HomeMy WebLinkAboutHVAC LOAD CALCULATIONSThe Saitta Residence HVAC Load Calculations for i Mr. & Mrs. Saitta i Port St. Lucie, FI i R. H-- .. VA. H.VAC LoAvs Prepared By: Jose Nisair Air Conditioning 3497 5e Lionel Terrace Stuart, FI 34997 772=283=0904 Tuesday, April 12, 2005 Project Filename: C:\Elite\Rhvacw\Projects\Saitta.rhv Project (Title: The Saitta Residence Project bate: Friday, March 11, 2005 Client Name: Mr. & Mrs. Saitta Client City: Port St. Lucie, FI Company Name: Nisair Air Conditioning Company Representative: Jose Company Address: 3497 Se Lionel Terrace Company City: Stuart, FI 34997 Company Phone: 772-283-0904 Refere , ce City: Fort Pierce, Florida Daily Temperature Range: Medium Latitude: 27 Degrees Elevation: 25 ft. Altitude; Factor: 0.999 Elevation Sensible Adj. Factor: 1.000 Elevation Total Adj. Factor: 1.000 Elevation Heating Adj.-Factor: 1.000 Elevation Heating Adj. Factor: 1.000 Outdoor Outdoor Indoor Indoor Grains Drni Bulb Wet-BUIb Rel.Hum Dry Bulb Difference Winter: 42 0 0 72 0 Summer: 90 78 50 75 61 Total Building Supply CFM: 1,554 (4.3 AC/hr) CFM Per Square ft.: 0.667 Square ft. of Room Area: 2,331 Square ft. Per Ton: 616 Calculations are based on 8th edition of ACCA Manual J. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads. Winter: 42 0 30 72 3,44 Summer: 90 78 50 75 61,09 ,................................................................................................::.:.: ��,}} ,�,�i.��yy��,�� }}}} ��.�yy.���� iti{::i(iiit i ii.::ii iiiiitii�������:�����.��.���'iA������������i::iiiiiitiCJ):[::::::::::[::[::::::::::y: '�ri�G1If'i�Z'.L/fZiiii'�:�ii.: j:i2ij>.`,.:::::•jjii :;i::y:.:::::.<:}: iii i :;::•i;isi ti:•ii};•'+;.....•.Y}:?....... :•:.:C%2:ii:.:i:::::::[:::.::i.:.:.}:n:;?;• :•:i \iii•:Miiiiiivi:iiiih Main Trunk Runouts... Calculate: Yes Yes Use Scedule: Yes Yes Roughness Factor: 0.00300 0.01000. Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wgJ100,ft. Minimum Velocity: 650 Umin 450 ft./min Ma)dmum Velocity: 900 ft./min 750 Urnin Minimum Height: 0 in. 0. in. Ma)dmum Height: 0 in. 0 in. :. Winter Summer Infiltration: 0.700 AC/hr 0.400 AC/hr Volume'of Conditioned Space: X 21679 Cu.ft. X 21679 Cuk 15,175 Cu.ft./hr 8,672 Cu.ft./hr X 0.0167 X 0.0167 Total Building Infiltration: 253 CFM 145 CFM Total Building Ventilation: 0 CFM 0 CFM —System 1— Infiltration & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 32.97 = (1.10 X 0.999 X 30.00 Winter Temp. Difference) System 1 Zone 1 1-Foyer/Hall 2-Din 3-Bdrrn #2 4-Bdrrn #1 5-Den 6-Bath #2 7-Ufil' 10-Liv Rm 11-Mstr Bth 12-WIC #2 13-WIC #1 14-Mstr Bdrm 2,331 img 2,331 2,331 200 169 260 247 192 66 84 18 154 456 126 42 51 266 34,166 11,216 45,382 48,130 34,166 11,216 45,382 48,130 2,479 360 2,839 3,180 4,955 743 5,698 71034 5,122 1,517 6,639 6,956 2,136 724 2,860 3,024 1,634 415 2,049 2,467 984 833 1,89 7 1,694 1,255 1,806 3,061 2,744 48 87 135 259 410 1,287 1,697 785 6,242 606 6,848 7,635 2,800 1,243 4,043 3,773 112 87 199 337 304 319 623 1,101 5,685 1,189 6,874 7,141 626 1,554 1,554 626 1,554 1,554 16A 7 626 1,554 1,554 41 113 113 1-6 91 225 225 2-6 90 233 233 2-6 39 97 97 1-6 32 74 74 1-5 22 45 45 1-4 36 57 57 1-4 3 2 2 1-4 10 19 19 1-4 99 284 284 24 49 127 127 1-7 4 5 5 1-4 14 14 14 1-4 93 259 259 2-7 Loans 10A-m: (Glazing -French door, single pane clear glass, 61.2 3,066 0 2,544 2,544 metal frame no break, ground reflectance = 0.32, outdoor insect screen with 50% coverage, dark color drapes with loose weave with 25% coverage 1A-hb-6: Glazing -Single pane, operable window, heat- 30.1 975 0 1,084 1,084 absorbing, metal frame with break, ground reflectance = 0 J32, dark color drapes with loose weave with 25% coverage 10A-m: Glazing -French door, single pane clear glass, 139.4 6,984 0 6,444 6,444 metal frame no break, ground reflectance = 0.32, dark color drapes with loose weave with 25% coverage 1A-hb-o: Glazing -Single pane, operable window, heat- 199 6,450 0 10,112 10,112 absorbing, metal frame with break, ground reflectance = 0.32, outdoor insect screen with 50% coverage, dark color drapes with loose weave with 25% coverage 1A-hb-o:-Glazing-Single pane, operable window, heat- 9 292 0 259 259 absorbing, metal frame with break, ground reflectance = 0132, outdoor insect screen with 100% coverage, dark color drapes with loose weave with 25% coverage 13A-5ocs: Wall -Block, board insulation only, R-5 board 1602.7 6,011 0 2,216 2,216 insulation, open core, siding finish 16B-194 Roof/Ceiling-Under attic or knee wall, Vented 2331 3,424 0 5,711 5,711 Attic, No Radiant Barrier, Dark Asphalt Shingles or Dark Metal, Tar and Gravel or Membrane, R-19 insulation 22A-pm: Floor -Slab on grade, No edge insulation, no 247 8,746 0 0 0 insulation below floor, any floor cover, passive, heavy - drylor light wet soil Subtotals for structure: 35,948. 0 28,370 28,370 People: 3 600 690 1,290 ' Equipment: 3,400 0 3,400 Lighting: 0 0 0 Ductwork: 3,841 1,218 2,723 3,941 Infiltration: Winter CFM: 253, Summer CFM: 145 8,341 5,998 2,383 8,381 Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0 Total Building Load Totals: 48,130 11,216 34,166 45,382 Total Building Supply CFM: 1,554 (4.3 AC/hr) CFM Per Square ft.: 0.667 Squat el ft. of Room Area: 2,331 Square ft. Per Ton: 616 .......................................................................................................................................:..............................:....................................................................................................... Total Heating Required With Outside Air: 48,130 Btuh 48.130 MBH Total Sensible Gain: 34,166 Btuh 75 % Total Latent Gain: 11,216 Btuh 25 % Total Cooling Required With Outside Air: 45,382 Btuh 3.78 Tons (Based On Sensible + Latent) >lf3t:.:................................................:.......................................:.....................:...:............:..................................:...:.................:........................................................................:..... :»<: Calculations are based on 8th edition of ACCA Manual J. Ala computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads. System 7 Saitta Residence Summary Loads (Peak Method) .. ..... .. w.,, ... .. .. .... ...... ............:: x. \\t}jam\\\�� ::iii'•; \.: i�f: R'.YVF:..- � v:l :.v:.:. vyXXff :• Cits.i'iiiiii-:?`•'''i::i::i::isYv''2:1!`.W ��� Ifs?`•��`��;�<�?z>_`?l�Ef`>':'•:�>......:.:#1 ..................iutiflt: k T: 10A-m:Glazing-French door, single pane clear glass, 61.2 3,066 0 2,544 2,544 metal frame no break, ground reflectance = 0.32, outdoor insect screen with 50% coverage, dark color drapes with loose weave with 25% coverage 1A-hb-6: Glazing -Single pane, operable window, heat- 30.1 975 0 1,084 1,084 absorbing, metal frame with break, ground reflectance = 0.i32, dark color drapes with loose weave with 25% coverage 10A-m:I,Glazing-French door, single pane clear glass, 139.4 6,984 0 6,444 6,444 metal frame no break, ground reflectance = 0.32, dark color drapes with loose weave with 25% coverage 1A-hb-o: Glazing -Single pane, operable window, heat- 199 6,450 0 10,112 10,112 absorbing; metal frame with break, ground reflectance = 0132, outdoor insect screen with 50% coverage, dark color drapes with loose weave with 25% coverage 1A-hb-6: Glazing -Single pane, operable window, heat- 9 292 0 259 259 absorbing, metal frame with break, ground reflectance = 0E32, outdoor insect screen with 100% coverage, dark color drapes with loose weave with 25% coverage 13A-5ocs: Wall -Block, board insulation only, R-5 board 1602.7 6,011 0 2,216 2,216 insulation, open core, siding finish 16B-19Roof/Ceiling-Under attic or knee wall, Vented 2331 3,424 0 5,711 5,711 Attic, No Radiant Barrier, Dark Asphalt Shingles or Dark Metal, Tar and Gravel or Membrane, R-19 insulation 22A-pm: Floor -Slab on grade, No edge insulation, no 247 8,746 0 0 0 insulation below floor, any floor cover, passive, heavy dry�or light wet soil Subtotals for structure: 35,948 0 28,370 28,370 People: 3 600 690 1,290 Equipment: 3,400 0 3,400 Lighting: 0 0 0. Ductwork: 3,841 1,218 2,723. 3,941 Infiltration: Winter CFM: 253, Summer CFM: 145 8,341 5,998 2,383 8,381 Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0 System 1 Saitta Residence Load Totals: 48,130 11,216 34,166 45,382 Supply CFM: 1,554 (4.3 AC/hr) CFM Per Square ft.: 0.667 Square ft. of Room Area: 2,331 Square ft. Per Ton: 616 ::• .....:.:: •Tpl: .. :A:. Total Heating Required With Outside Air: 48,130 Btuh 48.130 MBH Total Sensible Gain: 34166 Btuh 75 % Total Latent Gain: 11,216 Btuh 25 % Total Cooling Required With Outside Air: 45,382 Btuh 3.78 Tons (Based On Sensible + Latent) Calculations are based on 8th edition of ACCA Manual J. AM computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads. System 1, Zone ' Summary Loans (Peak Method) 10A-m: Glazing -French door, single pane clear glass, metal frame no break, ground reflectance = 0.32, 61.2 3,066 0 2,544 2,544 outdoor insect screen with 50% coverage, dark color drapes with loose weave with 25% coverage 1A-hb-o: Glazing -Single pane, operable -window, heat- 30.1 975 0 1,084 1,084 absorbing, metal frame with break, ground reflectance = 0.32, dark color drapes with loose weave with 25% coverage 10A-m: Glazing -French door, single pane clear glass, 139.4 6,984 0 6,444 6,444 metal frame no break, ground reflectance = 0.32, dark color drapes with loose weave with 25°% coverage 1A-hb-o: Glazing -Single pane, operable window, heat- 199 6,450 0 10,112 10,112 absorbing, metal frame with break, ground reflectance = 0132, outdoor insect screen with 50% coverage, dark color drapes with loose weave with 25% coverage 1A-hb-o: Glazing -Single pane, operable window, heat- 9 292 0 259 259 absorbing, metal frame with break, ground reflectance = 0i32, outdoor insect screen with 100% coverage, dark color drapes with loose weave with 25%coverage 13A-5ocs: Wall -Block, board insulation only, R-5 board 1602.7 6,011 0 2,216 2,216 ins l lation, open core, siding finish 16B-19: Roof/Ceiling-Under attic or knee wall, Vented 2331 3,424 0 5,711 5,711 Attic, No Radiant Barrier, Dark Asphalt Shingles or Dark Metal, Tar and Gravel or Membrane, R-19 ins l lation 22A-pm: Floor -Slab on grade, No edge insulation, no 247 8,746 0 0 0 insulation below floor, any floor cover, passive, heavy dryl or light wet soil Subtotals for structure: 35,948 0 28,370 28,370 People: 3 600 690 1,290 Equipment: 3,400 0 3,400 Lighting: 0 0 0 Ductwork: 3,841 1,218 2,723 3,941 Infiltraiion: Winter CFM: 253, Summer CFM: 145 8,341 5,998 2,383 8,381 Syste 1, Zone 1 Load Totals: 48,130 11,216 34,166 45,382 ..................... Supply CFM: 1,554 (4.3 AC/hr) CFM Per Square ft.: 0.667 Square ft. of Room Area: 2,331 Square ft. Per Ton: 616 ::::.::::::.::::::::::...................................................................................................................................................................................... ,«.>:.,,:. :...>::;:.>:..;:..:.::..::.::.::::::::::::::::::::::::::::::::::::::.:.....::::::::::::::::.:::::::::::::::::::::::::::.:::::::::::::::.:::::.::::::.::::::. t•::::::::::..t..t................................................................................... Total Heating Required: 48,130 Btuh 48.130 MBH Total Sensible Gain: 34,166 Btuh 75 % Total Latent Gain: 11,216 Btuh 25 % Total Cooling Required: 45,382 Btuh 3.78 Tons (Based On Sensible + Latent) :iit::isiit?iiiii::ii::i::i�'?i��ii:•i:;:yj:�::•i:;;•iiiiiiiiiiiiii:•:viiiiiiiiiiiiiiii\::�i vti\ii`::::'.`.::i::::isi?::::±:$?:ii::i:�:�:::::::?vj:-:ii::i� tvv\\;::• Calculations are based on 8th edition of ACCA Manual J. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads. Detailed Room Loads - Room I - Foyer/Hall (Peek Method) j :...: Calcul' tion Mode: H & cl . Occurrences: 1 Room Length. 16.0 % System Number: 1 Room Width: 12.5 ft. Zone Number: 1 Area: 200.0 sq.ft. Supply Air: 113 CFM Ceiling Height: 9.3 ft. " Supply Air Changes: 3.6 AC/hr Volume: 1,860.0 cu.ft. Required Vent.: 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM Runo6tAir: 113 CFM Percent of Supply.: 0 % Runo6t Duct Size: 6 in. Actual Summer Vent.: 0 CFM Runout Air Velocity: 574 Urnin. Percent of Supply: 0 % Desigri Loss: 0.100 in.wg./100 ft. Actual Winter Infill: 12 CFM Actual Loss 0.211 in.wg.l100 ft. Actual Summer Infil.: 7 CFM :::::...::.:.....:.::::::.:::::::.......................................,.......:..:......: ,:.:.:.:-:.:.:................:..................:.:.::::.::.::::.....%... .,, Ott]#:�:<•?::.????::•::;•?>:•?:•?:•?:•}::•:f•:::::•}s>::>:<}.•?::}:::}:;.?:-???:-?::.?:.??:.?::•}:.?::•::•::•?:-?:;;•?>: ::.. ' ..:..::::...,....................................4vvvv.vnvv •.vv.vv.::::v: :..�::::: ::tt:;^:?:?: :•: :w:: x:::::::::::::::: w:::.v: :r.::::.b:::: ;:.?v„ :v :::•. :::,......:.............. .� ......... n... r......r........:...:..:...2-:2:'._-:.i{;�-::it\22{•tiiii kii \'.k,:t•:•:t;...?:. .:....... .....::: ...::::: .. .. ... ••vi:•:•:{.:2iS:•:t•:iti-? •: .. ............:..y :}:::I:i%::{::�Yli:isisiiiyli:{iiQ[�•L':j:::i:i::?:}Li:':i:i::G N Mal 1-1 3A-5ocs 10 X 9.3 51.5 0.125 3.8 193 1.4 0 74 N -GIs 10A-m shgc-0.53100%S 20.4 1.670 50.1 1,022 41.6 0 848 N-GIs11A-hb-o shgc-0.52100%oS 13.6 1.680 32.4 440 36.0 0 490 (2)1N -GIs-1A-hb-o.shgc-0.52100%S 7.5 1.080 32.4 243 36.0 0 270 U P-Ceil-1 613-19 16 X 12.5 200 0.049 1.5 294 2.5 0 490 Floor-22A-pm 10 ft..Per. 10 1.180 35.4 354 0.0 0 0 Subtotals for Structure: 2,546 0 . 2,172 Infil.: in.: 11.5, Sum.: 6.6 93 4.086 380 1.172 273 109 Ductwork: 0.087 254 0.087 87 198 Room �otals: 3,180 360 2,479 Detailed Room Loads - Room 2 - Din. (Peak Method) 10•Calculation Mode: Htg. & c1g. Occurrences: 1 Room Length: 13.0 ft. System Number. 1 Room Width: 13.0 ft. Zone Number: I Area, 169.0 sq.ft. Supply Air: 225 CFM Ceiling �Height: 9.3 ft. Supply Air Changes: 8-.6 AC/hr Volume: 1,572.0 cu.ft. Required Vent.: 0 CFM Numbe I r of Registers: 2 Actual Winter Vent.: 0 CFM Runoui,Air: 113 CFM Percent of Supply.: 0 % Runout Duct Size: 6 in. Actual Summer Vent.: 0 CFM Runouj, Air Velocity: 574 ft./min. Percent -of Supply: 0 % DesignILoss: 0.100 in.wg./l 00 ft. Actual Winter Infil.: 28 CFM Actual Loss: 0.210 in.wg./I 00 ft. Actual Summer Infil.: 16 CFM .................. ....... .......... E -Wall'l 3A-5ocs 13 X 9.3 71.1 0.125 3.8 267 0.8 0 57 S -Wall il 3A-5ocs 11 X 9.3 61.3 0.125 3.8 230 0.9 0 54 E -Gls-i0A-m shgc-0.53 100%S (2) 40.8 1.670 50.1 2,044 46.2 0 1,886 E -GIs-I,A-hb-o shgc-0.52 100%S 9 1.080 32.4 292 36.0 0 324 S -GIs-1, A-hb-D shjc-0.52 1 00%S 24 1.080 32.4 778 32.4 0 778 (2)1 S -GIs-I OA-m shgc-0.53 100%S 17 1.670 50.1 852 46.2 0 786 ' UP-Ceil,-1 613-19 1'3 X 13 169 0.049 1.5 248 2.5 0 414 Floor-22A-pm 24 ft..Per. 24 1.180 35.4 850 0.0 0 0 1 Subtotals for Structure: 5,561 0 4,299 Infil.: Win.: 27.7, Sum.: 15.8 223 4.086 912 1.169 656 261 Ductwork: 6.087 561 0.087 87 395 Room Totals: 7,034 743 4,955 cr"'J6.it 'wIM i#ti `f d " ...:: »»»> <» .... Detailed Room Loads. - Room 3 - Bdrm #2 (Peek Method) ......................................................... ::..::........:.............................................:.....:............... .......... .......................................................................:.::.....:.:: _.:..................::......:::.:.......:. _::..... ....... .:::......::.:::,::....:..::.:.. Calculation Mode: Ht & cl 9 9 Occurrences: 1 Room Length. 20.0 ft. System Number: 1 Room Width: 13.0 ft. Zone Number, 1 Area: 260.0 sq.ft. Supply Air: - 233 CFM Ceiling Height: 9.3 ft. Supply Air Changes: 5.8 AC/hr Volume: 2,418.0 cu.ft. Required Vent.: 0 CFM Number of Registers: 2 Actual Winter Vent.: 0 CFM RunootAir. 117 CFM Percent of Supply.: 0 % Runodt Duct Size: 6 in.. Actual'Summer Vent.: 0 CFM Runout Air Velocity: 593 ft./min. Percent of Supply: 0 % Desig � Loss: 0.100 in.wg./100 ft. Actual Winter Infil.: 52 CFM Actual, Loss: 0.225 in.Wg.1100 ft. Actual Summer Infil.: 30 CFM l6HFiT:::t.s:• :::»>»:;«:;:: E: N -Wall-13A-5ocs 13 X 9.3 96.9 0.1,25 3.8 363 1.4 0 139 W -Wall-13A-5ocs 20 X 9.3 170 0.125 3.8 638 2.8 0 470 S-Wa1-13A-5ocs 12 X 9.3 111.6 0.125 3.8 419 0.9 0 98 N-GIOA-hb-o shgc-0.52 1 00%S 24 1.080 32.4 778 32.4 0 778 (2)� W -Gls 1 A-hb-o shgc-0.52 0%S (2) 16 1.080 32.4 518 117.1 0 1,874 LIP-Cell-1613-19 20 X 13 Floor-22A-pm 45 ft..Per. 260 0.049 45 1.180 1.5 382 35.4 1,593 2.5 0.0 0 0 637 0 Subtotals for Structure: 4,691 0 3,996 Infil.: Win.: 51.9, Sum.:29.6 419 4.086 1,710 1.166 1,230 488 Ductwork: 6.087 555 0.087 87 408, People: 200 lat/per, 230 sen/per: 1 200 230 Room Totals: 6,956 1,517 5,122 i Detailed Room- Loads - Room 4, - Bdrm #1 (Peak Method) . . . ......... .. ..... .. * . ...... Calculation Mode: Htg. & c1g. Occurrences: 1 Room Length; 1910 ft. System Number: 1 Room VVidth. 13.0 ft. Zone Number:' 1 Are., � 247.0 sq.ft. Supply Air: 97 CFM Ceiling Height: 9.3 ft. Supply Air Changes: 2.5 AC/hr Volum'e: 2,297.0 cu.ft. Required Vent.: 0 CFM Numbe'r of Registers: 1 Actual Winter Vent.: 0 CFM Runou I t Air: 97 CFM Percent of Supply.: 0 % RunoUt Duct Size: 6 in. Actual Summer Vent.: 0 CFM Runout Air Velocity: 495 ft./min. Percent of Supply: 0 % Design Loss: 0.100 in.wg./l 00 ft. Actual Winter Infil.: 18 CFM Actual� Loss. 0.157 in.WgJl 00 ft. Actual Summer Infil.: IT CFM .... ...... . ..... .XX­ ........... ............. N -Wall-1 3A-5ocs 16 X 9.3 124.8 0.125 3.8 468 1.4 0 179 N -GIs-,I A-h b-o shgc-0.52 I 00%S 24 1.080 32.4 778 32.4 0 778 (2) UP-Ceiki 6EI-19 19 X 13 247 0.049 1.5 363 2.5 0 605 Ftoor-2'2A-pm 16 ft..Per. 16 1.180 35.4 566 0.0 0 0 Subtotal Is for Structure: 2,175 0 1,562 Infil.: Win.: 18.4, Sum.: 10.5 149 4.086 608 1.169 4137 174, I - Ductwork: 0.087 241 0.087 87 170 Peopled 200 lattper, 230 sen/per: 1 200 230 Room 3,024 724 2,136 Deta �1ed Room Loads. - Roam' 5 - Den (Peak Method) . . ..•-•:. v: ::v :w::::::::::::::: nv wn\\.}}}}}}}J}}Ji}}:;¢};±.}}}}:i•;{ry}:{•}:4:^;{:;}:v}i}i}}iJi:i};p}};•y;{.};i;}}}}}}}};{{!•}:?:}}:{{.. ............................t.............................................................. ... ..... .... . ......................................... ........ ................w: ..... ................. .....................:...:: w:::::: •:::::..n•v :............. . .... v.......v:.:v:::•::.....t..............:................... .. w:{:::•:::::::n•...... t.:}J}:tiff?}:::i4:•J:j'i .: i•::v: -- O}\.}}� \.\i\ti tti{{ti::.yYJl:rni:.}.v..\\vv.............\n4.....v...,.......n ..................................... }:{i'}J:: J:: : •.:::::::::. kh\ti,v}}:Ct Calculation Mode: Htg. & clg. Occurrences: 1 Room Length. 16.0 ft. System Number: 1 Room Width. 12.0 ft. Zone Number. 1 Area: 1 192.0 sq.ft. Supply Air: 74 CFM Ceiling Height: 9.3 ft. Supply Air Changes: 2.5 AC/hr Volume: 1,786.0 cu.ft. Required Vent.: 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM Runout Air: 74 CFM Percent of Supply.: 0 % Runout Duct Size: 5 in. Actual Summer Vent.: 0 CFM Runout Air Velocity: 545 ft./min. Percent of Supply: 0 % Design Loss: 0.100 in:wg./100 ft. Actual Winter Infil.: 14 CFM Actual Loss: 0.245 in.wg./100 ft. Actual Summer Infil.: 8 CFM ........... ..:..........,..:. .:.. J.:...............:...............::::::::::::::::::::::::::::::::::::::::::::: \•: w::.:::::::::::::::::::::::......::::::::i-}J}JJJ}i:{ti4:{.i:^iii:^}}}Y•}}:•}: ......::...:.:::. �:::::::::::::::::: ....... . w:...............................t........ .::n:: :::•.,:• ............................t.. . ................................................................................y .. n.....................................................t............................... .:..:..:... ......r.:..:::::.t.:.•:::::\::...: ., ..:::: }::: v.N.3-.\.k: :..: :.: :....::.-:.:..:,x .: .:.:.:...................:.....:: v: {{: w- :;•. iac�n-J::J:.J:.J:.J:.J:.J:.JJ}}}>}}}?>}:^}::..t...:.:i.}::;}::}'. p {...........:... }::. �'ICF�i:::<:i$iii:::{:;{:isG:ii:i�w�il:y:i:i:::<?}::ii:}:iii}::i:::•: n:::,:..v.,,vvv. � j' :.�ii::}:::::;± :y::} ''. {y��} f� .......:...................:......................... .... •}:{....,. v- vw::?Y.�!!: -w: w:i•:::.{•:: x: :w::.1vi:::::::: ................ ................. ..tttt:v,:.. }.:.... .. .. .tv. .t.... .. . ......................t.{ ..:......tv.. ... ... •Ila:::::::v::;. :.:::::: :..:... t• w::.v:•: ::w::x J.vt.......... ... ...... ........w.P: .: ... .......:: •: •:: •.::: ...., .: .... ;.:........... ....:>.:.:..... � �iij:•}T: i{>. i:Jj}{yYi'rV�S�.:{iG:i{ n H. 1�...:.::.:............H.....................:... :p:: ...,.,..:............ �} L{' •'4 ''v'viiiiijii;::•Q T. •. •: ::: •: m:n:.v.v..:.:::::::.-::::::: vw:.tw: . t.......................... ... v . .... w: }::::.. . .t.... :I✓Te�n N-Wall-5ocs 12 X 9.3 87.6 0.125 ............. 3.8 329 ............ 1.4 0 126 N -Gis-I A-hb-o shgc-0.52 100%S 24 1.080 32.4 778 32.4 0 778 (2)1 UP-Ceil-16B-1916 X 12 192- 0.049 1.5 282 2.5 0 470 Floor-22A-pm 12 ft..Per. 12 1.180 35.4 425 0.0 0 0 Infil.: Win.: 13.8, Sum.: 7.9 Ductwork: Room Totals: 1,814 0 1,374 112 4.086 456 1.165 328 130 0.087 197 0.087 87 130 2,467 415 1,634 Detailed Room Loads - Room 6 - Bath #2 (Peak Method) Calculation Mode: Htg, & clg. Occurrences: 1 Room Length: 11 A % System Number: 1 Room Width; 6.0 ft. Zone Number: 1 Area: 66.0 sq.ft. Supply Air: 45 CFM Ceiling Height: 9.3 ft. Supply Air Changes: 4.4 AC/hr Volume: 614.0 cu.ft. Required Vent.: 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM Runout Air: 45 CFM Percent of Supply.: 0 % Runout Duct Size: 4 in. Actual Summer Vent.: 0 CFM Runout Air Velocity: 513 Urnin. Percent of Supply: 0 % Design Loss: 0.100 in.wg./100 ft. Actual Winter Infil.: 10 CFM Actuali Loss: 0.297 in.wg./100 ft. Actual Summer Infil.: 6 CFM .,. ..:n:v.v....vn\i::i::�:: ::: ::�ii::vi:ii?}.{{{t{iii� ^ ..:.{{{{{{ti{{{{{{{{{3 .:....... .................. >:::«<:>::: >:::<:::::::::>:::::::::::::::> >«< <>«>.<,:ea.....:>.:«:....:;:><::»:. t-:<;:::>::>::>::>::>::>::>:::: H: ::>::� o> >:::::::> ... ...... y......... . .y•• ::{::::::::}i::}::{::.. ;: •:: •.�: «:> »««: C ::<:::...... w..............:.::.:...........::::.:::::::::::,...........:::::::::,:..::::::::::::::::::::::::::::::::::::::::::.:::::::::::::.:::: T6so : »»> »» :::::<> ;> « L#dT1 >:lf8toe: ;;;;;;;,,>.; =' H'I•tV� ;............... os� <:::::<::<::»::: H �is<::::>:::::::>::>::«:>:i�eEn: N -Wall-13A-5ocs 9 X 9.3 66.7 0.1.25 3.8• 250 1.4 0 96 N -Gls i1A-hb-o shgc-0.52 1 00%S 17 1.080 32.4 551 32.4 0 550 UP-Ceil-I613-1911 X 6 66 0.049 1.5 97 2.5 0 162 Floor-22A-pm 9 ft..Per. 9 1.180 35.4 319 0.0 0 0 Subtotals for Structure: 1,217 0 808 Infil.: Win.: 10.4, Sum.: 5.9 84 4.086 342 1.171 246 98 Ductwork: 0.087 135 0.087 87 78 Eciuir)ment: 500 0 Room Totals: 1,694 833 984 I Detailed Room Loads - Room 7 - Utility- (Peak Method) .. . . . .. ... .... *.-,.,,......,.......'..'...--.-.....-......,..:, .. . ... . .. . ...... ... . Calculation Mode: ...... H4 & c1g. Occurrences: 1 Room Length: 12.0 ft. System Number: 1 Room Width. 7.0 ft. Zone Number: I Area. 84.0 sq.ft. Supply Air: 57 CFM Ceiling Height: 9.3 ft. Supply Air Changes: 4.4 AC/hr Volume: 781.0 cu.ft. Required Vent.: - 0 CFM Number of Registers: I Actual Winter Vent.: 0 CFM Runout Air: 57 CFM Percent of Supply.: 0 % Runout Duct Size: 4 in. Actual Summer Vent.: 0 CFM Runout Air Velocity: 654 ft./min. Percent of Supply: 0 % Design) Loss: 0.100 irmg./I 00 ft. Actual Winter Infil.: 22 CFM Actual Loss: 0.481 in.wg./l 00 ft. Actual Summer Infil.: 13 CFM U .................... ................... --------- --- a W -Wall-1 3A-5ocs 12 X 9.3 111.6 0.125 3.8 419 2.8 0 308 S -Wall il 3A-5ocs 7 X 9.3 53.1 0.125 3.8 199 0.9 0 46 S -GIs-I A-hb-o shgc-0.52 1 00%S 12 1.080 32.4 389 32.4 0 389 UP-Ceil -1613-19 12 X 7 84 0.049 1.5 123 2.5 0 206 Floor-22A-pm 19 ft..Per. 19 1.180 35.4 673 0.0 0 0 Subtotalls for Structure: 1,803 0 9419 Infil.: Win.: 21.9, Sum.: 12.5 177 4.086 722 1.166 519 206 Ductwork: 6.087 219 0.087 87 100 Equi ment: 1,200 0 Room Totals: 2,744 1,806 1,255 tvai:isiiiritiai:&.t.:: > »»:»>:»»><: <:> :»f titGnirnm..rcr:lt c��d............................................... 79.. =:......... `......::: > »:>>«: <> < <> « «..... �;: ci#i�ai� C3etrelzr"t3 6 R. :........:..:.............:............................. . Detailed Room Loads - Room 8 - Pantry (Peak Method) Calcul on Mode: Htg. & clg. Occurrences: 1 Room Length: 6.0 ft. System Number: 1 Room Width; 3.0 ft. Zone Number: 1 Area: 18.0 sq.ft. Supply Air: 2 CFM Ceiling Height: 9.3 ft. Supply Air Changes: 0.8 AC/hr Volume: 167.0 cu.ft. Required Vent.: 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM" Runout Air: 3 CFM Percenf of Supply.: 0 % Runout Duct Size: 4 in. ' Actual Sumfner Vent.: 0 CFM Runout Air Velocity: 39 ft./min. Percent of Supply: 0 % Design Loss: 0.100 in.wg./100 ft. Actual Winter Infil.: 0 CFM Actual Loss: 0.002 in.wg./100 ft. Actual Summer Infil.: 0 CFM UP-Cei'-1613-19 Floor-22A-pm 6 X 3 6 ft..Per. 18 0.049 1.5 6 1.180, 35.4 26 212 2.5 0.0 0 0 44 0 Subtotals for Structure: 238 0 44 Infil.: Win.: 0.0, Sum.: 0.0 0, 0 0 0, 0 0 Duciwork: 0.087 21 0.087 87 4 Room Totals: 259 87 48 Koom wain; i I .0 U. LUIIe INUIIIIJCI. 1 Area: 154.0 sq.ft. Supply Air: 19 CFM Ceiling Height: 9.3 ft. Supply Air Changes: 0.8 AC/hr Volume: 1,432.0 cu.ft. Required Vent.: ' 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM -Runout Air: 19 CFM Percent of Supply:: 0 % Runout Duct Size: 4 in. Actual Summer Vent.: 0 CFM Runout Air Velocity: 214 Umin. Percent of Supply: 0 % • Desig , Loss: 0.100 in.wg./100 ft. Actual Winter Infil.: 0 CFM Actual1Loss: 0.054 in.wg./100 ft', Actual Summer Infil.: 0 CFM ::.:::..:::::::::::;::::..:::._:.:::.:.:.:...::...:::::::.::.:...:......:.:......................:.::.::::.::.::.::.;:.::.;:.;;:.;:.;.... ..,..,.......,...... ...................Sep;::.:;;:.::::::. vw::.:}::, ;:fie : • I;r�n:>::::>::<::::::::::::::.:::::::::. ..:::::::.�:.,. .,.,. . UP-Cei-1613-19 14 X 11 154 0.049 1.5 226 2.5 0 377 Floor-22A-pm 14 ft..Per. 14 1.180 35.4 496 0.0 0 0 Subtotals for Structure: 722 0 377 Infil.: Win.: 0.0, Sum.: 0.0 0 0 0 0 0 0 Ductwork: 0.087 63 0.087 87 33. Equipment: 1,200. 0 Room Totals: 785 1,287 410 Calcul Room Room Loads. - Room 9 - Kitchen (Peak Metha Mode Htg. & c1g. Occurrences: 14.0 ft. Sv--,tem Number: Room- Loads - Room 10 - Liv Rm (Peak Method) Aode: Htg. & clg. Occurrences: Room Length: 24.0 ft, System Number: r Room Width: 19.0 ft. Zone Number. Area: 456.0 sq,ft, Supply Air: Ceiling Height: 9.3 ft. Supply Air Changes: Volume: 4,241.0 cu.ft. Required Vent.: Number of Registers: 2 Actual Winter Vent,: Runout Air: 142 CFM Percent of Supply.: Runout Duct Size: 7 in, Actual Summer Vent.: Runout Air Velocity: 531 ft./min. Percent of Supply: DesignlLoss: 0.100 in.wgJ100 ft. Actual Winter Infil.: Actual Loss: 0.146 in.wg./100 ft, Actual Summer Infil.: €if`?<«<<s' i >`:: ":>:» >>>>.............. :<_:.`: ?» >>?:::Are :«««:> «` .::<;:>:::;:>::>::>::::::::::. :::>: ............ ' L{i'A:Yi::«STTT:?:<fi:<?:?:?f?????i:�iii:{•`.C•`.it .1LTGi:1 ', �•:. S -Wall 13A-5ocs 19 X 9.3 77.1 0.125 3.8 289 0.9 S-Gls-10A-m shgc-0.53 100%S (4) 81.6 1.670, 50.1 4,088 46.2 S -GIs-1A-hb-o shgc-0.52100%S 18 1.080 32.4 584 32.3 (2) UP-Ceil 16B-19 24 X 19 456 0.049 1.5 670 2.5 Floor-22A-pm 19 ft..Per. 19 1.180 35.4 673 0.0 1 1 284 CFM 4.0 AC/hr 0 CFM 0 CFM 0 % 0 CFM 0 % 22 CFM 13 CFM ............ . :>:::: »;»:::::Gat >.: 0 67 0 3,772 0 582 0 1,117 0 0 Subtotals for Structure: 6,304 0 5,538 Infil.: Wn.: 21.9, Sum.:12.5 177 4.086 722 1.166 519 206 Ductwork: 0.087 609 0.087 87 498 Room Totals: I i 7,635 606 6,242 1 1 127 CFM 6.5 AC/hr 0 CFM 0 CFM 0 % 0 CFM 0 % 28 CFM 16 CFM 0 57 0 389 0 1,378 0 309 0 0 Subtotals for Structure: 2,560 0 2,316 Infil.: Wi'n.: 27.7, Sum.:15.8 223 4.086 912 1.169 656 261 Ductwork: 0.087 301 0.087 87 223 Equipment: 500 0 Room Totals: 3,773 1,243 2,800 I r` � 1 �::::.�. .::: ..v: :.: :. .::. :: .:. .:�v. .: ...::: ::.::::: ::::..r;.iiii:Y..:Li:::i::::iii�::i::ii::is�_::::_::�ivivi::<::::CCLC::<:i::i:<:i:C:i::i::i::i::i: :. fi'e`.-.I�snier�t�a1:&.:la 1;14:%✓..�.'.:F�•.1w:.7i.::i::::::i::':i:'<:::i::isi:i:i:.?:.>:.:i'>:.::'?:.:i'>:.: 9... P f rs riaized` vice<lri «<><«..........< ><«<<< ..... `e. Detailed Room Loads - Room 12 - WIC #2 (Peak Method) }jpry�{ :::.:..•.....a.n..:....a.a.aaa.aaa...n..:aa.:a-.m.•aaaaa.aaaaaaa.aa:::::a:aa:...a.aa::a:::.:.a::::::::::a:aa ............. v..a............. .:........... ... n.... ... ....... ...... ......... ....:..:...... n. Calculation Mode: Htg: & clg. Occurrences: 1 RoomlLength: 7.0 ft. System Number: 1 Room Width: 6.0 ft. Zone Number: 1 Area: 1 42.0 sq.ft. Supply Air: 5 CFM Ceiling Height: 9.3 ft. Supply Air Changes: 0.8 AC/hr Volume: 391.0 cu.ft. Required Vent.: 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM Runout Air: 5 CFM Percent of Supply.: 0 % Runout Duct Size: 4 in. Actual Summer Vent.: 0 CFM Runout Air Velocity: 58 ft./min. Percent of Supply: 0 % Design Loss: 0.100 in.wg./100 ft. Actual Winter Infil.: 0 CFM Actual (Loss: 0.005 in.wg./100 ft. Actual Summer Infil.: 0 CFM UP-Ceil-166-19 7 X 6 Floor-2�A-pm 7 ft..Per. 42 0.049 1.5 7 1.180. 35.4 62 248 2.5 0.0 0 0 103 0 Subtotals for Structure: 310 0 103 Infil.: W'n.: 0.0, Sum.: 0.0 0. 0 0 0. 0 0 Ductwork: 0.087 27 0.087 87 9 Room Totals: 337 87 11'2 >�3'$Altq�l <Siieri= • Detai Calcula Room Loads - Room 13 - WIC #1 (Peak Method) ::��::�L::::Li:.iLi���t.i<i��i.i�::�f Aode: Htg. & clg. Occurrences: Room Length: 8.5 ft. System Number: Room Width: 6.0 ft. Zone Number: Area: ; 51.0 sq.ft. Supply Air: Ceiling !Height: 9.3 ft. Supply Air Changes: Volume: 474.0 cu.ft. Required Vent.: Number of Registers: 1 Actual Winter Vent.: Runout Air: 14 CFM Percent of Supply.: Runout Duct Size: 4 in. Actual Summer Vent.: Runout Air Velocity: 164 ft./min. Percent of Supply: Design Loss: 0.100 in.wg./100 ft. Actual Winter Infil.: Actual Loss: 0.028 in.wg./100 ft. Actual Summer Infil.: ........:..................................................................... .......:..: tg 13A-5ocs 8.5 X 9.3 79.1 0.125 3.8 296 0.8 1613-19 8.5 X 6 51 0.049 1.5 75 2.5 A -pm 9 ft..Per. 9 1.180 35.4 319 0.0 Infil.: Win.: 9.8, Sum.: 5.6 DuctworK: Room Totals: 1 1 14 CFM 1.8 AC/hr 0 CFM 0 CFM 0 % 0 CFM 0 % 10 CFM 6 CFM 0 0 63 125 0 690 0 188 79 4.086 323 1.164 232 92 0.087 88 0.087 87 24 1,101 319 304 Room Loads - Room 14 - Mstr Bdrm (Peak Method) :::................... . .................................. .<a\i...�i..i.<i.....�..'....t::.......::::.::.::... ...... Ilode: Htg. 8, cig. v Occurrences: Room Length: 19.0 ft. System Number: r Room Width: 14.0 ft. Zone Number: Area: 1 266.0 sq.ft. Supply Air: Ceiling Height: 9.3 ft. Supply Air Changes: _ Volume: 2,474.0 cu.ft. Required Vent.: Number of Registers: 2 Actual Winter Vent.: RunoutAir: 129 CFM Percent of Supply.: Runout Duct Size: 7 in. Actual Summer Vent.: Runoui Air Velocity: 484 ft./min. Percent of Supply: Design Loss: 0.100 in.wg./100 ft. Actual Winter Infil.: Actual Loss: 0.122 in.wg./100 ft. Actual Summer Infil.: j %�{i>:!�iCCYii::i::i::i:`.:iiC1 '.:Itli!!:[•�i:::':':'f!:ii'tititi::ti{:iiiF•iiti rii'•iiiii::iiiY.:i:i;ii::}iL}jC<ii �::ii}}jiiiii::i:{i4i: iiii::: •''. .: ii.ii2i�{t::t •.1GG.F:1'• �,j• (.gyp `�' :zz:cg:;:;?;;;�;?;;'tizi W:`.':v::}%?:i:•:4:{i•?::i:{:::i%..........;:j}ii.�j.�}i ?ia• TZ�.}.�'�`, :::ii: {C:FF\i::ry;:i i::i:iii:3 :Fi E -WaIIA 3A-5ocs 19 X 9.3 S-Wall_13A-5ocs 14 X 9.3 160.7 80.4 0.125 0.125 3.8 603 3.8 301 0.8 0.9 E -GIs-IA-hb-o shgc-0.52 0%S (2) 16 1.080 32.4 518 114.9 S -GIs-10A-m shgc-0.53100%S (2) 40.8 1.670 50.1 2,044 41.6 S -GIs-1A-hb-o shgc-0.52 1 00%S 9 1.080 32.4 292 28.8 UP-Ceill-1613-1919 X 14 266 0.049 1.5 391 2.5 Floor-22A- m 33 ft..Per. 33 1.180 35.4 1,168 0.0 1 1 'I 259 CFM 6.3 AC/hr 0 CFM 0 CFM 0 % 0 CFM 0 % 38 CFM 22 CFM 0 70 0 1,838 0 1,696 0 259 0 652 0 0 Subtota,s for Structure: 5,317 0 4,644 Infil.: Win.: 38.0, Sum.: 21.7 307 4.086 1,254 1.167 902 358 Ductwork: 0.087 570 0.087 87 453 People:1200 lat/per, 230 sen/per: 1 200 230 Room Totals: 7,141 1,189 5,685 ig'i 1 Room Load --------------------- r>< i <><<< s -Zone 1- 1 Foyer/Hall 2 Din _ 3 Bdrm #2 4 Bdrm #1 5 Den 6 Bath #2 7 Utility 8 Pantry 9 Kitchen 10 Liv Rm 11 Mstr Bth 12 WIC #2 13 WIC #1 14 Mstr Bdrm System 1 total System 1 Main Trunk Size: Velocity: Loss per 100 ft.: 200 3,180 41 1-6 574 2,479 360 113 113 169 7,034 91 2-6 574 4,955 743 225 225 260 6,956 90 2-6 593 5,122 1,517 233 233 247 3,024 39 1=6 495 2,136 724 97 97 192 2,467 32 1-5 545 1,634 415 74 74 66 1,694 22 1-4 513 984 833 45 45 84 2,744 36 1-4 654 1,255 1,806 57 57 18 -259 3 1-4 39 48 87 2 2 154 785 10 1-4 214 410 1,287 19 19 456 7,635 99 2-7 531 6,242 606 284 284 126 3,773 49 1-7 477 2,800 1,243 127 127 42 337 4 1-4 58 112 87 5 5 51 1,101 14 1-4 164 304 319 14 14 266 7,141 93 2-7 484 5,685 1,189 259 259 331 48,130 626 34,166 11,216 1,554 1,554 16x17 in. 880 ft./min 0.081 in.wg 3.78 75% / 25% 34,166 11,216 45,382 Heafinq System Coolinq System n/a 0 Btuh n/a 0 Btuh