAPOR DAHMER. ALL POINTS TO BE
LAPPED MIN, 8• AND SEALED.
2 4. 250D PSI CONC. SLAB W/ 6XB 10/10 W W F. OR MININUM .75 LBS
OF FIBER PER CUIrC YARD FIBERMESH/FIBERMIX ADDED TO THE
CONCRETE, I.Y ACCORDANCE W/ MANUFS INSTRUCTIONS AND NER-284
FOR FIBERMESH OR NER414 FOR FIBERMIX, OVER 6 MIL VISQUEEN VAPOR
BARRIER h TREATED FOR TOWNES.
3 ■ INDICATES FILLED CELL W/3000 PSI CONC. FROM FTR. TO
BEAM W/(1) M5 REBAR GRADE 40 U.N.O.TYPICAL. ABV. SLAB. HOOKED FIG.
DOWELS IT' EMBEDMENT W/ 25- EXr. ABOVE SLAB.
4 CONSULT W/ MANUF. SPECIFICATIONS PRIOR TO POURING OR
RECESSING DOOR SILLS OR SLIDING GLASS DOOR SILLS.
6 EXTERIOR SLABS SHALL SLOPE 1/12- PER FOOT AWAY FROM HOUSE
U.N.O.ON PLAN.
6 CONTROLJOINTS OF SHOWN)ARE NOT REQUIRED BY CODE BUT ARE
SUGGESTED (ESPECULLLY WHEN USING FIBER RELNF. CONCRETE OR
IN EXTERIORCONDRIONSJ. OONTROL POINTS TO BE 1/8' SAW CUT
A DEPTH OF 1/4 OF THE THICKNESS OF THE SLAB. FILLCUT W/
APPROVED )DINT MATERIAL OR USE ALTERNATEAPPROVEO METHOD.
7 NO WOOD STAKES PERMITTED IN FOUNDATION.
8 PENDING SITE CONDITIONS, FOUNDATION MAY HAVE TO BE STEPPED
DOWN, O.C. TO DMNVNE STEP LOCATIONS WREQUIRED.
D ALL FOOTING $HALL BE MIN 12' BELOW GRADE
10 MASON TO COORIDATE WITH BUILDER ANY ELECTRICAL REQUIREMENT
THROUGH SLAB
I1 PROVIDE 4' STEPDOWN TO SIDEWALK FROM ENTRY
12 ASSUMEDALLOWABLESOIL BEARING PRESSURE AFrERCOMPACTION:
2000 PSF SEE SOILS REPORT AND SPECIFICATIONS FOR COMPACTION
REQUIREMENTS IF SOIL CONDTIONNS IN THE PROJECT DD NOT MEET OR
EXCEED THE CAPACITY THE GENERAL CONTRACTOR SHALL CONTACT THE
ENGINEER PRIOR TO FOUNDATIDN POUR FOR VERMCATION OF
FOUNDATION DESIGN. SOIL TO BE COMPACTED TO AT LEAST 95% OF MAX.
DRY DENSITY AS DETERMINED BY ASTM • 155T ( MODIFIED PROCTOR )
THE FOUNDATION SIZES INDICATED ON THE FOUNDATION PLAN HAS BEEN
OESIGNFD FOR A MINIMUM SOIL BEARING CAPACITY OF 2000 PSF.
8. Comment: Submitted truss drawing documents must be submitted with original signatures
and stamped reviewed and approved by the design professional. See Section 107.1 of the
2017 Florida Building Code.
Response: To be provided by Builder.
If you have any questions, please do not hesitate to call.
�oaeooBst,treiis
Sincerely, 101DO tvl-
.s
October 1, 2018 8r 1 018
Carl A. Brown, P.E .:���
FLPE# 56126 a' `� BE# 8212�, 4
'ell Aj
If Seal and Signature are not blue or cant be smudged contact FOR for authorization
"Doing Business with a Service Mindset and an Eye for Detail"
f 249 Maitland Ave, Suite 3000 1 Altamonte Springs, Florida 32701
P: (321)972-0491 1 F: (321)972-0484 E: info@fdseng.com
Website: www.fdseng.com
ENGINEERING ASSOCIATES
October 1, 2018 ; °"���G E NS�cOoNr 1, 2018
0 126
Carl A. Brown, P.E 'TodA. Boni
FLPE# 56126 =� 8 6
If Seal and Signature are not blue or can't be smudged contact FOR for authonza �o�i o00
"Doing Business with a Service Mindset and an Eye for Detail"
r"