Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
Client:, Ryan Homes
1450 C t k BI d S 't 340
en repar v ut e<`ce�Ppa 1e
West Palm Beach, FL 33401 ,VA' C,0��� ent
Project: Oakland Lake Subdivision Lot 68 - &i' 8®
5337 Oakland Lake Circle, Fort Pierce, St. Lucie County, FL Ole co
As requested, Universal Engineering Sciences, Inc. (UES) representative(s) performed constructionfriaterials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets; The contents of this package are summarized below:
Scope of Work
Work Order No. Date Type of Report
102332-1 1 11/01/2018 In -Place. Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
PROVED 0 APPROVED AS NOTED
11 REVISE & RESUBMIT 0 REJECTED/ RESUBMIT
❑ NOT REVIEWED ❑ FOR YOUR INFORMATION
Submittals are reviewed for conformance with design intent
and general compliance with the Contract Documents only.,
Notations Do Not Authoirize Changes to Contract Sum.
Approyal, comments and/or eorredtions does not relieve the
Contractor from compliance with the Contract Documents. The
Contractor is responsible for confirming and correlating air,
quantities, dimensions, tolerances, clearances, fabrication
processes, techniques and sequences of construction,
compatibility of materials and methods, coordination of their
work with other trades and subcontractors, rformance of
F i safe ajid satisfactory manner and full compuance
with I1 of :' I ,rac �/xuments.
7/
AT ED BY
A. B. D,t%N GROUP
NO.48.79s
• ,STATE OF
�fj7/ aON!
Sincerely,
Universal Engineering Sciences, Inc.
Certificate of Authorization No. 00000549
Richard E.
Hoaglin, P.E.
2018.11.02
11:58:33
-04'00'
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
This item has been electronically signed and sealed by
Richard E. Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verified on any electronic
copies.
ICC Email: cbugg@nvrinc.com; elibrihi@nvrinc.com; Imhoff, Bryan [BIMHOFF@nvrinc.com]; jomcalli@nvrinc.com; rofingar@nvrinc.com; sign/seal MAIL to
ryan homes at 1777 Willows Square, Vero Beach, FL 32966
I
LIES Project No: 0310.1700251.0031
UNIVERSAL LIES ROCS No:
_ LIES Report No: 102332-1 ARC 110118
ENGINEERING SCIENCES On -Site Time (hrs):1.00
Consultants In: Geotechnical Engineering • Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services • Materials Testing • Threshold Inspection Travel Time (hrs): 0.50
Building Code Administration, Compliance Inspection & Plan Review Total Time (hrs): 1.50
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 68
5337 Oakland Lake Circle, Fort Pierce, St. Lucie County, FL
Date lof Activity: Thursday, 01 November, 2018
Technician: Cliff
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the House pad.
Whiled on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering - Environmental Sciences
I Geophysical Services - Materials Testing - Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
CI
Project:
Area Tested:
Type Hof Test:
Tech i ician:
Requirements:
In -Place Density Test Report
UES Project No: 0310.1700251.0031
UES DOCS No:
UES Report No: 102332-1 DT 110118
Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Oakland Lake Subdivision Lot 68
5337 Oakland Lake Circle, Fort Pierce, St. Lucie County, FL
House pad
Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 11/01/2018
Lab: ASTM D1557 Modified Proctor
Cliff Cherrnay
l
95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underlyinq soils below the tested depths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1
N/W test
0-1 ft
12.00
21180
110.5
9.9
99 '
A
2
N/E test
0-1 ft
12.00
21180
109.6
9.8
98
A
3
S/E test
0-1 ft
12.00
21180
108.8
9.5
97
A
4
S/W test
0-1 ft
12.00
21180
110.6
10.3
99
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
j 21180
112.0
11.0
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This test was performed without deviation from ASTM procedures.
This r port shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.