Contractor Florida Breeze
Mechanical License # CAC1814113
Building Plan #
County, Town, Municipality, Jurisdiction
Header Information
REQUIRED ATTACHMENTS'
Manual J1 Form (and supporting worksheets):
or MJ1AE Form" (and supporting worksheets):
OEM performance data (heating, cooling, blower):
Manual D Friction Rate Worksheet:
Duct distribution system sketch:
Home Address (Street or Lot#, Block, Subdivision)
Winter Design Conditions
Outdoor temperature
42
OF
Indoor temperature
70
OF
Total heat loss
31324
Btu/h
Summer Design Conditions
Outdoor temperature
95
OF
Indoor temperature
75
OF
Grains difference 53
L\ Gr @ 50
% Rh
Sensible heat gain
30174
Btu/h
Latent heat (gain
6112
Btu/h
Total heat gain
36286
Btu/h
Form
RPER 1.01
3 Mar 10
ATTACHED
Yes QX No ❑
Yes ❑ No XQ
Yes FX No ❑
Yes ❑ No QX
Yes ❑ No ❑X
Building
Orientation (Front door faces) South
North, East, West, South, Northeast, Northwest, Southqq, South
Number of bedrooms 4 <(, ' 7—��®
Conditioned floor area 1916 sa Ft
Number of occupants 5
Windows Roof
Eave overhang depth 2.7 Ft
Internal shade Eave
Blinds, drapes, etc Depth rWVindow
Number of skylights 0
-ating Equipment Data
Cooling Equipment Data
Equipment type
Heat pump
Equipment type
Heat
pump
Furnace. Heat pymp. Boiler, etc.
Air Conditioner. Heat pump, etc
Model
25HBC536A*030*
Model
25HBC536A*030*
Heating output capacity
34600 Btu/h
Sensible cooling capacity
30303
Btu/h
Heat pumps • capacity at winter design outdoor conditions
Latent cooling capacity
6�
BtU/h
Auxiliary heat output capacity
Btu/h
Total cooling capacity
37231
Btu/h
Design airflow
External Static Pressure (ESP)
Component Pressure Losses (CPL)
Available Static Pressure (ASP)
ASP = ESP - CPL
Contractor's Printed Name
Contractor's Signature
CFM
Longest supply duct:
IWC
Longest return duct:
IWC
Total Effective Length (TEL)
IWC
Friction Rate:
Friction Rate = (ASP x 100) - TEL
Blower Data
Heating CFM ___1341 CFM
Cooling CFM __1341 CFM
Ft Duct Materials Used (circle)
Trunk Duct: Duct board. Flex, Sheet metal,
Ft Lined sheet metal, Other (specify)
— Ft Branch Duct: Duct board, Flex, Sheet metal,
IWC Lined sheet metal, Other (specify)
Date 7/6/2018
' The AHJ shall have; the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions.
Y If abridged version of Manua( J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions.
Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program.
Air Conditioning Contractors of America
Manual S (Residential Equipment Selection)
Cooling Design Information
Outdoor Design Temp: 91 -F db
Summer
Outdoor Design Temp: F 43 °F db
I Winter
Indoor Design Temp: 75 °F db
50 %RH 63 °F wb
Manual J,Load Calculations
Total Load Sensible Latent SHR Heat Lass
36286 30 774 6112 0.832
I
OEM Information
Manufacturer.
Airflow Calculations
Design TD for Airflow
19
Design Sensible CFM
F 1444
Carrier I Furnace Model #: I I AFUE:
Coil or Fain -Coil Model #: FX4DN(B,F)037L Condenser Model #: 25HBC536A-030" I SEER: 15.0 HSPF: 8.50
(A) Manuti acturers cooling Nertormance Uata
Lower Return Air
Outdoor Temperature =
95 (F db)
Entering Coil Temperature = 75 (F db)
CFM (F wb)
Total BTUH
Sensible BTUH
Latent BTUH
SHR
Rated CFM @ Rated RA Temperature
65
F 39,370
30,600_j
F6.777
Rated CFM @ Design RA Temperature
1 1050 1 63
37.746
30,536
7,210
0.809
Rated CFM @ Rated RA Temperature
60
35,310
30,440
4,870
0.862
(B) Manutacturers cooling Hertormance uata
Higher Return Air Outdoor Temperature = 95 (F db)
Entering Coil Temperature = 75 (F db) CFM (F wb) Total BTUH Sensible BTUH Latent BTUH SHR
Rated CFM @ Rated RA Temperature 65 —38-4761 1 28,000 1 Fi-o.-47610.728
Rated CFM @ Design RA Temperature 1550 63 37,092 29,204 7,888 0.787
Rated CFM @ Rated RA Temperature 60 35,025 31,010 4,015 Fo.885
Manufacturer's Cooling Performance Data (Interpolated)
Design Return Air Outdoor Temperature = 95 (F db)
CFM (F wb) Total BTUH Sensible BTUH Latent BTUH SHR
29,487 7,744 0.792
Excess Latent Capacity Calculation + 816 816
Capacity @Design CFM / RA (F wb) F 1444 F 63 F 37,231 30,303 6,928 0.814
EAuipment Capacity as a % of Design 102.6017% 1 100.43% j 1-13—.350/6
i
i" Manufacturer's Heat Pump Data
I
Capacity
Capacity
Balance Supplemental
47 °F db
17 °F db
Point Heat Required
34,800
18,820
18.3 115.87
Manufacturers Furnace Data
Input Output Desired Calculated
Capacity Capacity AI FUE Temp.
� Ai
rflow
0
. I �F