Product Approval
USER: Public User
Product Approval Menu > Product or Application Search > Application List > Application Detail
FL #
Application Type
Code Version
Application Status
Comments
Archived
Product Manufacturer
Address/Phone/Email
Authorized Signature
Technical Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category
FL2533-R20
Revision
2017
Approved
N
SCANNED
BY
St Lucie County
CertainTeed Corporation -Roofing
20 Moores Road
Malvern, PA 19355
(610) 893-5400
mark.d.harner@saint-gobain.com
Mark Harrier
mark.d.harner@saint-gobain.com
Mark D. Harrier
18 Moores Road
Malvern, PA 19355
(610) 651-5847
Mark.D.Harner@saint-gobain.com
Roofing
https:ltfloridabuilding.org/pr/pr app dtl.aspx?param=wGEVXQwtDgvwelwRFXRvHOHSbalV%2f8Ets3rRVh8k3uB2Sy%2b%2gMVggA%3d%3d
ST. LUCIE
BUILDING
FOR
REVIEWED BY
DATE to I2C— 1
F AN5 AND PER IT
MUST BE KEPT ON OB OR
NO INSPECTION WIL BE MADE
THESE PLANS AND ALL PROPOSED WORK. .
ARE SU ECT TO ANY CORREC T ONS ,.
(REQUIRED BY FIELD INSPECTORS THAT
MAY DE NECESSARY IN ORDER M �
COMPLY WITH ALL APPLICAKE CODES.
CONCEALED FASTENERS OR -ATTACHMENTS
ARE THE RESPONSIBILITY OF THE
CONTRACTOR OF RECORD
P
t _
E %40PY
. -a
113
1 0/8/201 8 „
Florida Building Code Online
Subcategory Modified Bitumen Roof System
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed Florida
Professional Engineer
E' Evaluation Report - Hardcopy Received
Florida Engineer or Architect Name who developed the
Evaluation Report
Florida License
Quality Assurance Entity
Quality Assurance Contract Expiration Date
Validated By
Certificate of Independence
Referenced Standard and Year (of Standard)
Equivalence of Product Standards
Certified By
Sections from the Code
Product Approval Method
Date Submitted
Date Validated
Date Pending FBC Approval
Robert Nieminen
PE-59166
UL LLC
03/09/2020
John W. Knezevich, PE
W) Validation Checklist - Hardcopy Received
FL2533 R20 COI 2018 01 COI NIEMINEN.pdf
Standard
Year
ASTM D6162
2008
ASTM D6163
2008
ASTM D6164
2011
ASTM D6222
2011
ASTM D6509
2009
FM 4470
2012
FM 4474
2011
Method 1 Option D
06/20/2018
06/20/2018
06/27/2018
https://floridabuilding.org/pr/pr app_dtl.aspx7param=wGEVXQwtDgvwelwRFXRvHOHSbaIV%2f8Ets3rRVh8k3uB2Sy%2b%2fMVggA%3d%3d 2/3
10/8/2018 . Florida Building. Code Online
Date Approved 08/15/2018
Summary of Products
FL # Model, Number or Name Description
2533.1 Flintlastic Modified Bitumen Roof Modified Bitumen Roof Systems
Systems
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL2533 R20 II 2018 06 FINAL Al ER CERTAINTEED MODBIT FL2533-
Approved for use outside HVHZ: Yes R20.pdf
Impact Resistant: N/A Verified By: Robert Nieminen, PE PE-59166
Design Pressure: +N/A/-635 Created by Independent Third Party: Yes
Other: 1.) Refer to ER Section 5 for Limits of Use. 2.) Evaluation Reports
The design pressure noted in this application relates to FL2533 R20 AE 2018 06 FINAL ER CERTAINTEED MODBIT FL2533-
one specific system. Refer to the ER Appendix for all R20.pdf
systems and max design pressures. Created by Independent Third Party: Yes
Back Next
Contact Us :: 2601 Blair Stone Road, Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida.:: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a public -records request, do not send electronic mail to
this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. *Pursuant to Section 455.275(1), Florida
Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address if they have one. The emails provided may
be used for official communication with the licensee. However email addresses are public record. If you do not wish to supply a personal address, please provide the Department
with an email address which can be made available to the public. To determine if you are a licensee under Chapter 455, F.S., please click here .
Product Approval Accepts:
® 99 Im
Credit
s� eurit�=n�t_7•xte5-
https://floridabuilding.org/pr/pr app_ fl.aspx?param=wGEVXQwtDgvwelwRFXRvHOHSbalV%2f8Ets3rRVh8k3uB2Sy%2b%2fjjMVggA%3d%3d 3/3
nt4
- -NEMO
TABLE`
DECK:' ::.,
APPLICATION, . '.::
":TYPE
'DESCRIPTION ."
PAGE;
1A
Wood
New or Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
5-6
18
Wood
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
7
1C
Wood
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
8-9
1D
Wood
New, Reroof (Tear -Off) or Recover
D
Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
10-12
1E-1
Wood
New, Reroof (Tear -Off)
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
13-15
1E-2
Wood
New, Reroof (Tear -Off) or Recover
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
16-17
1F
Wood
New or Reroof (Tear -Off)
F
Non -Insulated, Bonded Roof Cover
17
2A
Steel or Structural Concrete
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
18-20
28
Steel or Structural Concrete
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
2141?
2C
Steel or Structural Concrete
New, Reroof (Tear -Off) or Recover
D
Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
26-;L_ -
3A
Concrete
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
29-36
3B
Concrete
New or Reroof (Tear -Off)
A-3
Bonded Temp Roof/Vapor Barrier, Bonded Insulation, Bonded Roof Cover
36
3C
Concrete
New or Reroof (Tear -Off)
F
Non -Insulated, Bonded Roof Cover
37
4A
LWIC
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
38-39
4B
LWIC
New or Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
40
4C
LWIC
New, Reroof (Tear -Off)
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
41-44
5A
CWF
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
45
58
CWF
New or Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
46
Sc
CWF
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
46
SD
CWF
New, Reroof (Tear -Off)
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
47
6A
Gypsum
Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
48-49
6B
Gypsum
Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
50
6C
Gypsum
Reroof (Tear -Off)
C
Mech. Attached Insulation, Bonded Roof Cover
51-
6D
Gypsum
Reroof (Tear -Off)
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
51
7A
Various
Recover
A-1
Bonded Insulation, Bonded Roof Cover
52-57
713
Various
Recover
F
Non -Insulated, Bonded Roof Cover
57
The following notes apply to the systems outlined herein:
1. The roof system evaluation herein pertains to above -deck roof components. Roof decks shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the
roof deck shall be documented through proper codified and/or FBC Approval documentation.
2. Unless otherwise noted, fasteners and stress plates for insulation attachment shall be as follows. Fasteners shall be of sufficient length for the following engagements:
➢ Wood Deck: OMG #14 Roofgrip with Flat Bottom Plate (Accutrac), OMG HD with OMG 3 in. Galvalume Steel Plate, Dekfast #14 with Hex Plate or 3" Round Insulation Plate, Trufast HD with Trufast 3"
Metal Insulation Plates or FlintFast #14 Fastener with FlintFast 3" Insulation Plates. Minimum 0.75-inch plywood penetration or minimum 1-inch wood plank embedment.
➢ Steel Deck: OMG #12 or #14 Roofgrip with Recessed or Flat Bottom Plate (Accutrac), OMG #12 Standard or HD with OMG 3 in. Galvalume Steel Plate, Dekfast #12 or #14 with Hex Plate or 3" Round
Insulation Plate, Trufast DP or HD with Trufast 3" Metal Insulation Plates or FlintFast #12 or #14 Fastener with FlintFast 3" Insulation Plates. Minimum 0.75-inch steel penetration and
engage the top flute of the steel deck.
➢ Structural Concrete: OMG #14 Roofgrip with Recessed or Flat Bottom Plate (Accutrac), OMG HD or CD-10 with OMG 3 in. Galvalume Steel Plate, Dekfast #14 or DekSpike with Hex Plate or 3" Round
Insulation Plate, Trufast HD or CF with Trufast 3" Metal Insulation Plates or FlintFast #14 Fastener with FlintFast 3" Insulation Plates. Minimum 1-inch embedment. Fasteners installed
with a pilot hole in accordance with the fastener manufacturer's published installation instructions.
NEMO ETC, LLC Evaluation Report 3520.03.04-R21 for FL2533-1120
Certificate of Authorization #32455 CH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 21: 06/20/2018
Prepared by: Robert Nieminen, PE-59166 CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-5B47 Appendix 1, Page 1 of 57
1
ONEM01jetc.
3. Unless otherwise noted, insulation may be any one layer or combination of polyisocya nu rate, polystyrene, wood fiberboard, perlite, GlasRoc Roof Board or gypsum -based roof board that meets the QA requirements
of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover.
4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for, or installed beneath rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover),
whereby the base sheet screws and plates are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck
listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper
codified and/or FBC Approval documentation.
S. Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016).
6. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer's published instructions.
➢ Hot asphalt (HA): Full coverage at 25-30 Ibs/square
➢ Ashland Pliodeck (A-PD): Continuous 0.75 inch wide ribbons,12-inch o.c. Ribbons of subsequent layers shall be perpendicular to those in the layer below.
➢ Dow INSTA-STIK Quik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1 inch wide ribbons,12-inch o.c.
➢ Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c.
➢ Millennium PG-1 Pump Grade Adhesive (M-PG3): Continuous 0.5 to 0.75-inch wide ribbons, 12-inch o.c.
➢ OMG OlyBond 500 or OlyBond Green (OB500): Continuous 0.75-inch wide ribbons, 12-inch o.c. (PaceCart or SpotShot)
➢ ICP Adhesives CR-20: Continuous 2.5 to 3-inch wide ribbons, 12-inch o.c.
➢ Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon -applied adhesive, boards shall be staggered from layer -to -layer.
➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
Unless otherwise noted, all insulations are flat -stock or taper board of the minimum thickness noted. Tapered polyisocyan u rate at the following thickness limitations may be substituted with the following Maximum
Design Pressure (MDP) limitations. In no case shall these values be used to 'increase' the
MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then
the thinner board listed below may be used as a drop -in for the equivalent thicker material listed in the table:
➢
Ashland Pliodeck (A-PD) @ 12-inch o.c.
MDP
-105.0 psf
(Min.1.0-inch)
➢
Ashland Pliodeck (A-PD) @ 6-inch o.c.
MDP
-277.5 psf
(Min. 1.0-inch)
➢
Dow INSTA-STIK Quik Set Insulation Adhesive (D-IS):
MDP
-120.0 psf
(Min.1.0-inch)
➢
Millennium One Step Foamable Adhesive (M-OSFA):
MDP
-157.5 psf
(Min.1.0-inch)
➢
Millennium PG-1 Pump Grade Adhesive (M-PG3):
MDP
-157.5 psf
(Min.1.0-inch)
➢
OMG OlyBond 500 (OB500):
MDP
-45.0 psf
(Min. 0.5-inch Multi -Max FA3)
➢
OMG OlyBond 500 (OB500):
MDP
-187.5 psf
(Min. 0.5-inch ISO 95+GL)
➢
OMG OlyBond 500 (08500):
MDP
-315.0 psf
(Min. 0.5-inch ENRGY 3)
➢
OMG OlyBond 500 (OB50O):
MDP
-487.5 psf
(Min. 0.5-inch ACFoam II)
➢
ICP Adhesives CR-20:
MDP
-117.5 psf
(Min.1.0-inch)
B. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft.
For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC
Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria, Commonly used methods are ANSI/SPRI WD3, FM Loss
Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for
Zone 2/3 enhancements.
10. For assemblies with all components fully bonded in place, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no
rational analysis is permitted.
11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the
minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105.
NEMO ETC, LLC Evaluation Report 3520.03.04-1121 for FL2533-R20
Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 21: 06/20/2018
Prepared by: Robert Nieminen, PE-59166 CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 6S3-SB47 Appendix 1, Page 2 of 57
OMEMO I etc.
12. For existing substrates in a bonded recover or re -roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the existing
roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with
ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13. For Concrete Deck or Recover Applications using System Type D, the insulation is optional.
14. Lightweight Insulating Concrete (LWC) shall be cast, in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction.. For systems where specific LWC is referenced, refer to current LWC
Product Approval for specific deck. construction and limitations. For systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat thickness is 2-inches.
For LWC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1
15. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications.
CERTAINTEED FLINTLASTIC" MODIFIED BITUMEN COMPONENTS & APPLICATION METHODS
REFERENCE
MATERIAL
APPLICATION••
BP -AA
Base
Glasbase; All Weather/Empire Base; Flexiglas Base; Flintlastic Base 20
Hot asphalt at 20-40 Ibs/square
Ply
One or more Flintglas PIy.4; Flintglas Premium Ply 6
(Base and Ply sheets, Asphalt -Applied)
BP-AA2
Base
Yosemite Venting Base
Hot asphalt in 24-inch diameter spots in 30-
(Base, Spot -Asphalt -Applied)
inch grid pattern
BP-AA3
Base
Yosemite Venting Base
Hot asphalt in 9-inch diameter spots in grid
(Base, Spot -Asphalt -Applied)
pattern noted herein.
BP-AA4
Base
Yosemite Venting Base
Hot asphalt in 9-inch wide ribbons spaced
(Base, Strip -Asphalt -Applied)
as noted herein.
BP-CA2
Base/Ply
Glasbase; All Weather/Empire Base; Flexiglas Base; Flintlastic Base 20
Henry #903 Adhesive at 1.5 gal/square
BP CA3
Base/Ply
Glasbase; All Weather/Empire Base; Flexiglas Base; Flintlastic ease 20
Millennium Hurricane Force Membrane
Adhesive, beads spaced 6-inch o.c.
Base
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
SBS AA
Ply
One or more Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
Cap
Flintlastic Cap 30; Flintlastic Cap 30 CoolStar, Flintlastic FR Cap 30; Flintlastic FR Cap 30 CoolStar; Flintlastic FR Dual
(SBS, Asphalt -Applied)
Hot asphalt at 20-40 Ibs/square
Cap; Flintlastic FR-P; Flintlastic FR-P CoolStar; Flintlastic Premium FR-P; Flintlastic Premium FR-P CoolStar;
Flintlastic GMS; Flintlastic GMS CoolStar
Base
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
Note:
Base ply cures overnight prior to application of the ply or cap ply.
Flint.8ond Brush or Karnak No. 81 Cold
SBS-CAI
ISM, Cold -Applied)
Process Modified Bitumen Adhesive Brush \
Ply
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
Cap
Flintlastic FR Cap 30, Flintlastic FR Cap 30 CoolStar; Flintlastic FR Dual Cap; Flintlastic FR-P; Flintlastic FR-P CoolStar,
Grade at 1 gal/square
Flintlastic Premium FR-P; Flintlastic Premium FR-P CoolStar; Flintlastic GMS; Flintlastic GMS CoolStar
Base
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
Ply
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
SBS-CA2
Cap
Flintlastic Cap 30; Flintlastic Cap 30 CoolStar, Flintlastic FR Cap 30; Flintlastic FR Cap 30 CoolStar; Flintlastic FR Dual
(SBS, Cold -Applied)
Henry #903 Adhesive at 1.5 gal/square.
Cap; Flintlastic FR-P; Flintlastic FR-P CoolStar, Flintlastic Premium FR-P; Flintlastic Premium FR-P CoolStar;
Flintlastic GMS; Flintlastic GMS CoolStar
NEMO ETC, LLC Evaluation Report 3520.03.04-R21 for FL2533-R20
Certificate of Authorization #32455 6"' EDITION (2017) FBC NON-HVHZ EVALUATION Revision 21: 06/20/2018
Prepared by: Robert Nieminen, PE-59166 CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-SB47 Appendix 1, Page 3 of 57
ONEMO I etc.
CERTAINTEED FLINTLASTIC" MODIFIED B... . .. (CONTINUED)
°<REFERENCE '..:
LAYER:' _
MATERIAL.
APPWCATION
Base
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
Ply
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
SBS-CA3
(SBS, Cold -Applied)
Millennium Hurricane Force Membrane
Adhesive, beads spaced 6-inch o.c.
Cap
Flintlastic Cap 30; .Flintlastic Cap 30 CoolStar; Flintlastic FR Cap 30; Flintlastic FR Cap 30 CoolStar; Flintlastic FR Dual
Cap; Flintlastic FR-P; Flintlastic FR-P CoolStar; Flintlastic Premium FR-P; Flintlastic Premium FR-P CoolStar;
Flintlastic GMS; Flintlastic GMS CoolStar
Base
Flintlastic Ultra Poly SMS Base; Flintlastic Base 20 T
Ply
One or more Flintlastic Ultra Poly SMS Base; Flintlastic Base 20 T
SBS-TA
(SBS, Torch -Applied)
Torch -Applied r
Cap
Flintlastic FR Cap 30 T; Flintlastic FR Cap 30 T CoolStar; Flintlastic GTS; Flintlastic GTS CoolStar; Flintlastic GTS-FR;
Flintlastic GTS-FR CoolStar; FlintClad
APP-TA
(APP, Torch -Applied)
Base
One or more Flintlastic APP Base T; Flintlastic STA; Flintlastic STA Plus
Torch -Applied
pP
Cap
Flintlastic STA; Flintlastic STA Plus; Flintlastic GTA; Flintlastic GTA CoolStar; Flintlastic GTA-FR; Flintlastic GTA-FR
CoolStar
SBS-SA-H
(SBS, Self -Adhering, Hybrid Systems)
Base/Ply
Black Diamond Base Sheet; Flintlastic Ultra Glass SA
Self -Adhering
Base
Flintlastic SA PlyBase; Flintlastic SA Mid Ply
SBS-SA
(585, Self -Adhering)
Self -Adhering
Ply
Flintlastic SA PlyBase; Flintlastic SA Mid Ply
Cap
Flintlastic SA Cap; Flintlastic SA Cap CoolStar, Flintlastic SA Cap FR; Flintlastic SA Cap FR CoolStar
16. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following MDP limitations. The lesser of the MDP listings below vs. those in Table 3A applies:
OPTION
#
VAPOR
..
PRIMER
BARRIER OPTIONS; STRUCTURAL CONCRETE DECK; ADHERED INSULATION PERTABLE 3A; (The lesser of the MDP listings below VS. those
VAPOR BARRIER
in Table 3A applies)
INSULATION ADHESIVE
MDP (PSIS ;:
TYPE
ATTACK.:- -
VB-1.
FlintPrime
Flintlastic SA PlyBase
Self -adhering
OB500,127inch o.c.
-82.5
VB-2.
FlintPrime
Flintlastic GTA
Torch -applied
M-OSFA or M-PG1,12-inch o.c.
-420.0
VB-3.
FlintPrime
Flintlastic Base 20 T, Flintlastic FR Cap 30 T or Flintlastic GTS
Torch -applied
M-OSFA or M-PG1,12-inch o.c.
-495.6'
17. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads.
NEMO ETC, LLC
Certificate of Authorization #32455
Prepared by: Robert Nieminen, PE-59166
eEDITION (2017) FBC NON-HVHZ EVALUATION
CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-5847
Evaluation Report 3520.03.04-R21 for FL2533-R20
Revision 21: 06/20/2018
Appendix 1, Page 4 of 57
ONEMO I etc.
TABLE 1E-2: WOOD DECKS — NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER
SYSTEM TYPE E. NON -INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System ,
.: Deck.
Base Sheet
RoofCover.(Note 14)
1VIDP
No.
(Noted)
::(Psfl :.
Base:
Fasteners
Attach'
Ply:
Cap;
Glasbase; Flexiglas; Flintlastic
Flintfast 3 in. Insulation Plates with
(Optional) BP -
W-89
Min. 15/32-inch plywood
Base 20; Poly SMS Base; Ultra
FlintFast #12 or #14; Trufast 3" Metal
6-inch o.c. at 4-inch lap and 6-inch o.c, in three
AA, SBS-AA,
SBS-AA, SBS-
_97,5
at max 24-inch spans
P
Poly SMS Base; Yosemite
Insulation Plates with DP or HD; OMG 3
(3), equally spaced, staggered center rows
SBS-TA or
TA or APP-TA
in. Round Metal Plates with OMG #14 HD
APP-TA
W 90
Min. 15/32-inch plywood
Flintlastic APP Base T
OMG 3 in. Round Metal Plates with OMG
6-inch o.c. at 4-inch lap and 6-inch o.c. in three
APP-TA
APP-TA
-97.5
at max 24-inch spans
#14 HD
(3), equally spaced, staggered center rows.
Glasbase; Flexiglas; Flintlastic
W-91
Min. 15/32-inch 1
plywood
Base 20; All Weather / Empire
Flintfast 3 in. Insulation Plates with
8-inch o.c. at 4-inch lap and 8-inch o.c. at three
(Optional) BP-
SBS-AA or
at max 24-inch spans
P
Base; Poi SMS Base; Ultra PolyFlintFast
y
Trufast 3" Metal Insulation
(3) equally spaced, staggered center rows
AA, SBS AA or
SBS-TA
-97.5
SMS Base; Yosemite
Plates with Trufast HD
w th T
SBS-TA
W-92
Min. 19/32-inch plywood
Glasbase; Flexiglas; Flintlastic
Base 20; Poly SMS Base; Ultra
Note 2
7-inch o.c. at 3-inch lap and 7-inch o.c. in three
BP -AA, SBS-
AA SBS-TA or
SBS-AA, SBS-
-105.0
at max 24-inch spans
Poly SMS Base; Yosemite
(3), equally spaced, staggered center rows
APP-TA
TA or APP-TA
W 93
Min.19/32-inch plywood
Flintlastic APP Base T
OMG 3 in. Round Metal Plates,with OMG
#14 HD or Dekfast Hex Plate with Dekfast
7-inch o.c. at 3-inch lap and 7-inch o.c. in three
APP-TA
APP-TA
-105.0
at max 24-inch spans
P
#14
(3), equally spaced, staggered center rows
Glasbase; Flexiglas; Flintlastic
Flintfast 3 in. Insulation Plates with
(Optional) BP-
W-94
Min. 15/32-inch plywood
Base Poly SMS Base; Ultra
FlintFast #12 or #14; Trufast 3" Metal
6-inch o.c. at 4-inch lap and 6-inch o.c, in four
AA, SBS-AA,
SBS-AA, SBS-
-127.5
P at max 24-inch spans
Poly SMS Base; Yosemite
M
Insulation Plates with DP or HD; OMG 3
(4), equally spaced, staggered center rows
SBS-TA or
TA or APP-TA
in. Round Metal Plates with OMG #14 HD
APP-TA
W-95
Min. 15/32-inch plywood
Flintlastic APP Base T
OMG 3 in. Round Metal Plates with OMG
6-inch o.c. at 4-inch lap and 6-inch o.c. in four
APP-TA
APP-TA
-127.5
at max 24-inch spans
#14 HD
(4). equally spaced, staggered center rows.
Glasbase; Flexiglas Base;
W-96
Min.15/32-inch plywood
Flintlastic Base 20; All Weather /
Flintfast 3 in. Insulation Plates with
8-inch o.c. at 4-inch lap and 8-inch o.c. in three
(Optional)
at max 24-inch spans
P
Empire Base; Yosemite Venting
FlintFast #12 or #14; Trufast 3" Metal
(3), equally spaced, staggered center rows
SBS-CAl
SBS-CA3
52.5
Base; Flintlastic Poly SMS Base;
Insulation Plates with DP or HD
Flintlastic Ultra Poly SMS Base
.
.-System . Deck' Roof CoVer;(Note;14)
No.. (Note 1) Pri Base. Ply cap.
mer MDP (Psf) .
W-97 Min. 15/32-inch plywood at max 24-inch spans FlintPrime or FlintPrime SA SBS-SA-H (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -112.5
W-98 Min. 1S/32-inch plywood at max 24-inch spans FlintPrime or FlintPrime SA SBS-SA (Optional) SBS-SA SBS-SA -127.5
NEMO ETC, LLC Evaluation Report 3520.03.04-1121 for FL2533-1120
Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 21:- 06/20/2018
Prepared by: Robert Nieminen, PE-59166 CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-S847 Appendix 1, Page 17 of 57
1