wrightsoft° Project Summary Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: For. BOTT RESIDENCE SOUTHWIND TRAIL, FORT PIERCE, FL 34951 Notes: Winter Design Conditions Outside db 42 OF Inside db 70 OF Design TD 28 OF i Heating Summary Structure 27034 Btuh Ducts 10582 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 37616 Btuh Infiltration Method Simplified Construction quality Average Fireplaces 0 Heating Cooling Area (ft� 2652 2652 Volume (ft3) 27076 27076 Air changes/hour 0.32 0.16 Equiv. AVF (cfm) 144 72 Heating Equipment Summary i Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat i 100 EFF 9.5 kW 32404 BFuh 1933 cfm 0.051 cfm/Btuh 1.00 in H2O Job: Date: Aug 20, 2018 By: COM Summer Design Conditions Outside db 90 OF Inside db 75 OF Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Sensible Cooling Equipment Load Sizing Structure 31524 Btuh Ducts 12925 Btuh Central vent (0 cfm) 0 Btuh Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 42226 Btuh Latent Cooling Equipment Load Sizing Structure 4016 Btuh Ducts 4241 Btuh Central vent (0 cfm) 0 Btuh Equipment latent load 8268 Btuh Equipment total load 50484 Btuh Req. total capacity at 0.70 SHR 5.0 ton Cooling Equipment Summary Make Rheem Trade RHEEM Cond RA1660AJlNA Coil RH1T6024STANJA AH R I ref 7943714 Efficiency 13.0 EER, 16 SEER Sensible cooling 40600 Btuh Latent cooling 17400 Btuh Total cooling 58000 Btuh Actual air flow 1933 cfm Air flow factor 0.043 cfm/Btuh Static pressure 1.00 in H2O Load sensible heat ratio 0.84 FILE COPY Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft® 2018-Aug-2013:48:32 Right -Suite® Universal 2017 17.0.08 RSU08101 page 1 EADocumnetslWrightsoft HVACIBOTr RESIDENCE.rup Calc = MJ8 Front Door faces: W -- wrightsofta RighW@ Worksheet Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772466-6796 Email: QUICKCALCS@AOL.COM Job: Date: Aug 20, 2018 By: 1 I Room name Entire House FAMILY ROOM 2 =ed wall 205.0 ft 39.0 ft 3 ROom height 10.2 ft 10.0 ft heat/cool 4 Room dimensions 1.0 x 335.0 ft 5 Room area 25520 ft2 335.0 ftz 61 c)!AED excursion o 1 1 -221 41elope loss/gain 22591 15984 3714 1877 12 a) Infiltration 4444 1190 824 221 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 ARpllance.s. thef 1.4350 3000 Subtotal (lines 6 to 13) 27034 31524 4538 5097 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 1 2 14 Subtotal 27034 31524 4540 5100 15 Duct loads 1 391/6 41% 105821 12925 39% 41%1 1777 2091 Total room load 37616 44449 6317 7191 Air required (cfm) 1933 19M 325 313 wrightsoft" Right -Suite® Universal 2017 17.0:08 RSU08101 E:1Documnets\WrightsoftWAC%BOTFRESIDENCE.rup Calc=MJB FrontDoorfaces: W 2018-Aug-20 13:48:32 Page 1 -1- wrightsoft- Right-JO Worksheet Job: Entire House Date: Aug 20, 2018 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Emall: QUICKCALCS@AOL.COM 1 Room name BREAKFAST NOOK WCHEN 2 3 Exxrsed wall Room height 20.0 ft 10.0 ft heat/cool 9.0 ft 10.0 ft heat/cool 4 5 Room dimensions Room area 7.0 x 13.0 ft 91.0 ft2 1.0 x 246.0 ft 246.0 ft2 Tye; Construction number U-value (Btuhlft= °F) Or HTM (Btuh/ft� Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-0ocs 2 glazing, clr low-e 2 glazing, clr lower •: OA43 0.650 0.650 n n n 4 0q 18.20 18.20 219 14.99 14.99 0 0 0 0 0 0 0-- 0 0 0 0 0 0. 0 0 0 0 0 0 0 0 0 0 0 11 2 glazing,' cir low-e -, _ 13A4ocs 2 glazing, clr low-e 2 glaznq, clr low-e 13A-4ocs 2 glazing, clr low-e .- 0.650 0.143 0.650 0.650 0.143 0.143 0.650 ,n a a .- e - se s s , .18.20 4.00 18.20 -18.20 4.00 4.00 18.20 ., 14.99: 2.19 33.77 33.77 2.1.9 2.19 14.99 _, 0, 70 0 _ _ _ .0 _0 130 0 - 0 70 0 -- 0 _ .0 90 0 _ _ 0 280 0 0 . ; ..... 01, 360 0 - 0 153 0 0 0 197 0 0 0 0 0 50 40 0 . _ _ 0 0 0 ._. 0 _ 50 40 0 0 0 0 0 :_ 200 160 0 0 0 0 _ _ 0 109 88 0 WE�8 �11113A-4ocs... G {G 2 glazing, clr low-e 2glazinq, drlow-e _ 13A-4ocs 2 glazing, clr low-e .2 glazm9, clr low-e _ 0.650 0.650 0.143 0.650 .. __..0.650 s s w w w. 18.20 -_ 18.20 4.00 1820 .._ .18.20 14.99 _ 14.99 219 33.77 _. 33.77 0 40 0 0 " . __ _ _.:0 0 .40 0 0 - ... _. 0 0 _ -728 0 0 ,_..,.. __ .0 0 -__600 0 0 _ . _ _ .. 0 0 _- - - 0 0 0 ._.. _. - _ 0 0 _ __.0 0 0 . _- .... 0 0 0 0 0 .. __.-_ .0 0 - 0 0 0 ._ _-.. _ 0 W i G_ C F I _. 16B-30ad _ - _ _ - _ 22A-tph_ .. - _ -_ _ 0.032 1.358 - _ _- -.. - 0.90 38.02 - - _ _1.60 0;00 91 ` 91 91 20 . - 82 --- .. Z60 - _ - _ _ 146 0 - 246 246 - . - 246 9 - 220 ._._ .. 342 394 0 - 6 c)!AED excursion -74 -110 "velope loss/gain 2211 1021 923 481 12 a) Infiltration 423 113 190 51 b)� Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 1600 2000 Subtotal (lines 6 to 13) 2633 2734 1113 2532 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 11 18 14 Subtotal 2633 2734 1124 2550 15 Duct loads 39% 41% 1031 1121 39% 41% 440 1045 Total room load 3664 3856 1564 3595 Air required (cfm) 1 188 168 180 156 Of wrightsoft' Right -Suite® Universal 2017 17.0.08 RSU08101 2016-Aug 20 13:Paagege 2 2 EADocumnets\Wrightsoft HVAC\BOTT RESIDENCE.rup Calc = MJ8 Front Door faces: W wrightsoft' Right-.10 Worksheet Job: Date: Aug 20,2018 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FUK I PIERCE, I-1-34M vnone: fix-4bt>-btuv t-au itz-4a"itju =Fnall: UU1UMtALU0%yMUL.�UiV1 I - I Room name HALL PANTRY 2 Exposed wall 0 ft 0 ft 3 height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 4.0 x 8.0 ft 9.0 x 8.0 ft 5 R6om area 32-0 ft2 72.0 ftz Tyl Construction U-value Or HTM Area (ftj Load Area (ftj Load number (BtUtff---F) (13tuh/fl:5 or perimeter (ft) (13tuh) or perimeter (ft) (13tuh) Heat I Cool Gross N/P/S Heat Cool Gross N/PIS Heat Cool 6 W�� 1 n ?- 19 --b d 2 glazing, clr la". 0.650 n 18.20 -14.99 0 0 0 0 0 0 0 2 glazing,'cIr low-e 0.650 n 18.20 -.14.99 0 0 0 0 0 0 0 0 G 2 glazing, clr lower 0.650 n _14.99 0 0. _0 0 11 w I 1 AAo6i 0.143 e 4.00 Z19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 e 18.20 33.77 0 0 0 0 0 0 0 0 2 qlazino,-clr-law-e- 0.650 e-- -18.20 .33.77 --...-0 0 0 0 0 ---- --- - -- - 0 -----,0- --- ------ 0 VV 13AAocs- - ----- .0--, 0 '70 -9 _0 V� 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 clr low 2 glazing, -e 0.650 S 18.20 14.99 0 0 0 0 0 0 0 0 2,.az n cirlow-e " 0.650 s 18.20 14.99, O 0 _0 0 0 0 0 0 w "13AAocs- -16vie 7' 0.143 -�W- k 00, - Z19 '0 0 -0 0 0 0 �12 2 glazing, ,clr A 0.650 w 18.20 6; 33.77 0 0 0 0 '0 0 2 gjazing_clrjow-e.,�--' -.-_-.9.660 w 18.20 -Ax mo _0 . 0 -0 1613-30ad 0.032 0.90 1.60 32 29--------6-1 - - - ,72 72 65 115 ,-C F -- ---- -- 22A-.tph- 7 --- ------ - , - -- - 1.358 --- 38.02 0.00, -7- 7- 32 _32 - 0 -6 - 77 7 0 72 V ----- 0 -- - 0 7 7 6 c):AED excursion -2 -5 1 Envelope loss/gain 29 49 65 110 12 a), Infiltration 1 0 0 0 0 b), Room ventilation 0 0 0 -0 13 i Internal gains: Occupants @ 230 01 0 0 01 Appliancestother 0 0 Subtotal (lines 6 to 13) 29 49 65 1101 Less eAemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -29 -49 10 16 14 Subtotal 0 0 74 127 15 Duct loads 39% 41% 0 0 390/6 41% 29 52 Total room load 0 0 103 179 Air required (cfm) 1 01 01 1 1 51 8] wrightscDft" Right -Suite® Universal 2017 17.0.08 RSU0B101 EMocumnetslWrightsoft HVACXBOTTRESIDENCE.rup Calc = MJ8 Front Doorfaces: W 2018-Aug-20 13:48:32 Page 3 32 �A 'r-j - W rigtttt50ft Right -Suite® Universal 2017 17.0.08 RSU08101 2018 Aug 20 1 P ge 4 E:\Docurrnets%Wrightsoft HVAC\BOTT RESIDENCE.rup Calc = MJ8 Front Door faces: W s- 6 C) QED e)cursion 48 -1 Envelope loss/gain 86 106 14 25 12 a) Infiltration � 0 0 0 0 b) Room ventilation 0 0 0 0 13 Int I emal gains: Occupants @ 230 0 0 0 0 I Appliances/other ioQQ 0 Subtotal (lines 6 to 13) 86 1106 14 25 Less a demal load - 0 0 0 0 Less transfer 0 0 0 0 Redistribution 10 18 -14 -25 14 Subtotal 96 1123 0 0 15 Duct loads 39% 41% 38 461 390/0 41% 0 0 Total room load 134 1584 0 0 Ail required (cfm) 71 69 01 0 +I&- wrightsioft, 2018-Aug-20 13:48:32 Right -Suite® Universal 2017 17.0.0B RSU08101 Page 5 E:kDocuffmets%WrightsoftWACIBOTrRESIDENCE.rup Calc=MJ8 FrontDoorfaces: W ---------- -- _7 "T Z- 7 7W -- - -- - -------------- ----- 7 T' ------ - - ------ - ----- --------- —7- --- --------- ------ ----- ---- yF :7- - 77 --I -31--�1— z�,717,1;7"R- �,n 6 C)AED excursion -70 F� I velope loss/gain 1 13221 6901 1 1231 648 12 a) Infiltration 254 68 233 621 b) � Room ventilation 0 0 1 0 0 13 Int6mal gains: Occupants @ 230 0 0 0 0 1 Appliances/other 900 900 Subtotal (lines 6 to 13) 1575 1658 1464 1610 LeLs e)demal load 0 0 0 0 Leis transfer 0 0 0 0 Redistribution 13 22 11 18 14 Subtotal 1589 1680 1474 1628 15 Ddct loads 39% 41% 622 689 39% 41% 577 668 Total room load 22101 23691 2051 2296 Air, required (dm) 114 103 105, 100 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. +1=11- wrightsoft, 2018-Aug-20 13:48:32 Right -Suite® Universal 2017 17.0.08 RSU08101 Page 6 E:\Documnets\WrightsoftWAC\BOT7RESIDENCE.rup Calc = MJB Front Door faces: W i -1- wrightsoft' Right-JO Worksheet Job: Entire House Aug 20, 2018 By: y i QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 2 CLST 2 2 wall 8.0 ft 0 ft 3 Reed Reed 10.0 ft heat/cool 10.0 ft heaNcool 4 Room dimensions 12.0 x 8.0 ft 2.0 x 7.0 ft 5 Room area 96.0 ft' 14.0 ftz Ty Construction U-value Or HTM Area (ftj Load Area (ftj Load number (Btuh/ft1 °F) (Btuh/ftj or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) j Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 " ,13A flocs. , ' _ 0,143 n ,. - 4.00 2.19 $0 '77 ' M8 -_ - 188 . ` 0 l) - :0 0. 2 glazing, clr low-e 0.650 n 18.20 ` 14.99 3 0 55 45 0 0 0 0 glazing, 2 lazing, 18.20 14.99 . 0 0 0 0 0 0 6 0 2glazi clr, Iow,e, . _ _ . 0 650 ,.n 18.20. .-,14.99' ..,.. -.O .. .. '. 0 _ c;.. 0 v :... ..0 _.._.0 .. 0 . 0. 11 W( 13A-4ocs 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 2alazlnq..clrlow-e 0.650---e-- 18.20. 33.77 0 - _0 -0 - --0 ____0 W A :19A-4ocs . _ :, ": 0.143 _ se. "... 4.00. - . :.2.19 .. _ , .. ;_0 . .. - _0 . _.. 0 ---- -.., ., ._ 0 ".::., ..... -0 0 .. 0 >, ... ,. _.0 ,_ .. ----- g 0 Wi l 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 I G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low a 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazlnq, cir low-e 0.650 s 18.20 14 99 0 0 - 0 _ 0 0, 0_ 0 - 0 W `t- -IG 13A-4ocs' 2 glazmg, clt low-e 0.143 0.650 w w 4.00 ` 18.20 219 33 77 D 0 0 0 0 0 0 01 0 0 0 0 0 % 0 0 r .2 glazing Gr low-e _ ... _ 0.650 w , 18.20 33,77 ; _ . ,._ 0 _ 0 _ = 0 , . 0 ..,_ .., 0 0 0 0. C 1613-30ad 0.032 - 0.90 1.60 96 96 86 164 14 14 22 --._. 22A-tph _ _ - 38.02' . .,' °0.00 _ :.. 96 8 . , 304 _ .:. c, , .0 ...:: _.14 . _ _ -- 0 _ _ ,13 0 0 { - -- - _ _ - - ------ - _.. 6 c) AED e>rcursion -25 1 Envelope loss/gain 753 342 13 21 12 a) Infiltration 169 45 0 0 b) Room ventilation 0 0 0 0 13 Intemal gains: Occupants @ 230 0 0 0 0 Appliances/other 200 0 Subtotal (lines 6 to 13) 922 587 13 21 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 -13 -21 14 Subtotal 922 587 0 0 15 DUctloads 39% 41% 361 241 39% 41% 0 0 Total load room Air required (cfm) 1283 66 827 36 0 0 0 01 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. t A & ' wrilghtsoft- Right -Suite® Universal 2017 17.0.08 RSUD8101 2018-Aug-2013:48:32 Page 7 E:\Documnets\Wrightsoft HVAC\BOTT RESIDENCE.rup Calc = M,18 Front Door faces: W - - wrightsoft' Right-M Worksheet Job: Entire House Date: Aug 20, 2018 B QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 2' 3 Room name E)posed wall Room height DINING ROOM 13.0 ft 10.0 ft heat1cool FOYER 7.0 ft 12.0 ft heat/cool 4 5 Room dimensions Room area 13.0 x 14.0 ft 182.0 ft2 7.0 x 14.0 ft 98.0 ft2 Ty; Construction number U-value (Btuh/ft2--°F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 �.. 13p�tocs ' -'.. 2 glazing, clr low- 2 glazing, clr low-e 0.143 0.650 0.650 .... n' n n 4.00 18.20 18.26 2.19 14.99 14.99 0, 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e_ 13AAocs _0:650 0.143 n a 18.20 4.00 , ,14-99 219 0 0 - 0- 0 .. _ -0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, ctr low-e -2 plazmp,_clr low-e - 13AAocs- .'_ 0.650 ---0.650 0.143 a - e_ .se 18.20 _ ..18.20 4.00 33.77 __, 33.77 . ° .:2.19 0 -- _ 0 0 .0 0 - 0 0 0 -- - 0- - .. 0 0 -- -- --0-- - _.- _.. 0 . -- -- 0 0 0 -- _ -- 0. . _ .._- . 0 0 - 0 0 . W Wi I �- G - 13AAocs 2 glazing, clr low-e .. 0.143 0.650 s s 4.00 18.20 2.19 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 l��;-G 2 glazing, clr low-e 2 plazm9, clr low e - 13AAocs 2 glazing, clr low-e 2.glazmg, cicJow e., 0.650 0.650 0.143 0.650 s _ s w w . w . 18.20 18.20- 4.00 18.20 _ 14.99 _ 14.99 2.19 33.77 _33.77 0 _ _ 0-- 130 20 _ . _ - 0 0 0 110 0 ' ..-_...._ 0 0 0 440 364 -- -_.... :0 0 ---- -0 241 675 _-..... 0 0 -- _ _-- 0 84 0 48 0 _ _ . 36 D 0 0 - 0 . 144 0 _ ._ . 874 0 0 79 0 _ . 1621 W C -- 16B-30ad - - -0.650 _._ -.18.20 0.90- 1.60 . _. 182 182 - 163 _ _ 291 _- - - - 98 - 98 - - 88 _ - 157 F. _._. _ , _-_ 22A7tph ' • . _ _- _0.032 1.358 _- - _ ,- . . 38.02 -_ - 0.00 182 ,13 _ , - ' 494 - 0 98 _ . _ 7 _ 266 0 6 c)AED excursion 199 576 Envelope loss/gain 1462 1406 1372 2433 12 a)I Infiltration 275 74 178 48 b); Room ventilation 0 0 0 0 13 Internal gains: Occupants (d 230 0 0 0 0 Applianceslother 500 0 Subtotal pines 6 to 13) 1737 1980 1549 2481 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1737 1980 1549 2481 15 Duct loads 390/6 41% 680 812 399/6 41% 606 1017 al room load 7Ak� 2416 2792 2156 3498 required (cfm) 124 121 111 152 Calculations awroved bvACCA to meet all reauirements of Manual J 8th Ed. C wrightsoft" 2018-Aug-2013:4B:32 Right -Suite® Universal 2017 17.0.08 RSU08101 Page 8 EADocumnetstWrightsoft HVAC%BOTT RESIDENCE.rup Calc = MJ8 Front Door faces: W -�- w0ghtsoft- Right-J® Worksheet Job: Entire House Date: Aug 20, 2018 B QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC MASTER BATH 2 B�osed wall 7.0 ft 17.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 7.0 x 14.0 ft 1.0 x 166.0 ft 5 Room area 98.0 ft2 166.0 ft' Ty Construction U-value Or HTM Area (ftj road Area (ft� Load number (Btuhlft? °F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 ( 1N.1G- - lazing, low-e 0 650 _.._ 18.20 14 99 j._ _.._ - --0 0 0' 2 .clr 2 cir low-e 0.650 n n 18.20 14.99 0 0 0 0 0 0, 0 L -G 2 glazing, clr low e.,-- __ 0.650 _ n , _18.20 14,99 , :0-..__0 0 . _. _ 01 ___. 0 .- _ 0 _- 0 0 11 W 13A4ocs 0.143 a 4.00 Z 19 0 0 0 0 0 0 0 0 2 glazing, cir low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 2 glazmq._clr low-e . -- 0.650 --- e_.. 18.20. 3377 ,.._. 0 0 _ _ 0 - 0 ---- 0 _- .. .-0 -- --- 0 -0. _ 13AAocs:..-... .. ._ .. _._0.143. se. _ _ ._,4,00,... 219'., ._. 0 ": .-.. _0 _,0.._ .., .._0_ 0.. _ ,. 0 - Of _,..0 13AaOcs 0.650 s 4.20 2.19 0 0 0 0 86 74 190 2 glazing, clr low-e 0.60 s 18.20 14.99 0 0 0 0 6 6 109 109 90 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazinq, clr low-e _ 0 650 _ s . _ 18.20 _ 14.99 - --0-- 0 -------- 0 0 _ 0 _ _ 0 0 - _ _0 W 13A-4ocs � . 0143 w 4.00 2.19 70 70 280 153 90 70 280 153 . 2 glazing, clr low-e 0.650 w 18.20 33.77 0 0 0 0 20 0 364 675. _ . 2,glazing,clrlow-e.;;_.. 0.650_-w, _ 18.20.._ 33770._-_..,..__0 _0_.. __._.0 _..__----_0 _ . U.-.�_ _..0 . _. ..:0. C 16B30ad_ 0.032 _ 0.90 9-8 98 _._ 88 157 .-__ 166 166 _ _-. 149 266 - F 22A tph _ 1.358 - - 38 02 - _1.601 - 0.00 _ .. , - _ _ 98 7 266 0 166 _ . 17 646 0 - - - - -------- - 6 c)�ED excursion -15 200 Fsivelope loss/gain 634 295 1845 1546 12 a)� Infiltration 148 40 359 96 b), Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal pines 6 to 13) 782 335 2204 1642 Less eAemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 782 335 2204 1642 15 Duct loads 39% 41% 306 137 39% 41% 863 673 ITTotal room load 1088 472 3067 2316 Air required (cfm) 56 21 158 101 Calculations approved WACCA to meet all requirements of Manual J 8th Ed. wrigFr,tsoft" 2018 Aug 20 1 ACCP. Right -Suite® Universal 2017 17.0.08 RSU08101 Page 9 1E:\Docurrmets\WdghtsoftHVAC\BOTiRESIDENCE.rup Calc=MJ8 Front Door faces: W w rightsotr Right-JO Worksheet Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 7724666799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M TOILET 2' E ed wall 11.0 ft 3 Room height 10.0 ft heat/cool 4 Rc Qm dimensions 5.0 x 6.0 ft 5 Room area 30.0 ft2 Job: Date: Aug 20, 2018 By: MASTER BEDROOM 38.0 ft 11.0 ft heaticool 18.0 x 20.0 ft 360.0 ft2 61 c)AED excursion 1 -15 1 1 -226 Envelope loss/gain 886 274 4137 2843 12 a) Infiltration 233 62 884 237 b) Room ventilation 0 0 0 0 13 Intelmal gains: Occupants @ 230 0 0 0 0 ARRllarmtother 0 =0 Subtotal pins 6 to 13) 1118 336 5020 5380 Less erdemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1118 336 5020 5380 15 DUctloads 390/6 41% 438 138 39% 41%1 1965 2206 Total room load 1556 474 6985 7586 Air required (cfm) 80 21 359 330 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft' 2018-Aug-2013:48:32 I Right -Suite® Universal 2017 17.0.08 RSUOB101 I&K Page 10 E:%Documnets%Wdghtsoft WACIBOTT RESIDENCE.rup Calc = MJB Front Door faces: W -�+ wrightsoft® Duct System Summary Job:Date: Aug 20, 2018 Entire House By: QUICK CALCS, INC. LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772466-6796 Email: QUICKCALCS@AOL.COM For. BOTT RESIDENCE SOUTHWIND TRAIL, FORT PIERCE, FL 34951 Heating Cooling External static pressure 1.00 in H2O 1.00 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 1.00 in H2O 1.00 in H2O Supply / return available pressure 0.500 / 0.500 in H2O 0.500 / 0.500 in H2O Lowest friction rate 1.000 in/100ft 1.000 in/100ft Actual air flow 1933 cfm 1933 cfm Total effective length (TEL) 212 ft SupplyDetail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (In) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 1283 66 36 1.000 5.0 Ox 0 VIFx 35.3 135.0 st3 BEDROOM 2 h 2051 105 100 1.000 7.0 Ox0 VIFx 26.9 115.0 SO BEDROOM 3 h 2210 114 103 1.000 7.0 Ox 0 VIFx 37.8 135.0 st3 BREAKFASTNOOK h 3664 188 168 1.000 8.0 Ox0 VIFx 51.0 155.0 st4 DINING ROOM h 2416 124 121 1.000 7.0 Ox 0 VIFx 27.0 115.0 st1 FAMILY ROOM h 3158 162 156 1.000 8.0 Ox 0 VIFx 47.0 155.0 st4 FAMILY ROOM -A h 3158 162 156 1.000 8.0 Ox 0 VIFx 56.5 155.0 st4 FOYER I C 3498 111 152 1.000 8.0 Ox 0 VIFx 52.2 115.0 st2 KITCHEN c 3595 80 156 1.000 8.0 Ox 0 VIFx 36.2 135.0 st3 LAUDRY c 1584 7 69 1.000 6.0 Ox 0 VIFx 22.9 116.0 st1 LIVING ROOM C 2511 77 109 1.000 7.0 Ox 0 VIFx 63.3 135.0 st5 LIVING ROOM -A C 2511 77 109 1.000 7.0 Ox0 VIFx 64.1 135.0 St5 MTOILE T h 1556 80 21 1.000 5.0 Ox0 VIFx 54.8 115.0 st2 M WIC ' h 1088 56 21 1.000 5.0 Ox 0 VIFx 46.4 115.0 st2 MASTER BATH h 3067 158 101 1.000 7.0 Ox 0 VIFx 49.8 115.0 st2 MASTER BEDROOM h 3493 179 165 1.000 8.0 Ox 0 VIFx 61.9 135.0 st5 MASTER BEDROOM -A h 3493 179 165 1.000 8.0 Ox 0 VIFx 62.9 135.0 st5 PANTRY` C 179 5 8 1.000 4.0 Ox 0 VIFx 31.7 135.0 st3 POWDER c 392 2 17 1.000 4.0 Ox0 VIFx 21.9 115.0 st1 wri htsoft 2018-Aug-2013:48:33 ti 9 a Right -Suite® Universal 2017 17.0.08 RSU08101 Page 1 ACr-'I\ E:%DocumnetslWrightsoft HVAC\BOTT RESIDENCE.rup Calc = MJ8 Front Door faces: W • Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st5 Peak AVF 513 548 1.000 698 12.0 0 x 0 VinlFlx st2 st2 Peak AVF 917 842 1.000 858 14.0 0 x 0 VinlFlx st4 Peak AVF 513 480 1.000 777 11.0 0 x 0 VinlFlx st3 st3 Peak AVF 778 784 1.000 850 13.0 0 x 0 VinlFlx st1 st1 Peak AVF 1016 1091 1.000 889 15.0 0 x 0 VinlFlx Name Grill Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 j OxO 1933 1933 0 0 0 0 Ox 0 VIFx 1 wri htsoft° 2018-Aug-2013:48:33 i+- 9 Right -Suite@ Universal 2017 17.0.08 RSU08101 Page 2 AM E:\Documnets%Wrightsoft WAC%BOTT RESIDENCE.rup Calc = MJ8 Front Door faces: W This document was created with Win2PDF available at http://www.win2pdf.com. The unregistered version of Win2PDF is for evaluation or non-commercial use only. This page will not be added after purchasing Win2PDF.