HomeMy WebLinkAboutFIELD - LAB REPORT - 12-20-18c O —03V4
UES r ect No.: 0310.1700251.0032
UNIAMRSAL Date Typed: December 11, 2018
ENGINEERING SCIE:NCES
Consultai ts'ln Geotechnical:Engrneering • Environmental Sciences GeophysicaPServices • MateriMsTesting • Threshold In"spection FILE
COPY
Building Code Administration, Compliance Inspectionn& Plan Review
820 Brevard Avenue, Rockledge, FL 32965 - P: 321.638.0808 - F: 321.638.0978 . , 1 ` d 311
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
Client: Ryan Homes RECEIVED
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401 DEC 2 0 Z018
Project:, Oakland Lake Subdivision Lot 67 ST. Lucie County, PerrYiittirili
5321 Oakland Lake Circle Permit No 1810-0346, Fort Pierce, St. Lucie County;
As requested, Universal Engineering Sciences, Inc. (LIES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No. Date Type of Report
104051-1 12/07/2018 In -Place Density Test Report w/Activity Record
We hope, this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
4.
fr
GiEN
a q�
NQQ ,
♦-
v+
• ,�' C7l�it2, ,�`•
Sincerely,
Universal Engineering Sciences, Inc.
Certificate of Authorization No. 00000549
Richard E.
Hoaglin, P.E.
2018.12.12
16:13:00
-05'00'
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
This item has been electronically signed and sealed by
Richard E. Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verified on any electronic
copies.
ICC Email: cbugg@nvrinc.com; elibrihi@nvrine,com; Imhoff, Bryan [BIMHOFF@nvrinc.com]; jomcalli@nvrine.com; rofingar@nvrine.com; sign/seal MAIL to
ryan homes at 1777 Willows Square, Vero Beath, FL 32966
UES lat No: 0310.1700251.0032
UNIAM-
RSAL
UES DOCS No:
UES Report No: 10.4051-1 ARC 120718
ENGINEERING SCIENCES On -Site Time (hrs): 1.00
Consultants In":. 'otechnical Engineering Environmental Sciences Lab Time (hrs): 0.00
Geophysic#$ervices • MaierMTesting • Threshold lnspectign Travel Time (hrs): 1.00
Building CodeAdninistranon, Compliance inspection&'Plan Revievr Total Time (hrs): 2.00
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 67
1 5321 Oakland Lake Circle Permit No 1810-0346, Fort Pierce, St. Lucie County, FL
Date of Activity: Friday, 07 December, 2018
Technician: Cliff Cherrnay
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the House pad.
i
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
pad. All1test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirementp of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
up
ect No: 0310.1700251.0032
UNIVil-RSAL UES DOCS No:
• - ENGINEERING $CIENC:E_S UES Report No: 104051-1 DT 120718
Consuitants In: Geotechnical Engineering !Environmental Sciences
Geaphysical Services • Matehals Testing , Threshold In"specpo.n
Building Cone Adn►inisiiation; Coniplience Ins pectibn'& Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
In -Place Density Test Report
Client, Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 67
5321 Oakland Lake Circle Permit No 1810-0346, Fort Pierce, St. Lucie County, FL
Area Tested: House pad
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 12/07/2018
Lab: ASTM D1557 Modified Proctor
Technician: Cliff Cherrnay
Requirements- 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underlying soils below the tested depths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
% '
%
Compaction
Comments
(3)
1
N� test
0-1 ft
12.00
23343
106.3
11.1
97
A
2
N/E test
0-1 ft
12.00
23343
108.8
10.4
99
A
3
S IE test
0-1 ft
12.00
23343
105.9
10.6
97
A
4
S/W test
0-1 ft
12.00
23343
107.5
10.5
98
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
, Dry
Moisture
#
Density
Content
j 23343
109.5
12.5
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements.
C. Moisture does not meet requirements
D. Recompaction required -
E..Recompacted, Retested, Meets Requirements
This test was performed without deviation from ASTM procedures.
This report shall not be reproduced, except in full, without thewritten approval of Universal Engineering Sciences.