Loading...
HomeMy WebLinkAboutMANUFACTURED HOME INSTALLATION - TRIPLE WIDEMANUFACTURED HOME Il`ISTALLATIOI`I FOR I'H,'�IP I H O"IVES 'i Mul (Supplement to Manufactured Home Installation Manual) BRINGING Ann HOME. BRINGING Amika Iff SITE PREPARATION The site is to be prepared and the units interconnected and supported as per the special instructions for Double -Wide set-up and interconnection (outlined in the Manufactured Home Installation Manual.) The A -unit is to be lag bolted (3/8" diameter x 4" long) to the B-unit where the 12" wide sheathing is not removable at the sidewall gable. WARNING ONLY EXPERIENCED PERSONS KNOWLEDGEABLE OF MANUFACTURED HOME SET-UP PROCEDURES SHOULD SET UP THIS HOME. NOTE: THIS MANUAL IS INTENDED TO INSTRUCT AND TO ASSIST ALREADY QUALIFIED PERSONNEL IN PROPER INSTALLATION OF SKYLINE MANUFACTURED HOMES. IT IS NOT INTENDED TO ENABLE SOMEONE UNFAMILIAR WITH MANUFACTURED HOME INSTALLATION TO PERFORM THE INSTALLATION. SET-UP SHOULD BE DONE ONLY BY QUALIFIED PEOPLE. WHOEVER DOES THE SET-UP SHOULD GUARANTEE THEIR WORK IN WRITING FOR A REASONABLE TIME AND SHOULD, IF NECESSARY, AGREE TO RELEVEL THE HOME WITHIN 90 DAYS AFTER THE INITIAL SET-UP. The technical content of this Installation Manual has been reviewed by PFS Corporation and found to be in accordance with the Federal Manufactured Home Construction and Safety Standards. APPROVED PFS Corporation Madison WI 01/31/05 HUD Manufactured Home Construction & Safety Standard MANUFACTURED HOME INSTALLATION OF B-UNIT TO C-UNIT A parallel tag is indicated by the peak of the roof being located along the center of the B-unit. A dormer tag is indicated by the roof dormer being located at the tag location. Choose the instructions that match the tag to be installed. I. PARALLEL TAG INSTALLATION 2. 3. 4. y5. r The site is to be prepared and the units interconnected and supported per the special instructions for Double -Wide set- up and interconnection outlined in the Manufactured Home Installation Manual (see Fig. 1 below). After the A -unit and the B-unit have been blocked and leveled, the C-unit is to be connected to the B-unit in a like manner. When required for roof loads in excess of 20psf, the A, B and C-units should be perimeter blocked per the Manufactured Home Perim- eter Blockirig Supplement. Fold back the underlayment material in the area of the detachable roof sheathing. (Used for bolting beam halves together.) Remove the 16-inch wide pieces of sheathing, which were temporarily secured and are located adjacent to each ridge beam half. Bolt the ridge beams together as outlined in the Double - Wide set-up procedure in the Manufactured Home Installa- tion Manual,. For models with heat ducts in the roof cavity, make the interconnection of two units by running the provided flexible duct through the access hole in the ridge beam. Reinstall the detached sheathing using 15 gauge by 7/16" by 1-1/2" staples of 8d twist nails 4 inches on center at butt Pier at centerline within 1' of front and rear wall. This pier required only if there) is a column IRcated at front or rear vyall. (See Table 3) I -Beams -------------- Piers required at all interior column locations, per - Table 3. (See detail) Max. pier spacing as selected from Table 2. joints and at each truss between joints. Special fastening may be required at trusses located over shearwalls. These trusses will be marked with a paint spot on the truss top chord. Fasten roof sheathing to these trusses with fasten- ers 2" o.c. (3" o.c. if truss is doubled - to both trusses.) 6. Fasten roof underlayment back in place with 16 gauge by 1" by 1" staples or roofing nails 4'-0" (maximum) around the perimeter. Apply a 6" wide strip of asphalt cement between underlayment and roof decking at unit endwall, at Wind Zones II and III only. 7. Install 36" wide roofing underlayment centered above ridge beam. Install such that uphill side is below factory installed underlayment and downhill side is above factory installed underlayment. Fasten same as step 6 above. (See Fig. 3) 8. Fasten drip cap to sheathing above the underlayment at the roof edge. (See Fig.3) 9. Per the Manufactured Home Installation Manual, complete installation of shingles. 10. After completing the interconnections of the units, install the closure of siding at the front and rear walls of the C-unit. Install the provided inside corners (if required) as indicated in Figure 2. 11. See Fig. 4 for alternate sheathing attachment at unit centerlines. A -unit B-unit \ C-unit Roof Peak DIMENSIONS VARY. IF PRE -CONSTRUCTION OF FOOTINGS IS DESIRED, CONTACT THE SKYLINE DIVISIONI WHICH MANUFACTURED THE UNIT FOR APPLICABLE DIMENSIONS. FIG. 1 Varies The home shall be set-up and the utilities connected per the requirements of the Double -Wide set-up instructions specified in the Manufactured Home Installation Manual. Each I -Beam shall be supported per Table 2 and each column supported per Table 3. Each outside I-beam (on the A & C units) shall be tied down per the tie down requirements specified in the installation manual. All mating line connections, closure details, and utility connections shall be made per the applicable centerline details specified in the installation manual or other supplements. m CENTERLINE SUPPORT PIER LOCATION INDICATOR (METAL STRAP) OR CENTERLINE FLOOR JOIST MARKED WITH PAINT BENEATH HOME. Main Unit Hardboard Siding I Hardboard Siding /I Caulk Hardboard trim (factory supplied - field installed). Fasten with 8d galvanized box nails 8" o.c. staggered (6" o.c. staggered at Wind Zones II and III). Nails to have 3/16" min. dia. Heads. Hardboard Siding FIA. 2 Main Unit Lap Siding Inside Comer (factory supplied - field installed). Fasten with 16Ga.x7/16"x1-1/2" staples or 4d nails 12" o.c. at Wind Zone I, 6" o.c. at Wind Zones II and III. 4—j Lap Siding Vinyl Lap Siding SITE INSTALLED SHINGLES ROOFING UNDERLAYMENT FOLDED BACK FOR BEAM BOLTING _ 36" WIDE ROOFING UNDERLAYMENT 10 F 1 G. 3 4 feet See Detail 'A' A -HALF UNIT 4'x8' Plywood or O.S.B. roof decking, 3/8" or 7/16" thick. Ridge Beam B-HALF UNIT 4 feet Roof Trusses 4 feet Field InstalledRoof Decking at unit transition \� Roof Decking C-HALF UNIT Shim as required with wood shims, if trusses do not line up. INSTRUCTIONS: 1) Bolt ridge halves together as described in Skyline's manufactured home installation manual. 2) If trusses at unit transition do not line up vertically, then shim as required with wood shims. 3) Fasten 4' wide roof sheathing to trusses w/15Ga. x 7/16" x 1.1/2" staples 4" o.c. at joints at intermediate trusses. Special fastening may be required at trusses located over shearwalls. These trusses will be marked with a paint spot on the truss top chord. Fasten roof sheathing to these trusses with fasteners 2" o.c. (W o.c. if truss is doubled - to both trusses). Fastener length at shimmed area should be increased so there is 1 " min. penetration into truss top chord. 4) Fasten roof underlayment to decking w/16Ga. x 1 " x1 " staples 48" o.c. long top edge of lower course of underlayment. Apply a 6" strip of asphalt cement between underlayment and roof decking at unit endwalls at Wind Zones 11 and M. 5) Install remaining courses of shingles as described in Skyline's manufactured home installation manual. FIG. 4 II. DORMER TAGS The site is to be prepared and the A and B-units intercon- nected and supported per the special instructions for Double - Wide set-up and interconnection outlined in the Manufac- tured Home Installation Manual (see Fig. 5 below). After the A -unit and the B-unit have been blocked and leveled, the C- unit is to be connected to the B-unit. The set-up of the C-unit will vary depending on the type of Dormer tag included with your home. Determine the type of Dormer tag from the descriptive list below. Dormer Tag 1: Flush roof, flush floor, approved for Wind Zones II and 111, and has a triangular plywood beam between B and C-unit. Dormer Tag 2: Main unit roof overhangs tag roof, step down floor and approved for Wind Zones I, II, and III. Dormer Tag 3: Flush roof, step down floor, approved for Wind Zone I only, and main unit will have hinged roof. Dormer Tag 4: Flush roof, flush floor, approved for Wind Zone I only, and does not have triangular plywood beam. Pier at centerline within 1' of front and rear wall. This pier required only if there is a column located at front or rear wall. (See Table 3) I -Beams Piers required at all interior colum locations, per Table 3. (See detail) Max. Pier spacing as selected from Table 2. Dormer Tag 5: Main unit roof overhangs tag roof, flush floor and approved r for Wind Zone I only. - Dormer Tag 6: Flush roof, flush floor, approved for Wind Zone I only, and has a triangular plywood beam. Dormer Tag 7: Flush roof, flush floor, approved for Wind Zone I only, no triangular plywood beam and 320" long. For the Dormer tag to have a flush roof, the dormer on the main unit will line up with the tag roof. For the Dormer tag to have a flush floor, the floor of the main unit will line up with tag floor. For the Dormer tag to have a step down floor, the floor of the tag will line up 9 inches lower than the main unit floor. Once you have determined the correct tag for your home, go to the specific set-up instructions. See list below: Page(s) Figure(s) DormerTag 1 6 7 Dormer Tag 2 7 7 Dormer Tag 3 8 8 Dormer Tag 4 9 9 Dormer Tag 5 10 10 Dormer Tag 6 11 11 Dormer Tag 7 12 12 A -unit B-unit FIG. 5 * DIMENSIONS VARY. IF PRE -CONSTRUCTION OF FOOTINGS IS DESIRED, CONTACT SKYLINE DIVISION WHICH MANUFACTURED THE UNIT FOR APPLICABLE DIMENSIONS. See see specific set-up instructions in this manual (Figures 6-12) for all tag pier locations, sizes, loads, etc. CENTERLINE SUPPORT PIER LOCATION INDICATOR (METAL STRAP) OR CENTERLINE FLOOR JOIST MARKED WITH PAINT BENEATH HOME. DORMER • 1. Fold back as close as units toget must be tak 2. Bring the BI ing the'T'4 3. Align ceilin jacking the 4. Bolt the twc Manufactu beams is pi sheathing ( 5. Line up C-t moving C-t Fasten the 12inches t around per 6. Level the fl unit. FastE 16" o.c. or AG 1 nderlayment and valley flashing and align C-unit possible to the B-unit. Slide the tag and main ier with rolling and jacking equipment. Care en to avoid overstressing structural members. -unit and C-unit sidewall beams together. Jack - ieams of the C-unit may be necessary. a material joints and level ceiling edges by C-unit inside "I" -beam until ceiling joint is flush. r triangular beams together as described in the -ed Home Installation Manual. Access to the -ovided by two removable panels in the roof )f each unit. snit endwall studs with B-unit sidewall studs by Init floor either forward or backward as necessary. walls together using 16d nails or #8x3" screws at m center. Install sill sealer (roll of insulation) imeter of main unit before installing fasteners. oor by jacking on the inside "I" -beam of the C- :n the header joists together with #8x3" screws 3/8" x 2-1/2" lag screws 2 to 3 ft. o.c. f 160" max. ate piers under each end of a�ning between main unit and Pier load is 2623 lbs. �I �I C-unit PIER REQUIREMENTS Wall strap - Factory installed. , TABLE 1 Pier Height Minimum Maximum Wind I Zone II 18.6" 49 7" Wind Zone III I 17.1" 55.9" Hurricane Tie -down strap. Install at all wall strap locations. Strap may be located above or below (- Beam. ------------ Ground Level / Ground anchor FIG. 6 7. Level the C-unit and install the required piers as shown in Figure 6 below. Pier locations at the sidewall beam support columns are marked with paint under the floor. Follow pier and footing requirements as described in the Manufactured Home Installation Manual. 8. Install ground anchors and hurricane straps as shown in Figure 6 below, and per the requirements of the Manufactured Home Installation Manual. 9. Replace the access panels in the roof sheathing using 16 gauge x 7/16" x 1-1/2" staples or 8d twist nails at 4 inches on center. Install corner drip cap. 10.See roof covering close -off instructions for dormer tags on page 13. 11.Apply closure courses of siding to the front and rear walls of the C-unit. Install the provided inside corners as per Figure 2. 12.Seal the joint under the floor between the tag and the main unit with sill sealer. Locate piers at all four �,r��tj.Y • T. �; FQq,•�••� corners of tag unit. Pier �•• ; • �p1fSTEq `'•.vK'J load is 1485 lbs. • Q• %. ' 19W12 6TA7E OF J •••SS/ANAL;; • ��nu• A E .Lp0 Co Locate pier under wall, where ridge beam meets exterior wall. Pier load is 2540 lbs. Locate piers under unit I -beams. Piers are required at each end of beams and at center. Pier load is 3550 lbs. Unit I-beam * Pier with footing Pier Height - ;•;:;;; See Tablet. ' Strap Angle: Wind Zone II - 30 degrees min. 57 degrees max. Wind Zone III - 28 degrees min. 60 degrees max. TIE -DOWN REQUIREMENTS DORMER TAG 2 04 4. 5. TABLE 1 Pier eight Minimum Maximum Wind Zone I 12" 56" Wind Zone II 18.6" 49.7" Wind Zone III 17.1" 55.9" Align C-unit as close as possible to the B-unit. Slide the tag and main units together with rolling and jacking equipment. Care must be taken to avoid overstressing structural members. Align ceiling material joints and level ceiling edges by jacking the C-unit "I" -beam until ceiling joint is flush. Fasten C-unit to B-unit at roof line. Use #8x2" wood screws from tag unit extended plywood (at end truss location) to main unit (see Figure 7 below). Line up C-unit endwall studs with B-unit sidewall studs by moving C-unit floor either forward or backward as neces- sary. Fasten the walls together using 16d nails or #8x3" screws at 12 inches on center. Install sill sealer (roll of insulation) around perimeter of main unit before installing fasteners. Level the floor by jacking on the inside "I" -beam of the C- unit. The floor of the tag unit should be 9 inches lower than the floor of the main unit. Fasten the headerjoist of the main unit to the wall studs of the tag unit with #8 x 311, screws (16" o.c.). 6. Level the C-unit and install the required piers as shown in Figure 7 below. Pier locations at the Tag beam support columns are marked with paint under the floor. Follow pier and footing requirements as described in the Manu- factured Home Installation Manual. 7. Install ground anchors and hurricane straps as shown in Figure 7 below, and per the requirements of the Manufac- tured Home Installation Manual. 8. Apply closure courses of siding to the.front and rear walls of the C-unit. Install the provided inside corners as per Figure 2. 9. Seal the joint under the floor between the tag and the main unit with sill sealer. Locate piers at all four comers of tag unit. Pier I 160" max. load is 1720 lbs. at 20 Locate piers under tag ridge 4 PSF, 2340 at 30 PSF, #8x2" Screws beam column supports. Pier 2950 at 40 PSF, 4300 at 12" o.c. —� load is 3000 lbs. at 20 PSF, 60 PSF 3 5550 at 80 PSF 4070 at 30 PSF, 5140 at 40 roof live load. Dormer PSF, 7500 at 60 PSF and 9650 �/ Tag truss Rafter at 80 PSF roof live ioa d. Tag Main i , Unitt Unit % E ROOF CLOSE -OFF sa ,��ttftttuurr►� Locate piers Under Unit I -beams. Locate pier under wall each side of opening under tag ��`l�•........... .STE a{j i1,�'' Piers are required at each end of ridge beam. Pier load is 1500 lbs. at 20 PSF, 2035 at �Q� RFC• �>` beams and at center. Pier load 30 PSF and 2570 at 40 PSF, roof live load. Not pE 19600312 I is 4200 lbs. applicable to 60 or 80 PSF roof live loads. Install single pier at center of wall at 60 or 80 PSF roof live load. = 1 8 • • eZ I i Pier load is 7600 at 60 PSF, and 9650 at 80 PSF roof .- e 'S STATE OR : 4 ` live load. 1`�\ PIER REQUIREMENTS '�, ��••' ��!�DIANP•= •��i�.` Wall strap Factory Installed. Wind Zone II Unit I-beam and III o Hurricane Tie -down strap. Install 2 at front and rear of each I-beam % Pier with (8 total) for Wind Zone I. Install at %" footing all wall strap locations for Wind % Zone II and III. Strap may be ; ' Pier Hetght - located above or below I-bea _ • . see table 1. Ground Level Strap Angle: Wind Zone I - 20 degrees min. 60 degrees max. Ground anchor Wind Zone II - 30 degrees min. 57 degrees max. Wind Zone III - 28 degrees min. 60 degrees max. FIG. 7 TIE -DOWN REQUIREMENTS - DORMER TAG 3 1. Align C-unlit as close as possible to the B-unit. Slide the - tag and main units together with rolling and jacking equipment) Care must be taken to avoid overstressing structural members. 2. Align ceiling material joints and level ceiling edges by jacking the C-unit inside "I" -beam until ceiling joint is flush. 3. Fasten C-unit to B-unit at roof line. Use #8x3" wood screws (toe -screwed) from tag unit (at end truss location) to main unit (see Figure 8 below). 4. Line up C-unit endwall studs with B-unit sidewall studs by moving C- 1 nit floor either forward or backward as neces- sary. Fasten the walls together using 16d nails or #8x3" screws at 12 inches on center. Install sill sealer (roll of insulation) around perimeter of main unit before installing fasteners. 5. Level the floor by jacking on the inside" I "-beam of the C- unit. The floor of the tag unit should be 9 inches lower than the floor of the main unit. Fasten the header joist of Locate pies under tag ridge beam column supports. Pier load is 2890 Ibs at 20 PSF, 3920 Ibs atj 30 PSF and 4960 Ibs at 40 PSF roof live load. I }, Loca a piers under unit I -beams. Piers are required at each end of beans and at center. Pier load is 405C lbs. TABLE 1 I Pier Height Minimum Maximum Wind Zone I 12" 56" 160" max. C-unit the main unit to the wall studs of the tag unit with #8 'x 3" screws (16" o.c.). 6. Level the C-unit and install the required piers as shown in Figure 8 below. Pier locations at the Tag beam support columns are marked with paint under the floor. Follow pier and footing requirements as described in the Manu- factured Home Installation Manual. 7. Install ground anchors and hurricane straps as shown in Figure 8 below, and per the requirements of the Manufac- tured Home Installation Manual. 8. See roof covering close -off instructions for dormer tags on page 13. 9. Apply closure courses of siding to the front and rear walls of the C-unit. Install the provided inside corners as per Figure 2. 10. Seal the joint under the floor between the tag and the main unit with sill sealer. Locate piers at all four #8x3" screws corners of tag unit. Pier 12" o.c. �►� load is 1670 Ibs at 20 r- PSF, 2260 Ibs at 30 Tag truss / PSF and 2860 Ibs at 40 Ir PSF roof live load. TAG UNIT X M E io co Locate pier under wall each side of opening under tag ridge beam. Pier load is 1450 Ibs. at 20 PSF, 1960 Ibs at 30 PSF and 2475 Ibs at 40 PSF roof live load. PIER REQUIREMENTS Hurricane Tie -down strap. Install 2 at front and rear of each I-beam (8 total) for Wind Zone I. ------- ---- Ground Level Ground anchor MAIN Dormer Rafter UNIT ROOF CLOSE -OFF Unit I-beam Pier with footing ' ---I-_ Pier Height See Table 1. And Zone 1 - 20 degrees min. 60 degrees max. TIE -DOWN REQUIREMENTS FIG. 8 DORMER TAG 4 1. Align C-unit as close as possible to the B-unit. Slide the tag and main units togetherwith rolling and jacking equipment. Care must be taken to avoid overstressing structural members. 2. Align ceiling material joints and level ceiling edges by jacking the C-unit inside "I" -beam until ceiling joint is flush. 3. Fasten C-unit to B-unit at roof line. Use #80" wood screws (toe -screwed) from tag unit (at end truss location) to main unit (see Figure 9 below). 4. Line up C-unit endwall studs with B-unit sidewall studs by moving C-unit floor either forward or backward as neces- sary. Fasten the walls together using 16d nails or #8x3" screws at 12 inches on center. Install sill sealer (roll of insulation) around perimeter of main unit before installing fasteners. 5. Level the floor by jacking on the inside "I" -beam of the C- unit. Fasten the header joists together with #8x3" screws 16" o.c. or 3/8" x 2-1/2" lag screws 2 to 3 ft.,o.c. 6. Level the C-unit and install the required piers as shown in Figure 9 below. Follow pier and footing requirements as described in the Manufactured Home Installation Manual. 7. Install ground anchors and hurricane straps as shown in Figure 9 below, and per the requirements of the Manufac- tured Home Installation Manual. 8. See roof covering close -off instructions for dormer tags on page 13. 9. Apply closure courses of siding to the front and rear walls of the C-unit. Install the provided inside corners as per Figure 2. 10.Seal the joint under the floor between the tag and the main unit with sill sealer. #8x3" screws 12" o.c. Tag truss TAGUNIT Locate piers at each end of 1KRafte sidewall opening into tag unit per Locate piers under front Manufactured Home Installation and rear walls of tag Manual requirments for sidewall 164' max. unit. Pier load is 3800 openings. lbs. at 20 PSF roof live load and 4500 at 30 PSF roof live load. ROOF CLOSE -OFF E 0 N C-unit Locate piers under unit I -beams, spaced at 68" o.c. max. Pier load PIER REQUIREMENTS Unit I-beam is 2600 lbs. Hurricane Tie -down strap.lnstall 1 at front and rear of each I-beam (4 Pier with total) for Wind Zone I.� footing Pier Height See Table 1. -� ------ --- --- ---- - --- >< - Ground Level Ground anchor Strap Angle: Wind Zone I - 26 degrees min. 62 degrees max. TIE -DOWN REQUIREMENTS FIG. 9 TABLE 1 Pier Height Minimum Maximum Wind Zone I 16" 60" . DORME TAG 5 1. Align C-u it as close as possible to the B-unit. Slide tag and main units together with rolling and jacking equip- ment. Care must be taken to avoid overstressing struc- tural members. 2. Align ceiling material joints and level ceiling edges by jacking the C-unit inside "I" -beam until ceiling joint is flush. 3. Fasten C unit to B-unit at roof line. Use #8x2" wood screws fr m tag unit extended plywood (at end truss location) o main unit (see Figure 10 below). 4. Line up C-unit endwall studs with B-unit sidewall studs by moving C l unit floor either forward or backward as neces- sary. Fasten the walls together using 16d nails or #8x3" screws at� 12 inches on center. Install sill sealer (roll of insulation) around perimeter of main unit before installing 5. Level the floor byjacking on the inside "I" -beam of the C- unit. Fasten the header joists together with #8x3" screws 16" o.c. or 3/8" x 2-1/2" lag screws 2 to 3 ft. o.c. 6. Level the C-unit and install the required piers as shown in Figure 10 below. Pier locations at the Tag beam support columns are marked with paint under the floor. Follow pier and footing requirements as described in the Manu- factured Home Installation Manual. T Install ground anchors and hurricane straps as shown in Figure 10 below, and per the requirements of the Manu- factured Home Installation Manual. 8. Apply closure courses of siding to the front and rear walls of the C-unit. Install the provided inside corners as per Figure 2. 9. Seal the joint under the floor between the tag and the main unit with sill sealer. Locate piers at all four 156" max. corners of tag unit. Pier load is 22001bs. at 20 #8x2" screws Locate piers at each end of PSF roof live load and 12" o.c. sidewall openings into tag unit 2800 at 30 PSF roof ° per Manufactured Home Inst Ilation Manual requirements live ad. Tag truss -- —� Dormer fors dewall openings. Rafter _- Tag Main ` Unit Unit E N ROOF CLOSE -OFF C-unit Locate piers under unit I -beams. Piers are required at each end of beams and at center. Pier load is 3600 lbs. TABLE 1 Pier Height Minimum Maximum Wind Zone 12" 45" PIER REQUIREMENTS Hurricane Tie -down strap. Install at front, rear and center of each (- beam (6 total) for Wind Zone I. - Ground Level Ground anchor Unit I-beam FIG. 10 TIE -DOWN REQUIREMENTS DORMER TAG 6 TABLE 1 Pier Height Minimum Maximum Wind Zone I 12" 44.8" 1. Fold back underlayment and valley flashing and align C- unit as close as possible to the B-unit. Slide the tag and main units togetherwith rolling and jacking equipment. Care must be taken to avoid overstressing structural members. 2. Bring the B-unit and C-unit sidewall beams together. Jacking the "I" -beams of the C-unit may be necessary. 3. Align ceiling material joints and level ceiling edges by jacking the C-unit inside "I" -beam until ceiling joint is flush. 4. Bolt the two triangular beams together as described in the Manufactured Home Installation Manual. Access to the beams is provided by two removable panels in the roof sheathing of each unit. 5. Line up C-unit endwall studs with B-units sidewall studs by moving C-unit floor either forward or backward as necessary. Fasten the walls together using 16d nails or #8x3" screws at 12 inches on center. Install sill sealer (roll of insulation) around perimeter of main unit before installing fasteners. 6. Level the floor by jacking on the inside "I" -beam of the C- unit. Fasten the header joists together with #8x3" ` screws 16" o.c., or 3/8" x 2-1/2" lag screws 2 to 3 ft. o.c. _ 7. Level the C-unit and install the required piers as shown in Figure 11 below. Pier locations at the sidewall beam support columns are marked with paint underthe floor. Follow pier and footing requirements as described in the Manufactured Home Installation Manual. 8. Install ground anchors and hurricane straps as shown in Figure 11 below, and per the requirements of the Manu- factured Home Installation Manual. 9. Replace the access panels in the roof sheathing using 16 gauge x 7/16" x 1-1/2" staples or 8d twist nails at 4 inches on center. Install corner drip cap. 10.See roof covering close -off instructions for dormer tags on page 13. 11.Apply closure courses of siding to the front and rear walls of the C-unit. Install the provided inside corners as per Figure 2. 12.Seal thejoint under the floor between the tag and the main unit with sill sealer. Locate piers at all four 160" max. corners of tag unit. Pier load is 2800 lbs. (3600 Locate piers under each end of lbs at 60# roof, 4650 lbs opening between main unit and �at 80# roof). tag. Pier load is 6000 lbs. (8600 lbs at 60# & 80# roof). E NLocate pier under wall, where = ridge beam meets exterior wall. Pier load is 4500 lbs. (7600 a 60# roof, 9850 at 80# roof). C-unit Locate piers under unit 1-beams 9'-0" o.c. max. Piers are required at each end of beams.. Pier load is 2900 lbs. PIER REQUIREMENTS unit I-beam Hurricane Tie -down strap. Ilk I I' Pier with Install 1 at front and rear of each footing I-beam and 3 more evenly spaced (T-0" o.c. max.) along : ; :Pier Heigh - each I-beam (10 total). See Table 1. ------- ------------ - - Ground Level Strap Angle: Ground anchor Wind Zone 1 - 19 degrees min. 56 degrees max. TIE -DOWN REQUIREMENTS FIG. 11 DORMER TAG 7 I 1. Align C-gnit as close as possible to the B-unit. Slide the tag and main units together with rolling and jacking equipment. Care must betaken to avoid overstressing structural members. 2. Align ceiling material joints and level ceiling edges by jacking the C-unit inside "I" -beam until ceiling joint is flush. 3. Fasten C-unit to B-unit at roof line. Use #8x3" wood screws (toe -screwed) from tag unit (at end truss location) to main unit (see Figure 12 below). 4. Line up C-unit endwall studs with B-unit sidewall studs by moving C-unit floor either forward of backward as neces- sary. Fasten the walls together using 16d nails or #8x3" screws at 12 inches on center. Install sill sealer (roll of insulation) around perimeter of main unit before installing 5. Level the floor by jacking on the inside "I" -beam of the C- unit. Fasten the header joists together with #8x3" screws 16" o.c., �or 3/8"x2-1/2" lag screws 2 to 3 ft. o.c. L,Cate piers uner tag ddge beam o" supports. Pier bad Is 3000lbs at 20 PSF, 4070 Ibs fat 30 PSF and 5140 Ibs at 40 PSF roof Nve bad. , i 1 � 1 1 . Locale piers under unit I -beams. Piers are requked at each end of beams and at center. Pier load to 4290 lbs. I f TABLE 1 Pier Height Minimum Madmum Wind Zone 1 12" 56" 6. Level the C-unit and install the required piers as shown in Figure 12 below. Pier locations at the Tag beam support columns are marked with paint under the floor. Follow pier and footing requirements as described in the Manu- factured Home Installation Manual. 7. Install. ground anchors and hurricane straps as shown in Figure 12 below, and per the requirements of the Manu- factured Home Installation Manual. 8. See roof covering close -off instructions for dormer tags on page 12. 9. Apply closure courses of siding to the front and rear walls of the C-unit. Install the provided inside corners as per Figure 2. 10.Seal the joint under the floor between the tag and the main unit with sill sealer. Locate piers at al four 16(` max. comets of tag unit. Pier bad Is 1720 ibs at 20 PSF, 2340 On at 30 / PSF and 2950 Ibe at 40 i PSF roof We load. Iz = It ;J 1 '•Y•a 1—i—I 1 i i L ocde pier under atafl each side of openkV under fag ride beam. Pier bad is 1500 bs. at 20 PSF, 2035 An d 30 PSF and 2570 ft at 40 PSF roof Nw bad. PIER REQUIREMENTS Hurricane Tie•down strap. Install 2 at Front and rear of each I-beam (8 total) for Wind zone I. Ground Ground anchor FIG. 12 08)W screws 12" o.c. �1►, C— Tag truss TAG UNIT MAIN Dormer Rafter Unit I-beam r4 Pier with ~' tooting Pier Heiphl - See Table 1. TTT trap ArdW: "Zom 1 - 20 deproes min- 60 ftre-max TIE -DOWN REQUIREMENTS DORMER TAG ROOF COVERING INSTRUCTIONS 1. 2. 4. 5. 6. 7. If your home has a Dormer Tag 1, 4, 6 or 7 then follow steps 2 through 10. If your home has a Dormer Tag 3, then follow steps 11 through 17. If your home has a Dormer Tag 2 or 5, then no further work is required. Fold underlayment back in place on the C-unit. Apply asphalt cement between 1st and 2nd layers to a point 24 inches (minimum) inside the sidewall (see Fig. 13). Fold underlayment back in place on the 13-unit and overlay with the provided 36" wide roofing underlayment at the marriage line of the units; tack in place (see Fig. 13). Nail bottom layer of valley flashing back in place with 16 gauge x 3/4" x 1" staples or 12 gauge x 1-1/4" large head galvanized roofing nails at 12" on center (see Fig.14). If the valley on the home is an open valley, follow step 6. If the valley is a closed cut type, then go to step 8. Apply a 3" band of asphalt cement between top and bottom layer of roll roofing. Fasten top layer of valley flashing same as step 4 above (see Fig. 14). Apply shingles from eave up to ridge. Shingles and the starter course are to be cut to form the 8" valley (see Fig. 15). Apply a 5" band of asphalt cement between the shingle and the valley flashing. The shingles are to be fastened as described in the Manufactured Home Installa- tion Manual. Go to step 9. 8. First, install remaining shingles on the main unit side of the valley, extending them onto the dormer side. Shingles should extend onto dormer side 12" min. (see Fig.16). Use normal shingle fastening (see Manufac- tured Home Installation Manual) methods, except that no fastener should be within 6 inches of the valley centerline and two fasteners should be placed at the end of each shingle crossing the valley. Next, apply shingles on the dormer side'of the valley starting along the eaves and crossing the valley onto the previously applied shingles (see Fig. 17). Trim shingles no less than 2" back from the valley centerline. Trim one inch on a 45 degree angle from the upper corner of each end shingle. Finally, embed each end shingle in a 3" wide strip of asphalt cement. 9. When installing remaining shingles, take care to assure that butt joints of shingles on adjacent courses are not within 4" of each other. 10.Cut shingles for ridge cap and install as per the Manufac- tured Home Installation Manual. 36" WIDE UNDERLAYMENT CENTERED AT MATING LINE C-UNIT I B-UNIT UNDERLAYMENT � UNDERLAYMENT ASPHALT CEMI CORNER DRIP FIG. 13 SECURE BOTH LAYERS ALONG EDGE AT ILAO.C. UNDERL:AYIvIENT:.';�:• •.'. :• Y BAND OF ASPHALT '.`. CEMENT ALONG EDGE BOTTOM LAYER OF MINERAL SURFACED ROLL ROOFING - FIG.14 MINERAL SURFACED VALLEY FLASHING fTOP LAYER OF MINERAL SURFACED ROLL ROOFING E OF VALLEY I 5"BAND OF ASPHALT CEMENT BETWEEN SHINGLES AND VALLEY FLASHING t OF VALLEY FIELD APPLIED SHINGLES r CUT SHINGLE EDGES TO FORM 8" VALLEY I FIG. 15 Valley centerline i Roll Roofing X Field installed shingles FIG. 16 I I I I Valley centerline Clipped Comer Field installed shingles C2" Asphalt Cement FIG. 17 11. Fold underlayment back in place on the C-unit. Apply asphalt cement between 1 st and 2nd layers to a point 24 inches (minimum) inside the sidewall. 12. Fold underlayment back in place on the B-unit and overlay with the provided 36" wide roofing underlayment at the marriage line of the units. Trim to fit along valley centerline. The underlayment is to be carried up onto the main unit fascia board 3" to 4" where the main unit sidewall overhang meets the tag roof (see Figs. 18 & 20). 13. Nail 2 layers of valley flashing roll roofing in place with 16 gauge x 3/4" x 1" staples. Apply a 3" band of asphalt cement between layers of roll roofing (see Fig. 19). 14. Trim the valley flashing so that it extends 1 /4" below the FIG. 18 edge of the main unit, and 2" below the point where the 2 units meet (see Fig. 20). 15. Apply shingles from eave up to ridge. Install step flashing against main unit fascia as shown in Figures 18 and 21. Shingles and the starter course are to be cut to form the 8" valley (see Fig. 20). Apply a 5" band of asphalt cement between the shingle and the valley flashing. The shingles are to be fastened as described in the Manufac- tured Home Installation Manual. 16. When installing remaining shingles, take care to assure that butt joints of shingles on adjacent courses are not within 4" of each other. 17. Cut shingles for ridge cap and install as per the Manufac- tured Home Installation Manual. Underlayment carried up onto Fascia Board 3" to 4". Step flashing positioned over shingle so that ned course of shingles covers It completely. Fascia metal serves as cap flashing over step flashing. I/ Centerline of Valley. I �Shii 5" band of asphalt cement between I roll roofing and shingles. 3' band of asphalt cement I along each edge. 1 I Underlayment I Roof DecWng FIG. 19 36" wide layer of mineral surface roll roofing. Staple along each edge w tth 16Ga.x3/47t1' staples 12' o.c. 18" wide layer of mineral surface roll roofing. Staple along each 'edge with 16Ga.x3/4' x1' staples 12' o.c. .I•....i ....... c� i tide' wart wmg m. wx*kymenL DomwV&Uy iM Vaftydoh& Trkn the upper and lower sections of ffashkV so that tltey extend 114- below the edge of the main unit. Mahn Unk See Step FWWft petty Tp Unft ROOF COVERING DETAIL � • The lower section of the flan *V. In contact with the tap unit 90M W*d at least 2- below the point where the two roofs meet. Trim the top Foyer of flashing tot will He on the fag unit to —HUP tfx nearest course of shingles. I FIG. 26 Nat metal fMshbV to roof wn-roofing rase. 2" top laP, 5" FIG. 21 Corporate Office - P.O. Box 743 - Elkhart. Indiana 46515 10" minimum flexible O crossover duct. Register location (typical) vary. 10" minimu Im O flexible cross O over duct. 12" minimum flexible crossover duct. Aluminum duct or fiberglass --ductboard-duct.-- --- r� Aluminum duct or fiberglass ductboard duct. ...... \Aluminum duct or fiberglass ductboard duct. ........ Insulated metal wye (R-4 minimum). Typical Heat Duct Crossover Connection Notes: 1) See HVAC details for fiberglass ductboard ducts systems regarding duct size, register sizes; locations; etc. 2) See "Wine Corporation Manufactured Home Installation Manual" for additional information regarding connection and support of heat duct crossovers, Notes a 1) s .NE Corporate Office - P.O. Box 743 - Elkhart, Indiana 46515-0743 Rev. 01/11/05