HomeMy WebLinkAboutLETTER WITH RESPONSES TO REVIEW COMMENTS - 10-27-15i
Joseph P. McCarty, Architect, Inc.
%0' East Osceola Street
Stuart, Florida, 34994
772-287-6735 fax:772-287-4618
DPR Registration Number 9639
October 27, 2015 SCANNED
�St Lucie C®unty
Planning and Development Services
Building & Code Regulation Services
2300 Virginia Avenue
Fort Pierce, FL 34982
Re: 0 Dyer Road Permit #1510-0005
As follows is response to plan review comments:
1)Energy performance sheets of windows are attached. SH5500 has a OF of 0.3300 and
SHGC of 0.2200, the AW5540 has a OF of 0.3200 and SHGC of 0.1800.
2)I Truss drawings and engineering are attached in duplicate.
3)1 Weathering area is indicated as "negligible" per 301.2(3)
4)1 Termite infestation area is indicated as "very heavy" per 301.2(6)
5)1 Wall and ceiling finishes shall have a flame -spread classification of not greater than 200.
1 Wall and ceiling finishes shall have a smoke -developed index of not greater than 450.
All wall and ceiling finishes, are gypsum board.
6) Flame spread for Icynene insulation is 25 or less, smoke developed index of 450 or less.
The fiberglass batt insulation has a flame spread of 25 and smoke developed index of 50.
7) The window installation detail on sheet 1 has been revised to indicate fin -frame windows
with integral flashing.
8) Bath #2 door has been revised to 2'-8"
9) The elevations show piers and open space between the piers. This open space has been
labeled on the plans.
10) The area under the house is open. (see 7)
11) ICC report on foam insulation is attached.
12) Roof sheathing and nailing is specified on Sheet 5
1�) Two copies of Hardie Board product approval are attached.
14) Wall sheathing and nailing are indicated on sheet 1.
15) Sheet 3 has beerf revised to indicated 3000 PSI compressive strength on all concrete.
i
16) �. ' Sheet 1 shows floor sheathing as %" T&G plywood. IOd nails 6" on center has been
" noted on detail.
1
0,,
* oy 9639 �A<