EVALUATION REPORT
Polyglass USA, Inc.. Evaluation Report P12060.02.09-R24
1111 West Newport Center Drive SCANNED F1.5259-1128
Deerfield Beach, FL 33442 BY Date of Issuance: 02/24/2009
(954) 233-11230 St Lucie County Revision 24: 004/2018
SCOPE: I -
This'Evaluation Report is issued under Rule 61620-3 and the applicable rules and ' regulations governing the use of .
construction materials in the State of Florida..The documentation submitted has been reviewed by Robert Nieminen, P.'E.
for use of'Ithe product under the Florida Building Code and. Florida Building Code, Residential Volume.. The products
described herein have been evaluated for compliance -with the 6th Edition (2017) Florida Building Code sections noted
herein.
DESCRIPTION: Polyglass Roof. Underlayments
LABELING: Llabeling shall:be in .accordance With the requirements the Accredited Quality Assurance Agency noted herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the namedproduct(s) changes, the• referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of.this
Evaluation !Repo.rt by the named client constitutes agreement to notify Robert Nieminen; P.E..of any changes, to the
product(s),i the Quality Assurance or the production facility location(s). NEMO l etc. requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADvERTisEMENT: The Evaluation Report number preceded by the words "NEMOIetc. Evaluated" may be displayed -in
advertising literature. If any portion of the Evaluation -Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be available for inspection at the job site at the.request of the.Building Official. .
This Evaluation-Reportconsists of pages 1 through 14.
Prepared
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE2983
The facsimile seal appearing was authorized by Robert Nieminen,
P.E. on 01/24/2018. This does not serve as an electronically
signed document
CERTIFICATION OF INDEPENDENCE:
1. NEM01 etc. does not have, nor does it intend to acquire or will it acquire, a financial. interest in'any company manufacturing or
distributing products it evaluates.
2. NEMO J etc. is not owned, operated or control by any company manufacturing or distributing products it evaluates.
3. . Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports. are being issued..
4. Robert Nieminen,.P.E. does not have, nor will acquire, a financial interest in any other entity involved In the approval process of the
product. .
5. This is a .building code evaluation. Neither. MEMO I etc. nor Robert Nieminen, P.E. are, in. any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
O.-NEMOletc.
ROOFING COMPONENT EVALUATION:
I
1. SCOPE:
Product Category:
Roofing.
Sub -Category:
Underlayment
Compliance Statement:- Roof Underlayments, as produced byPolyglas;-US , l c., Piave demonstrated
compliance with the
following sections of the oh
Edition (2027).Florida Building. Coe
rough testing in accordance with the
following Standards.
Compliance is subject to the
Installation, Requirements.and Limitations
/ Conditions of Use.set forth herein.
2. STANDARDS:
Section
property
Standard
Year
150413.1
Wind Uplift
FM 4474
2011
150413.1
Wind Uplift
UL 1897
2012
150712.3
/ 1507.1.1
Physical Properties
ASTM D226 .
2009
150712.4
/ 1507.1.1, 1507.2.9.2
Physical Properties
ASTM' D1970
2025 .
1507!3.3
Physical Properties
FRSA/TRI April 2012
2012
15071,11.2
Physical Properties
ASTM D6164
2011
1507111.2
Physical Properties
ASTM D6222
2011
TAS 110
Accelerated Weathering
ASTM D4798
2011
3. REFERENCES:
Enti
Examination
Reference
Date
FM Approvals (TST 1867)
Wind Uplift
3004091
01/12/2000
PRI (TST 5878)
Physical Properties
PRIC1111
04/08/2002
PRI (TST 5878)
Physical Properties
PUSA-005=02-01
01/31/2002
PRI (TST 5878)
Physical Properties
PUSA-013-02-01
.12/23/2002
PRI (TST 5878)
Physical Properties
PUSA-013-02-02
12/23/2002.
PRI (TST 5878)
Physical Properties
PUSA-013-02-03
12/23/2002
PRI (TST5878)
Physical Properties _
PUSA-018-02-01.
07/14/2003
PRI (TST 5878)
Physical Properties
PUSA-028-02-01
07/23/2005
PRI (T57 5878)
Physical Properties,
PUSA-033-02-01
01/12/2006
PRI (TST 5878)
Physical Properties
PUSA-035-02-01
09/29/2006
PRI (TST 5878)
Physical Properties
PUSA-055-02-02
12/10/2007
PRI (75T 5878)
Physical Properties
PUSA-061-02-02
01/28/2008
PRI.(TST 5878)
.Physical Properties
PUSA-076-02-01
02/22/2008
PRI (TST 5878)
Physical Properties
PUSA=083-02-01
04/14/2008
PRI (TST 5878)
Physical Properties
PUSA-088-02-01 .
07/29/2009
MTI (TST 2508)
Physical Properties
JX20H7A
04/01/2008
MTI (TST2508)
Physical Properties
RX14E8A
01/29/2009
ERD (TST 6049)
Physical Properties
11752.09.99-1
02/08/2000
ERD (TST 6049)
Wind Uplift
11757.08.01-1
08/13/200.1
ERD (TST 6049)
Wind Uplift
11776.06.02
01/16/2003
ERD (TST 6049)
Physical Properties
02200.07.03
07/14/2003
ERD i(TST 6049)
Wind Uplift
P1740.01.07 .
01/04/2007
ERD (TST 6049)
Physical Properties
P5110.04.07-1
04/11/2007
ERD !(TST 6049)
Wind Uplift
P9260.03.08
03/21/2008
ERD;(TST6049)
Physical Properties
P13450.08.09
08/13/2009
ERDI(TST6049)
Wind Uplift
P30540.11.09-R1
11/30/2009
ERD
(TST 6049)
Physical Properties .
P11030.11.09-1
12/30/2009
ERDI(TST.6049)
Wind Uplift
P11030:11.09-2
11/30/2009
ERDI(TST6049).
Physical Properties
P11030.11.09-3
11/30/2009
ERDI(TST6049)
Physical Properties
P33360.06.10
06/25/2010
ERD
(TST 6049)
Physical Properties
P33370.03.11
03/02/2011
ERD
(TST 6049)
Physical Properties
033370.04.11
04/26/2011
ERD'I(TST
6049)
Physical Properties
P37300.10.11_
10/19/2011
NEMO ETC, LLC. Evaluation Report P12060.02.09-1124
Cer0rt—!ofAuth0&.t1on #32455 C" EDITION.(2017.) FBC NON-HVHZ EVALUATION F1.5259-1128
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 2 of 14
ERD
ERD
ERD
ERD
ERD
ERD
ERD
ERD
ERD
ERD
ERD
ERD,
ERD
ERD
ERD•
ERD
ERD
ERD
ERD
ERD
ERD
ERD
ERD
ERD
ERD
ERD
ERD
ERD
ERD
UL,
6049)
6049)
6049)
iT 6049)
iT 6049)
iT 6049)
iT 6049)
iT 6049)
iT 6049)
iT 6049)
iT 6049)
iT 6049) .
iT 6049)
iT 6049)
iT 6049) .
iT.6049)
iT 6049)
iT 6049)
iT 6049)
iT 60491
iT 6049)
iT-6049)
iT 6049)
iT 6049) .
iT 6049)
5T 6049)
iT 6049) . .
iT 6049)
(EVL 2396)
-Dade (CER 1592)
iss USA
ass USA
iss USA.
:. (QUA9625)
4. PRODUCT DESCRIPTION:
Examination
Physical Properties
Physical Properties
Physical Properties
Wind Uplift
Physical Properties
Wind Uplift.
Wind Uplift
Wind Uplift
Wind Uplift
Wind Uplift
Physical Properties
Physical Properties,
Physical Properties.
Physical Properties
Physical Properties
Physical Properties.
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties -
Physical Properties .
Wind Uplift
Physical Properties
Wind Uplift
Physical Properties
Physical Properties
Physical Properties
IBC Compliance
HVHZ Compliance
Manufacturing Affidavit
P/L Affidavit
Materials Affidavit
Quality Control
Reference
P40390.08.12-1
P40390.08.12-2
C41420.09.12-3
P39680.03.13
P45370.04.13 .
P1738.02.07-R2
11757.04.01-1-R1
P41630.08.13
P11751.05.03-111
P11781.11.03-R1
P45270.05.14
6020.07.14-1.
6020.09.14-2
6020.09.14-3
6020.09.14-4
6020.09.14 5
6020,09.14-6
P46520.10.14
P43290.10.14
PLYG-SC7550.03.15
P40390.04.15
P44360.10.14-R1
PLYG-SC8080.05.15-1
PLYG-SC8905.05.16-1
PLYG-SC8080.07.16
PLYG-SC12025.10.16
PLYG-SC13640.12.16
PLYG-SC11900.03.17
PLYG-SC12115.08.17
ESR-1697
NOA 14-0717.08
Products Current
Mule -Hide Cross Ltg
Polystick SA Compound.
Service Confirmation
a Mechaplcally Fastenetl'Untlerlayments
4.1A Elastobase is a fiberglass reinforced,•SBS modified bitumen base sheet.
4.1.2 Elastobase P is a polyester -reinforced, SBS modified bitumen base sheet..
4.1.3 Polyglass 62 Base is a fiberglass -reinforced, asphaltic base sheet.
i
4.1.4 Polyglass APP. Base is a fiberglass -reinforced,. APP. modified bitumen base sheet.
i
4:2 . :Self=Adhering Underlayments X,
ONEMO etc.
Date
08/06/2012
08/07/2012
09/11/2012
03/04/2013
04/26/2013
04/29/2013.
04/30/2013
08/06/2013
12/26/2013
11/26/2013
05/12/2014
09/08/2014
09/08/2024
09/08/2014
09/08/2024
09/08/2014
09/08/2014
10/03/2014
10/17/2014
03/24/2025
04/03/2015
05/18/2015
05/20/2015
05/17/2016
07/16/2016
10/12/2016
12/27/2016
03/10/2017
08/08/2017
11/01/2014
01/22/2015
02/19/2009
03/01/2008
08/18/2011
Exp.10/05/2018
4.2.2 . Polystick IR-Xeis a nominal 60-m. , y it thick rubberized asphalt waterproofing membrane; glass fiber reinforced, with an
aggregate surface; meets ASTM D1970.
4.2.3 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a
polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012.
NEMO ETC, LLC. Evaluation Report. P12060.02.09-R24
Certificate ofAutharization #32455 &P EDITION (2017) FBc NON-HVHZ EVALUATION FL5259-R28
P.olyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 3 of 24
O.NEMOletc.
4.2.4 Polystick TU P is a nominal. 130-mil thick rubberized asphalt waterproofing membrane,. glass=fiber/polyester
reinforced, with a granular surface; meets "FRSA/TRI April 2012.
4.2.5 Polyst)ck TU Max is a, nominal 60=mil thick rubberized asphalt waterproofing membrane with a.190.g/M2 polyester
fabric surface; meets ASTM D3970 and FRSA/TRI April 2012:
I
4.2.6 Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet, and Mule -Hide SA-APP Cap Sheet.(FR) are polyester .
reinforced, APP modified .bitumen cap sheets; meet FRSA/TRI April 2012. .
4.2.7 Polystick Dual Pro'" is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a "polyester fabric surface; meets ASTM D1970:
4.2.8 Polystick Tile Pro'" is a "nominal 60-mil thick "dual -layer rubberized asphalt waterproofing membrane, fiberglass,
reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI'April 2012. .
4.2.9 Polystick MU-X".is. a nominal " 54-mil thick, dual -layer rubberized asphalt waterproofing membrane,. fiberglass
reinforced,,with'a polypropylene film surface; meets"AC188 and physical, requirements of ASTM D1970 (See Section
4:3" "• Mechamcall Fastenedand/ori"ded"Undedayments:
4.3.1 Elastoflex G TU is a polyester reinforced, modified bitumen tile underlayment composed of a sand -surfaced SBS
modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU is for use as an
alternate to "Mineral Surface. Roll. Roofing" (ASTM D6380, Class.M) in the "Single Ply System" -from FRSA/TRI April
2012 (04-12) beneath" mechanically fastened the roof systems or Hot Asphalt applied "Cap Sheet"'in the Two Ply
System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered file roof systems. "
4.3.2 Elastoflex S6 G and Elastoflex S6 G FR are polyester reinforced, SBS modified bitumen cap sheets; "meet ASTM D6164. .
i
Elastofiex S6 G and Elastoflex S6 G FK are for use as an alternate to "Mineral Surface Roli Roofing" (ASTM" D6380,
-Class M) in the "Single Ply System" from FRSA/TRI.Apri12012 (04-12) beneath mechanically fastened the roof systems.
Elastoflex S6 G is for use as an, alternate to Hot Asphalt applied "Cap Sheet" in. the "Two. Ply System" -from FRSA/TRI
April 2012 (04-12) beneath mechanically fastened or adhered -tile roof'systems.."Elastoflex S6 G FR -is for use as an
alternate''to Hot Asphalt applied- "Cap Sheet" in the "Two Ply System from. FRSA/TRI.April .2012. (04-12) beneath
mechanically fastened tile roof systems.
4.3.3 Polyflex G. and .Polyflex G. FR are polyester reinforced, APP modified, bitumen cap sheets; meet ASTM D6222.
Polyflex G is for use as an alternate to Heat Applied "Cap Sheet" in the: 'Two'Ply System" from FRSA/TRI April 2012.
(0412) beneath mechanically fastened or adhered tile roof systems. Polyfle'x G"FR is for use as an alternate to Heat
Applied,"Cap Sheet" in. the `Two Ply System" from FRSA/TRI April 2012 (04-12) beneath. mechanically. fastened the
roof systems.,
5. LIMITATIONS:
5.1 This Is a building code• evaluation. Neither NEMOJ etc. nor Robert Nieminen,. P.E. are, in any way, the Designer of "
Record for any project on which this.Evaivation Report, or previous versions thereof, is/was used for permitting or
design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report Is not for use in the HVHZ.
5.3 Fire Classification Is not partof this Evaluation Report, refer to current Approved. Roofing Materials Diirectory_for.fire
ratings of.thisproduct.
5.4 i Polyglass Roof.Underlayments may be used with.any prepared roof cover.where the product Is specifically referenced
within FBC approval .documents. If not listed, a request may be .made to the Authority Having. Jurisdiction for
approval based on this evaluation combined with supporting data for the prepared roof covering.
i
NEMO ETC, LLC. " Evaluation Report P12060.02.09-R24
ceruflrnte ojAuthot&at/on N32455 O EDI710N (2017) FBC NON-HVHZ EVALUATION FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 4 of 24
ONEMOjetc.
5.5 i Allowable Roof Covers:
16OF:COVER OPTIONS
UndMayment
Asphalt Shingles
Nail -On The
Foam -On Tile
Metal
Wood Shakes
& Shingles
Slate
Elastobase
Y�
Base sheetYn2- I es
( p y system)
Yes
(Base Sheet In 2-ply system)
Yes
Yes
Yes
Elastobase P
Yes
Yes
(Base Sheet In 2-ply system)
Yes
(Base Sheet in 2-ply system)
Yes
Yes
yes
Polyglass G2 Base
No
' Yes
(Base Sheet in 2-ply system)
Yes
(Base Sheet In 2-ply system)
No
No
No
Polyglass APP Base
No
Yes
(Base Sheet in 2-ply system)
Yes
(Base Sheet In 2-ply system) -
No
No
No
IgStic S or MTS PLUS
Ye
Yes
Yes
No noYe
' Yes
Yes
Po ystick IR-Xe
No
No
No
Yes
Yes
Polystick TU P
No
Yes
Yes (See 5.5.1)
No
No
No
Polystick TU Plus
Yes
Yes
Yes (See 5.5.1)
Yes
Yes
Yes
PolystickTUMax
No
Yes
Yes (See 5.5.1)
Yes
No
No
Polykck Dual Pro
Yes
No
No
Yes
Yes .
Yes
Polystick Tile Pro
Yes
Yes
Yes (See 5.5.1)
Yes
Yes
Yes
Polystick MU-X
Yes
No
No
Yes
Yes
Yes
Elastoflex S6 G
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Elastoflex S6 G FR
Yes
Yes
No
No
Yes
Yes
Elastoflex G TU
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
PolyfjexG
Yes
Yes
Yes (See5.5.1)
No
Yes
Yes
Polyflex GFR
Yes
Yes
No
No
Yes
Yes
Polyflex SAP or SAP FR
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Mule -Hide SA-APP Cap Sheet
or SA-APP Cap Sheet (FR)
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations.
TABLE 1A:
ALLOWABLEML.E ADHESIVE UNDERLoMi N CONtBINATIONS .'
Adhesive
Florida Product
Underlayments
Approval
DAP Foam Touch 'n Seal StormBond Roof
FL14506
Polystick TU Plus, Polystick TU Max
Tile Adhesive
DoW TileBondTM
FL22525
Polystick TU P, Polystick TU Plus, Polyflex SAP or Tile Pro
Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro,
ICP Adhesives Polyset® AH-160
F1.6332
Elastoflex G TU, Elastoflex 56 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR,
Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR)
Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro,
ICP Adhesives Polyset" RTA-1
FL6276
Elastoflex G TU, Elastoflex 56 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR,
Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR)
2 Refer to Tile Manufacturer's orAdhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
NEMO ETC, I.I.C. Evaluation Report P12060.02.09-R24
Certificate of Authorization 932455 6t" EDITION (2017) FBC NON-HVHZ EVALUATION FL52S9-R28
Polyglass Roof Underlayments, (9S4) 233-1230 Revision 24: 01/24/2018
Page 5 of 14
5.6� 5.6.1
1
5.6.3
-ONE-Wjetc.
Allowable Substrates:
Direct=Bond to Deck-'
Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet
(FR) self -adhered to-
> New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D4.1 primed existing
plywood; New or existing, unprim - ed. OSB; ASTM D41 primed OSB;.Southern Yellow. Pine; ASTM D41 primed
Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels
(designed andinstalled to meet Wind loads for project).
Note: Polyglass does. not: require Priming of new or existing plywood or OSB sheathing. New or existing plywood or
.
OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes.
-Elastoflex GT.U,-ElastoflexS6,G,or Elastoflex S6 G FR in hot asphalt to:
>.➢ ASTM D41 primed structural concrete.
Polyflex d or Polyflex G FR torch -applied to:
>'ASTM: D41 primed structural concrete.
Band-tot-Insulatiom.
Polystick (all'Vaditions),- Polyflex SAP or -SAP FR, M4le-Hide'SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered
to:
> ASTM C1289, Type [I, Class 1 p 'olyi ocyanurate' or Type V polyisocVanurate-composite insulation; Dens Deck
s
DuraGuard; Dens Deck Prime; dr-SECUROCKGypsum-Fiber Roof Board.
Elastoflex G TU, Elastoflex S6G.orElas.toflekS6G FR in hot asphalt to:
> Dens Deck Prime or SECURO,CK Gypsum -Fiber Roof Board. .... ..
Polyflex,G or Polyflex G FR torch -applied to:
> ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically -attached prepared roof coverings, Insulation shall be attached.pdr minimum -
reiluirements of the.prepared roof covering manufacturer's Product Approval. For installations under foam -on tile
systems, insulation attachment shall be designed by a'qualified design professional and ,installed based on testing of
the insulation/underliyment system in accordance with FBC Section 1504.3.1.
Bond to Mechanically Attached Base Layer:
Polystick . (all. variations), Polyflex SAP or SAP FR, Mule -Hide. SA-APP Cap Sheet or SA-APP Cap Sheet (FR)'Dual Pro or
Tile Pro self-aidhered.to:'
-> ASTM D226, Type I . or-11 felt;. Elastobase; Elag@Sise P or Mule -Hide Nail- Base..
Elastoflex IS TU,- Elastoflex S6 G or.Elastoflex S6 G FR in hot asphalt to:
> . ASTM D226, Type
e I or 11 felt, Elastobase; Elastobase P, Mule -Hide Nail Base, or Polyglass'G2.Base.
Polyflex G or Polyflex G FR torch -applied to:
> Elastobase; Elastobase P,_ Mule -Hide Nail Base, Polyglass G2'Base or Polyglass APP Base.
For installations under mechanically attached prepared roof coverings, -base layer.shall be attached per minimum
codified requirements. :For installations under foam -:on tile systemi,.Oase layer shall, be attached per minimum
requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein,- or as tested in -
accordance with FBC Section 1504.11.
NEMOETC, U.C. lival - uation Report P12060.02.09-R24
I
Certificate ofAutharizaMn 432455 e EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28
PoIVgIass Roof Underla4menits, (954)233-1230 Revision 24:01/24/2018
Page 6 of 14
1
ONEMOletc.
5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12) does.not
address wind uplift resistance of all underlayment systems beneath foam -on the systems, where the.underlayment .
forms part of the load:path.' The following wind uplift limitations apply to underlayment systems that are not
addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure Is the
result of testing for wind. load resistance based on allowable wind'loads, and reflects the ultimate passing pressure
divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied).Refer to FRSA/TRI April 2012 (04-
12), Append)x A, Table 1A or FBC 1609 for determination of design wind loads.
#1 'Maximum Design Pressure -90 psf:
Deck: Min. IS/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: None
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus,.Polystick TU Max, Polyflex SAP, Polyfle,x SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule=Hide SA-APP Cap Sheet (FR), self -adhered.
#2 Maximum Design Pressure = -97.5 Dsf:
Deck: Min..15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: PG100 or ASTM D41
Base Ply: (Optional) Polystick MTS or. Polystick MTS PLUS, self -adhered.
Underlayment:• Polystick TU P; •Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x .
1Y.." ring shank nails through 32 ga:,1-5/8" diameter tin caps spaced 12-Inch o.c,
#3 Maximum Design Pressure = 405 DO
Deck: Min. 15/327inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: WB-3000.
Base. Ply:: (Optional) Polystick MTS or Polystick MTS PLUS; self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus,.Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA APP Cap Sheet and
Mule Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x
1Y," ring shank'nails'through 32 ga.,1-5/8" diameter tin caps spaced 12-Inch o.c.
#4 Maximum Design Pressure = -235 psf
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: (Optional)PG100orASTM,D41
Base Ply:: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Joints: Min. 4-inch wide strips of Elastoflex SA-V over all plywood joints.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP. FR, Mule -Hide SA APP Cap Sheet and
Mule -Hide SA=APP Cap Sheet.(FR), self -:adhered.
#5 Maximum Design Pressure = -315 psf,
Deck: - Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: PG 100 or ASTM 641
Base Ply: (Optional) Polystick MTS or'Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Tile Pro, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap
Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered:
#6 Maximum Design Pressure = -622.5 Dsf: .
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: PG100orASTM D41
Underlayment: Elastoflex G TU or.Elastoflex S6'G1 applied.in full mopping of hot asphalt or Polyflex G, torch -applied.. .
#7 Maximum Design Pressure = -30:0 Dsf*:. .
Deck: Min. 15/32-inch OSB to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase'or Mule -Hide. Nail Base (poly -film top surface)"
Fasteners: 11 ga. x 1.25-inch long x 1-inch head diameter round metal cap nails
Spacing:.. . 6-inch o:c. at the 3-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows.
Base Ply: (Optional)-Polystick MTS.or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR; Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self=adhered.
NEW ETC, I.I.C. Evaluation Report P12060.02.09-R24
CerGflcate ofAutharization #32455 . - 6T" EDITION (2017) FBC NON-HVHZ EVALUATION - FL5259-R28.
Polyglass Roof. Underlayments; (9s4) 233-1230 Revision 24: 01/24/2018
Page 7 of 14
#9
#10
#12
#13
#14'
IINNEMO etc.
Maximum Design Pressure = -37.5 psf*:
Deck:- Min.15/32-inch plywood to meet project requirements to satisfaction of Authority'Having.lurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) ..
Fasteners: 11 ga. x 1,25-inch long x 1-inch head diameter round metal cap nails. ,
Spacing: 6-inch o.c, at the 3-inch wide side laps and 6-Inch o.c. at two (2) equally spaced staggered center rows.
Base Ply:. (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU .P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet.and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered:
Maximum Design Pressure = -37.5 psf*:
Deck: Min..19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet:. One (1) or two (2) layers ASTM D226, Type II felt
Fasteners: 11 ga. x 1.25-inch long x -1-inch head diameter round metal cap nails "
Spacing:. 6-inch o.c. at the 3-inch wide side laps and 12-inch o.c. at two (2). equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt.
Maximum Design Pressure = -45 psf*: .
Deck: Mina 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: One (1) layer ASTM D226, Type 11,felt
Fasteners: 11 ga.'x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter. tin caps
Spacing: 4-inch o.c. at the 2-Inch wide side laps and 4-inch o.c: at two (2) equally spaced staggered center rows.
Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU, applied In full mopping of hot. asphalt:
Maximum Design. Pressure = -45 psf*:
Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. .
Base Sheet: Two (2) layers ASTM D226, Type II felt
Fasteners: 11 ga. x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1=5/8-Inch diameter tin caps
Spacing: 9-inch o.c. at the 2-Inch wide side laps and 9-inch o.c. at two (2). equally spaced staggered center rows.
Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Pius, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU,or Elastoflex S6 G, applied in full mopping of hot
asphalt.. . .
Maximum Design- Pressure = -45 osf
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having jurisdiction.,,
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners '
Spacing:... . 9-inch o.c. at.the 2-inch wide side laps and 18-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
Maximum Design Pressure = -52.5 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: - Elastobase (sanded top surface. for hot -asphalt or torch -applied -cap or poly-filrn surface for.torch=applied cap)
Fasteners: Simplex MAXX Cap Fasteners'
Spacing:: 9-Inch o.c. at the 2-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment; Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hat asphalt or,Polyflex G, torch -applied.
Maximum Design Pressure = -52.5 psf:
Deck: Min. 15/32-inch'plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: Simplex Original Cap Nails
Spacing: 64nch o.c. at the 3-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows.
Base Ply:. (Optional).Polystick.MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and.
Mule -Hide SA-APP Cap Sheet (FR),-self-adhered.
NEMO ETC, I.I.C. Evaluation Report. P12060.02.09-1124
CertbYcate ofAuthorizatfon A32455 6TM EDITION (2017) FBC NON-HVH2 EVALUATION FL52594t28
Polyglass Roof Underlayments, (954) 233-123Revision 24: 01/24/2018
.0
_ Page 8 of i4
#15 Maximum Design Pressure = -52.5 Dsf:
Deck:.. Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex Original Cap Nails
Spacing: 6-inch o.c. at the'3-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Elastoflex G.TU or Elastoflex S6 G, applied in full -mopping of hot asphalt or Polyflex G, torch -applied.
#16 Maximum Design Pressure = -60 Dsf:
Deck: Min.19/32-inch plywood to"meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface fortorch-applled cap)
Fasteners: 11 ga. x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter.tin caps
Spacing: 87inch o.c. at the 4-Inch wide side laps and 8-inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, "torch -applied.
#17 Maximum Design Pressure = -60 Dsf:
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.. - -
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: OMG #12 Standard Roofgrip with OMG Flat Bottom Metal Plates
Spacing: 12-inch o.c. at the 4-Inch wide side laps and 12-inch ox. at two"(2) equally spaced staggered center rows.
Underlayment: Elastoflex.G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#18 Maximum Design Pressure = -67.5 psf:
j Deck: Min. 15/32-inch" plywood to meet project requirements to satisfaction of Authority HavingJurisdiction.
Base Sheet: Polyglass G2.Base or Poiyglass APP Base (requires use of torch -applied underlayment)
Fasteners: 12 ga. x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/84nch diameter "tin caps
Spacing:. 8-inch o.c. at the 4-inch wide side laps and 8-inch o.c. at four (4) equally -spaced staggered. center. rows: .
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied..
#19 Maximum Design Pressure = -75 psf
Deck: -Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction:.
Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment)
Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG TGolvalume.Steel Plates, OMG Roofgrip #14 with
OMG flat.Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates -or Simplex MAXX Cap
Fasteners
Spacing:' 10-inch o.c. at the 4-inch wide side laps and 10-inch o.c. at three (3) equally spaced staggered center rows."
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied. .
#20 I Maximum Design Pressure = -90 Dsf:
Deck: Min: 15/32-inch plywood to meet project requirements to satisfaction of Authority. Having Jurisdiction.
Base Sheet: Elastobase (sanded.top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex.MAXX Cap Fasteners
Spacing: 6-inch o.c. at the 2-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment:. Elastoflex G TU or Elastoflex S6 G,.applled 16 full mopping of hot asphalt or Polyflex G, torch -applied.
#21 i, Maximum Design Pressure =-90 Dsf:' "
Deck Min. 15/32-4nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: OiVIG #12 Standard Roofgrip or OMG #14 Heavy, Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal " .
Plates r
Spacing:. 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows..
Underlayment: Elastoflex G TU or Elastoflex S6 G,, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#22 Maximum Design Pressure = -90 Dsf:
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction:
Base Sheet:. Elastobase (sanded top surface)
Fasteners: Trufast #12 DP or Trufast #14 HD with Trufast 3" Metal Insulation Plates
Spacing: " 6-inch o.c. at the'44nch wide side laps and 6-inch o.c. at three (3).equally spaced staggered'center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt.
NEMO ETC, I.I.C. Evaluation Report P32060.02.09-1124
Certificate ofAuthorization #32455 6'" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 9of14
#231
#24
I
#25
#26
#27
�I
#28
f0NEM0.1.ett.
Maximum Design Pressure = -90 psf
Deck:. Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction:
Base Sheet: Polyglass G2 Base or Polyglass APP Base.(requires use of torch-opplied underlayment)
Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with'OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with
CMG Flat Bottom Plates (Accarac),.Trufast HD with. Trufast'3-inchInsulation Plates or Simplex MAXX .Cap
Fasteners
Spacing: 9-inch o.c. at the 4-inch wide side laps and 9-inch o.c. at four (4) equally spaced staggered center rows.- .
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in'full mopping of hot asphalt or.torch-applied or Polyflex G, torch-.
applied.
Maximum Design Pressure =-97.5 psf:
Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film tap surface)
Fasteners: • • 11 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch. diameter tin caps
Spacing: 4-inch o.c. at the 4-inch'wide side laps and flinch o.c. at four (4) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick MTS.PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max,.Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule=Hide SA-APP Cap Sheet (FR), self -adhered.
Maximum Design Pressure = -105 psf. .
Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 6-Inch o.c. at the 2-inch wide side laps and.6-inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU.or Elastoflex S6 G, applied in full mopping of hot asphalt or, Polyflex G,,torch-applied.
Maximum Design Pressure = -112.5 psf:
Deck. Min'.,19/32-inch plywood.to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface)' .
Fasteners: 11 ga. x 1.25-Inch x 3/8-inch head diameter annular ring shank roofing, nails. at 1-5/8-inch diameter tin caps
Spacing: 6-1nch o.c. at the'4-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows.
Primer: PG100 or ASTM D41 primer at all tin -caps
Base Ply: Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA APP Cap Sheet (FR), self -adhered.
Maximum Design Pressure = -120 psf: -
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: •Elastobase.(sanded top surface for hot -asphalt or -torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: OMG .#12.Standard.Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal
Plates .
Spacing: . 6=inch o.c. at the, 4-inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows.-.
Underlayment: Elastoflex.G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
Maximum Design Pressure = -120 psf .
Deck: Min'.15/32-irich plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface) .
Fasteners: Trufast#12 DP orTrufast#14 HD with Trufast 3" Metal Insulation Plates
Spacing: . 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows.
Underlayment:.Elastof16 G TU.or. Elastoflex S6 G, applied in full mopping of hot asphalt.
All other. direct -deck, adhered. Polyglass underlayment systems beneath. foam -on the systems carry a Maximum
Design Pressure of-45 psf.
NEMO ETC, LLC. Evaluation Report P12060.02:09-1124
Certificate of Authadzatbn #32455 6TM EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-RZR
Polyglass Roof Underlayments; (954) 233-1230 -Revision 24: 01/24/2018
.. Page.10 of 14
I
f0NE]M0jlAC.
5.6..2 For mechanically attached. Base. Sheet; the maximum design pressure for the selected assembly shall meet or exceed
that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A. .
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design.
pressure determined in accordance. with FBC 1609. In this case, Zones 2 and 3 shall employ an 'attachment density
designed by a qualified. design professional to resist the elevated pressure criteria. Commonly used methods, are
ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29' and Roofing Application Standard RAS 117. Assemblies marked
with an asterisk's carry the limitations. set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January
2016) for Zone .2/3 enhancements: .
5.7 Exposure Limitations:
Elastobase; :Elastobase P, Polyglass G2 Base. or Polyglass APP Base shall not be left exposed for longer than .30-days
. after installation.
Polystick IR-Xe or. Polystick MU-X shall not be left exposed for longer than 90-days after installation.
Polystick MTS;.MTS.PLUS, TU P, TU Plus,TU Max; Dual Pro, Tile Pro or Elastoflex G.TU shall not be.left exposed for
longer than 180-days after. installation.
Polyflex SAP or SAPFR, .or Mule -Hide SA-APP. Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure
limitation, unless the prepared roof covering Is to be adhesive -set tile, in which 'case the maximum exposure is 30
days.
Elastoflex S6 .G or Elastoflex S6 G FR or Polyflex G or Polyflex G FR does not have. an exposure limitation, unless the
.prepared roof covering is to be adhesive -set tile (Elastoflex S6 G or Polyflex G only),. in which case the maximum
exposure is 180 days. .
5.8 Polystick MU-X has been found through comparative testing to have a lesser coefficient'of friction. than ASTM D226
roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as
set forth. in Section 4.3, Note 1 of ASTM D1970-15, should be established as to slip resistance.
5.9 Tile Slippage Limitations (FRSA/TRI April 2012 (04.42)):
when loading roof tiles on the underlayment-in direct -deck tile assemblies, the maximum roof slope shall be as
$illnum ThPcp chine limitations can -only he exceeded by using'battens during loading of the roof tiles.
Tg8LF;2:.TILE.SLIPPAGE UMITAT10N5FOR DIR�GT• DEGKTILEINS7ALLATIONS..
Underlayment
Tile Profile
Staging Method
Maximum Slope
Elastoflex G TU
. I
Flat
10-tile stack
7:12
. Lugged
RAlle stack (6 over 2)
6:12 .
Elastoflex S6 G or56 G FR
Flat or Lugged
6-tile stack (4 over 2)
4:12
Polystick MTS or MTS PLUS .
Flat
6-tile stack (4 over 2)
5:12
Lugged
&tile stack (4 over 2)
4:12
Polystick Tile Pro
Flat or Lugged,
6-tile stack (4 over 2)
7:12
Polystick TU Max
Flat
6-tile stack (4 over 2) or 10-tile stack
7:12
Lugged
6-tile stack (4 over 2)
7:12
Lugged:
10-tile stack
6:12
Polystick TU P
Flat
6-tile stack (4 over 2)
6:12
Lugged
6-tile stack (4 over 2)
4:12
Polystick TU Plus
I.
Flat or Lugged
6-tile stack (4 over 2)
7:12
Flat or Lugged ' .
104ile stack
6:12.
Poly(Iex,G or G FR
Flat or Lugged,
6-tile stack (4 over 2) '
4:12
Poly(lex SA P o -SA P FR
Flat or Lugged
6-tile stack (4 over 2)
4:22
NEMO ETC, LLC. Evaluation Report P12060.02.09-1124
eeri ate of AuthodwtFan #32455. GP EDITION (2017) FBC NON-HVHZ EVALUATION FL52S9-R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 11 of 24
i
ONEMOJetc.
6. INSTALLATION:
6.1 Polyglass .Roof Underlayments shall be installed in accordance with Polyglass published installation requirements
subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove
any dust and debris prior to application, and prime the substrate (if applicable).
6:3 Elastobase Elastoi>Iase PorMule-H(de Nail ease:.
Non Tile Applications:
Shall be installed in compliance with the codified requirements for ASTM D226, Type If underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polystick, Polyflex SAP, Polyflex SA
P FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastoflex G TU, Elastoflex S6 G or
Elastoflex S6 G FR in hot asphalt or Polyflex G or Polyflex G FR, torch applied. Roof cover limitations are those are
those associated with the top -layer underlayment, as set forth in Table 1.
6.3.2 Tile Applications:
Elastobase, Elastobase P or Mule -Hide Nail Base are limited to use as a mechanically attached base sheet in the 'Two
Ply System" from FRSA/TRI April 2012 (04-12). Reference is made to Table 1 and Section 5.6.4 herein, coupled with
FRSA/TRI April 2012 (04-12) Installation. Manual.
6.4 lystie[ fyfT , MTS PLUS, IR=Xe, TU.P, TU P.lus, TU Max, Dua(%Pro, Tile Pro or MU X or•Polyflex SAP, Polyflex SAP FR;
Mule-Hide`SA APP Cap Sheet orMule-Tilde SA APP Cap Sheets FR)
{
6.4.1 Shall be installedin compliance with the codified requirements for ASTM D1970 (except Polystick TU P) underlayment
6.4.2
in FBC Table 1507.1.1 for the type of prepared roof covering to be installed.
Direct -to -Deck with Mechanically Fastened Roof Covers:
All self-adhering'materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule -Hide SA-APP
Cap Sheet or SA-APP Cap Sheet (FR) should be. back -nailed in selvage edge seam in accordance with Polyglass / Mule -
Hide back nailing guidelines. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 1-inch
diameter metal disk or Simplex -type metal cap nail, at a minimum rate of 12" o.c. Polystick TU Plus should be back -
nailed using the above noted fasteners and spacing, in area marked "nail area, area para clavar" on the face of
membrane. The head lap membrane is to cover the area being back -nailed.
All seal -lap seams (selvage laps) must be
firmly rolled with a. minimum 28 lb. hand
roller to ensure full contact and adhesion.
For Dual Pro and Tile Pro, align the edge of
the top sheet to; the end of the glue pattern
(the sheet will overlap the fabric).
View of Ovelap Seam of Dual Pro and Tile Pro
All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus 50 Premium Modified
Wet/Dry Cement or Polyglass PG500 Modified Cement applied in between the application of the lap.
Polystick TU Plus, Dual Pro and Tile Pro may not be used in any exposed application_ such as crickets, exposed valleys,
or exposed roof to wall details
NEMO ETQ, U.C. Evaluation Report P12060.02.09-R24
Cert!lflcare ofAurhorLmdoo #32455 67X EDITION (2027) FBC NON-HVHZ EVALUATION . FL5259-R28
Polyglass Roof Underlayments; (9541233-2230 Revision 24: 02/24/2018
Page 12 of 14
NEW j etc.
Repair of Polystick membranes is.to be accomplished by applying Polyplus.50 Premium Modified Wet/Dry.Cement or
Polyglass P6500 Modified Cement-to.the area in need of repair, followed by a minimum 6 k 6 inch patch of the
Polystick material of like kind, set, and hand rolled In place over .the repair area. Patch laps,_ if. needed, shall be
installed in a water shedding manner.
All Polystick membranes. shall .be installed to ensure full, .contact with approved substrates. Polyglass requires a"
minimum of 40-lb weighted -roller or; -on steep slopes, use of a stiff broom with approximately 40-I4s of load applied •.
for.the field membrane.Hand rollers are acceptable for rolling of patches, laps (min. 28 lb roller) or small areas of the
roof that are not accessible to a large roller or broom.
_ 6.4.3 Tile Applications (not allowed for Polystick Dual P% IRXe or Polystick MU X): .
Reference is made to FRSA/TRI April 2012 .(04-12) Installation Manual and Table I. herein, using the instructions
noted.above as a guideline.
For mechanically fast roofing over 2-ply system; consisting of Base Sheet and self -adhering -top sheet(s), Base
Sheet fastening shall be not less than FRSA/TRI April 2012 (04712), Table 1.
For adhesive -set tile applications, refer to Section 5.6.4 herein..
6.4.4 Two (2) Ply Underlayment Systems:
Polystick MTS or: MTS PLUS'followed by Polystick MTS, MTS. PLUS,TU P, TU Pius, TU Max, Tile Pro, MU-X or Polyflex
SAP is allowable for. use under.mechanically attached prepared roof systems.. Limits -of use are those associated with
the top -layer material. This is not a requirement, but is allowable if a 2-
ply underlayment system is desired. .
Polystick MTS or MTS PLUS followed by Polystick TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP isallowable for use
under foam -on the systems. Limits of use are'those associated with.the top -layer. material. This is not.a requirement, .
j but is allowable if a 2-ply,underlayment system is desired.
E{a toflex G7U, Elastaf(ex S6:G oKIastof1eX56 G Fii
6.5A Elastoflex G TU, Elastoflex S6 IS or.Elastoflex S6 G. FR shall .be.installed in compliance with. current Polyglass published
installation requirements.. For use in tile applications:
j ✓ Elastoflex G TU is for use as an alternate to "Mineral Surface.Roll.Roofing" (ASTM D6380, ClassM) In the "Single.
Ply System" from FRSA/TRI April 2022 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied--'.'Cap.Sheet" in the "Two Ply System" .from FRSA/TRI April 2012 (04-12) beneath mechanically, fastened or
adhered tile roof systems.
✓ Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply
System"from FRSA/TRI April. 2012 (04-12) beneath mechanically fastened tile, roof systems or the Hot Asphalt
. .. applied"Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12).beneath mechanically. fastened. or
adhered tile roof systems.
✓ Elastoflex S6 G FR is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single .
Ply System" from.FRSA/TRI -April 2012 (64-12) beneath mechanically fastened tile roof systems or the•Hot Asphalt
applied "Cap Sheet" in the `Two Ply'System"from FRSA/TRI, April 2012 (04-22).beneath mechanically fastened tile
roof systems.
6.5. . For hot -asphalt -applications, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6. G FR shall.be fully asphalt -applied to.the
substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-inch wide, off -set.
minimum 3'feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt
with asphalt extending approximately 3/8-inch beyond the lap edge.
6.6:1 Polyflex.G or. Polyflex G FR shall be installed in compliance with current Polyglass published installation requirements.
For use in file applications:.....
j ✓ Polyflex G is for use as an alternate to.the Heat Applied,"Cap Sheet" in the "Two PIy. System" from FRSA/TRI April
2011(04-12) beneath mechanically fastened or'adhered tile roof systems (Base Sheet Limited per 5.6.3).
✓ Polyflex G FR is for use as an alternate to the Heat Applied "Cap, Sheet" irl the."Two Ply System" from FRSA/TRI.
April 2012 (04-12) beneath mechanically fastened the roof systems (Base Sheet Limited per 5.6.3).
NEMO ETC, I.I.C. Evaluation Report 1312060.02:09-R24
Certificate i fAuthodzation A324W e. EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230_ Revision 24: 01/24/2018
Page 13 of 14
i
7.
8.
NEMO l etc.
6.6.2 Polyflex G. or Polyflex G. FR shall be fully torch -applied to, the substrates. noted In Section 5.6. Side laps shall be
minimum 3-inch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course., Side and end
laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyondthe lap
edge.
6_7 Tile Stanina: .
6.7.1 Tile shall be loaded and staged In a manner that prevents tile slippage and/or, damage to the underlayment.. Refer to
Table 2 herein, and Polyglass published requirements for the staging.,
6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used
on all roof slopes greater than 7:12.. Precautions should be taken .as needed, such as the use of battens or nail-
' boards, to prevent tle sliding and/or damage to the underlayment during the loading process..
6.7.3 Polyglass.specifies the minimum .cure .time after installation of .self'adhering membranes and. before loading of
roofing tiles is forty-eight (48) hours.
BUILIDING PERMIT REQUIREMENTS:.. .
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate'the installation of this product.
MANUFACTURING PLANTS: .
Contact the noted QA agency for information on product locations covered for F.A.C. 61620-3 QA requirements..The following
olants have aualified oroducts under their respective physical properties specifications.
Plant .:.. • ' �.:'
7.
8.
NEMO l etc.
6.6.2 Polyflex G. or Polyflex G. FR shall be fully torch -applied to, the substrates. noted In Section 5.6. Side laps shall be
minimum 3-inch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course., Side and end
laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyondthe lap
edge.
6_7 Tile Stanina: .
6.7.1 Tile shall be loaded and staged In a manner that prevents tile slippage and/or, damage to the underlayment.. Refer to
Table 2 herein, and Polyglass published requirements for the staging.,
6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used
on all roof slopes greater than 7:12.. Precautions should be taken .as needed, such as the use of battens or nail-
' boards, to prevent tle sliding and/or damage to the underlayment during the loading process..
6.7.3 Polyglass.specifies the minimum .cure .time after installation of .self'adhering membranes and. before loading of
roofing tiles is forty-eight (48) hours.
BUILIDING PERMIT REQUIREMENTS:.. .
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate'the installation of this product.
MANUFACTURING PLANTS: .
Contact the noted QA agency for information on product locations covered for F.A.C. 61620-3 QA requirements..The following
olants have aualified oroducts under their respective physical properties specifications.
Plant .:.. • ' �.:'
:`So�cificat'io • „ `>���`•
;Product s
Fernley,. NV, Hazleton, PA & Winter Haven, FL
ASTM D1970
Pol stick.MU-X.
Hazleton, PA
M-D.13-.0004 •
Elastoflex G TU
i
Hazleton, PA & Winter'Haven, FL
j
ASTM D1970
Polystick IR-Xe
ASTM b1970 &•FRSA/TRI April 2012
Polystick TU Plus
ASTM D1970.& FRSA/tRl April 2012
Polystick TU Max .
Tuscaloosa, AL
ASTM D4601; Type II
Polyglass G2 Base
Winter
Haven, FL
ASTM D226 (physicals)
Elastobase, Elastobase P
ASTM D6509
Polyglass APP Base
FRSA/TRI April 2012.
Polystick MTS, Polystick MTS PLUS
FRSA/TRI April 2012
'PolystickTU P
FRSA/TRI April 2012
Polyflex SAP, Polyflex SA P FR
ASTM D1970
Polystick Dual,Pro
ASTM D1970.& FRSA/TRI April M12
Polystick Tile Pro
ASTM D6164
Elastoflex S6, Elastoflex S6 G FR
ASTM D6222
Polyflex G, Polyflex G FR
9. QUALITY ASSURANCE ENTITY:
LIL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com
- END OF EVALUATION REPORT - .