LOAD CALCULATIONS
(Cooling&
Heating)
ACCA MANUAL N, Commercial Load Calculation
Address:
UNIT 7133
Designed by: KAMAL HALABI, RE, LEED AP
7133 US-1
PREMIER CONSULTING ENGINEERS, LLC
PORT ST. LUCIE, FL 34952
2799 NW 2nd Ave, H-20Z Bop Raton, FL
Tet (954) 675-6235 I Fax: (561) 892-7700
1. DESIGN CONDITIONS (COOLING)
ZONE WHOLE AREA
Time of Day "@3
P.M.
Daily Range
16
Latitude 26
Inside db
75 DEG.
RH
50%
Outside db 91 Coincident wb 78
Grains Diff
56.5
TEMP. DIFF
16
Enteringwb 67
2. SOLAR RADIATION HEAT GAIN THROUGH GLASS.
COOLING LOAD
Exposure
Sq. Ft
Solar Factor
Shading and/or
Sensible
Notes
glass factor
N
0 x
29
x
1 =
0
NE
0 x
42
x
1 =
0
E
404 x
64
x
0.8 =
20,685
SE
0 x
60
x
1 =
0
St
S
0 x
44
x
1 =
0
SW
0 x
89
x
1 =
0
W
0 x
88
x
1 =
0
NW
0 x
46
x
1 =
0
3. TRANSMISSION GAINS (ENVELOPE)
Equivalent or db
Exposure
Sq. Ft.
U Factor
Temp Diff
Glass all
404 x
1.04
x
16 =
6,723
Walls N
0 x
0.125
x
15 =
0
NE
0 x
0.125
x
26
0
E
101 x
0.125
x
36 =
455
SE
0 x
0.125
x
34 =
0
S
0 x
0.125
x
23 =
0
SW
0 x
0.125
x
19 =
0
W
505 x
0.125
x
17 =
1,073
NW
0 x
0.125
x
16 =
0
Doors
42 x
0.56
x
16 =
376
0 x
0
x
NEVI
ED F
R
Partitions
Floors
1574 x
0.087
x
x
6
C96DE COMPLIANCE
19
ClglRoof
x
3996 x
0.05
x
T50 LU
E COO
TY
RA Ceilingx
x
—
0
4. TRANSMISSION GAINS (OCCUPANTS, LIGHTS & OTHERS)
Latent
a. Occupants
Number
Sensible
Latent
5 x
255
=
1,275
69 x
210
=
14,490
5
x
255 =
1,275
69
x
190 =
13,110
b. Lights & Others
Watts
Incandescent Lights
x
3.4 =
0
Flourescent Lights
1840
x
4.1 =
7,544
Load
Usage
N.P.H.P.
Btuh
Factor
Factor
Motors
x
x
=
x
x
=
Sens
Lat
Usage
Appliances
16304
x
100% =
16,304
0
x
100% =
0
0
Other
BTUH
x
100% =
0
a e 1 OF 2
78,108
14,385
'CANNED
BY
.ude County
FILE COPY
w,
LOAD CALCULATIONS
(Cooling & Heating)
Sensible
Latent
continued .............. ZONE
WHOLE AREA
78,108
14,385
5.
INFILITRATION
Hieght = 10 It
Volume =
39960
cu It
AIR Changes Per Hour = 0.1
CFM 67 x db Temp Diff
CFM =
16 x
67
1.1
=
1,172
CFM 67 x Grains Diff
56.5 x
0.68
=
2,559
6.
SUBTOTAL COOLING LOAD FOR SPACE
79,280
16,944
7.
SUPPLY DUCT HEAT GAIN
Gain Factor 0.03 x Line 6 Sensible Gain
79,280
=
2,378
8.
ZONE DESIGN LOAD
81,659
16,944
This load is used to estimate the cooling CFM
Line 8 Sensible Supply
Temp. Diff.
Cooling CFM
11
81,659 / ( 1.1 x
18 )
=
4,124
9.
VENTILATION
(Outside air requirements)
1,200 CFM
CFM 1,200 x db Temp Diff
16 x
1.1
=
21,120
CFM 1,200 x Grains Diff
60 x
0.68
=
48,960
10.
TOTAL LOAD ON EQUIPMENT
168,682 BTUH
102,779
65,904
TOTAL LOAD ON EQUIPMENT =
14.1
TON
11.
DESIGN CONDITIONS (HEATING)
Inside db 72 DEG F.
Outside db
45
DEG F.
TEMP. DIFF
27 DEG F.
12.
TRANSMISSION LOSSES
HEATING LOAD
Exposure Sq. Ft.
U Factor
db Temp Diff
Windows all 404 x
0.29
x
27 =
3,163
Walls
N 0 x
0.125
x
27 =
0
NE 0 x
0.125
x
27 =
0
E 101 x
0.125
x
27 =
341
SE 0 x
0.125
x
27 =
0
S 0 x
0.125
x
27 =
0
SW 0 x
0.125
x
27 =
0
W 505 x
0.125
x
27 =
1,704
NW 0 x
0,125
x
27 =
0
Doors
0 42 x
0.56
x
27 =
635
0 0 x
0
x
27 =
0
Partitions x
x
27 =
0
Floors
x
x
27 =
0
Roof
x
x
27 =
0
Roof/Ceiling 3996 x
0.05
x
27 =
5,395
13.
INFILITRATION
Hieght = 10 ft
Volume =
39960
ou it
AIR Changes
Per Hour = 0.1
CFM =
67
CFM 66.6 x db Temp Diff
27 x
1.1
=
1,978
14.
SUBTOTAL COOLING LOAD FOR SPACE
13,216
15.
VENTILATION
INFILTRATION FROM STEP-13 ABOVE =
67 CFM OA REQ'D=
1,200 CFM
CFM 1,200 x db Temp Diff
27 x
1.1
=
35,640
16.
SUPPLY DUCT HEAT LOSS
Gain Factor 0.05 x Line 14 Sensible Gain
13,216
=
661
17.
TOTAL HEATING LOAD ON EQUIPMENT
49,517
page 2 OF 2
LOAD CALCULATIONS
(Cooling
& Heating)
ACCA MANUAL N, Commercial Load Calculation
Address:
UNIT 7133
Designed by:
KAMAL HALABI, RE, LEED AP
7133 US-1
PREMIER CONSULTING ENGINEERS, LLC
PORT ST. LUCIE, FL 34952
2799 NW 2nd Ave, H-202, Boca Raton, FL
Tel: (954) 675-6235 Fax: (561) 892-7700
1. DESIGN CONDITIONS (COOLING)
ZONE
WHOLE AREA
Time of Day
@3 p.m.
Daily Range
16
Latitude 26
Inside db
75 DEG.
RH
50%
Outside db
91 Coincident wb 78
Grains Diff
56.5
TEMP. DIFF
16
Entering wb 67
2. SOLAR RADIATION HEAT GAIN THROUGH GLASS.
COOLING LOAD
Exposure
Sq. Ft
Solar Factor
Shading and/or
Sensible
Notes
glass factor
N
0 x
29
x
1
=
0
NE
0 x
42
x
1
=
0
E
404 x
64
x
0.8
=
20,685
SE
0 x
60
x
1
=
0
S
0 x
44
x
1
=
0
SW
0 x
89
x
1
=
0
W
0 x
88
x
1
=
0
NW
0 x
46
x
1
=
0
3. TRANSMISSION GAINS (ENVELOPE)
Equivalent or db
Exposure
Sq. Ft
U Factor
Temp Diff
Glass all
404 x
1.04
x
16
=
6,723
Walls N
0 x
0.125
x
15
=
0
NE
0 x
0.125
x
26
0
E
101 x
0.125
x
36
=
455
SE
0 x
0.125
x
34
=
0
S
0 x
0.125
x
23
=
0
SW
0 x
0.125
x
19
=
0
W
505 x
0.125
x
17
=
1,073
NW
0 x
0.125
x
16
=
0
Doors
42 x
0.56
x
16
=
376
0 x
0
x
16
=
0
Partitions
1574 x
0.087
x
16
=
2,191
Floors
x
x
16
=
0
x
x
16
=
0
Clg/Roof
3996 x
0.05
x
35
=
6,993
RA Ceiling
x
x
=
0
4. TRANSMISSION GAINS (OCCUPANTS, LIGHTS & OTHERS)
Latent
a. Occupants
Number
Sensible
Latent
5 x
255
=
1,275
69 x
210
=
14,490
5
x
255
=
1,275
69
x
190
=
13,110
b. Lights & Others
Watts
Incandescent Lights
x
3.4
=
0
Flourescent Lights
1840
x
4,1
=
7,544
Load
Usage
N.P.H.P.
Btuh
Factor
Factor
Motors
x
x
=
x
x
=
Sens
Lat
Usage
Appliances
16304
x
100%
=
16,304
0
x
100%
=
0
0
Other
BTUH
x
100%
=
0
a e 1 OF 2
78,108
14,385
LOAD CALCULATIONS
(Cooling & Heating)
Sensible
Latent
continued .............. ZONE
WHOLE AREA
78,108
14,385
5.
INFILITRATION
Hieght = 10 ft
Volume =
39960
cu It
AIR Changes Per Hour = 0.1
CFM =
67
CFM 67 x db Temp Diff
16 x
1.1
=
1,172
CFM 67 x Grains Diff
56.5 x
0.68
=
2,559
6.
SUBTOTAL COOLING LOAD FOR SPACE
79,280
16,944
7.
SUPPLY DUCT HEAT GAIN
Gain Factor 0.03 x Line 6 Sensible Gain
79,280
=
2,378
8.
ZONE DESIGN LOAD
81,659
16,944
This load is used to estimate the cooling CFM
Line 8 Sensible Supply
Temp. Diff.
Cooling CFM
JJ
81,659 / ( 1.1 x
18 )
=
4,124
9.
VENTILATION
(Outside
air requirements)
1,200 CFM
CFM 1,200 x db Temp Diff
16 x
1.1
=
21,120
CFM 1,200 x Grains Diff
60 x
0.68
=1
48,960
10.
TOTAL LOAD ON EQUIPMENT
168,682
BTUH
102,779
65,904
TOTAL LOAD ON EQUIPMENT =
14.1
TON
11.
DESIGN CONDITIONS (HEATING)
Inside db 72 DEG F.
Outside db
45
DEG F.
TEMP. DIFF
27 DEG F.
12.
TRANSMISSION LOSSES
HEATING LOAD
Exposure Sq. Ft.
U Factor
db Temp Diff
Windows all 404 x
0.29
x
27 =
3,163
Walls
N 0 x
0.126
x
27 =
0
NE 0 x
0.125
x
27 =
0
E 101 x
0.125
x
27 =
341
SE 0 x
0.125
x
27 =
0
S 0 x
0.125
x
27 =
0
SW 0 x
0A25
x
27 =
0
W 505 x
0.125
x
27 =
1,704
NW 0 x
0.126
x
27 =
0
Doors
0 42 x
0.56
x
27 =
635
0 0 x
0
x
27 =
0
Partitions x
x
27 =
0
Floors
x
x
27 =
0
Roof
x
x
27 =
0
Roof/Ceiling 3996 x
0.05
x
27 =
5,395
13.
INFILITRATION
Hieght= 10 8
Volume =
39960
cult
AIR Changes Per Hour = 0.1
CFM =
67
CFM 66.6 x db Temp Diff
27 x
1.1
=
1,978
14.
SUBTOTAL COOLING LOAD FOR SPACE
13,216
15.
VENTILATION
INFILTRATION FROM STEP-13 ABOVE =
67 CFM CA REQ'D=
1,200 CFM
CFM 1,200 x db Temp Diff
27 x
1.1
=
35,640
16.
SUPPLY DUCT HEAT LOSS
Gain Factor 0.05 x Line 14 Sensible Gain
13,216
=
661
17.
TOTAL HEATING LOAD ON EQUIPMENT
49,517
page 2 OF 2
6
RECEIVED
MAR 19 Z019
LOAD CALCULATIO Permitting
t„utle County,
(Cooling & Heating
ACCA MANUAL N, Commercial Load Calculation -
Address:
UNIT 7133
7133 US-1
Designed by:
KAMAL HALAeI, RE, LEED A
T.
PREMIER CONSULTING EN LL�
PORT ST. LUCIE, FL 34952
00,
2799 NW end Ave, H-202, Boca Ra e0, ;` (
Tel: (954) 675.62351 Fax: (561) 892- 0.
1. DESIGN CONDITIONS (COOLING)
ZONE
WHOLE AREA �c�ol
Time of Day
@3 p.m.
Daily Range
16
Latitude 26
Inside db
75 DEG.
RH
50%
Outside db
91 Coincident wb 78
Grains Diff
56.5
TEMP. DIFF
16
Entering wb 67
2. SOLAR RADIATION HEAT GAIN THROUGH GLASS.
COOLING LOAD
Exposure
Sq. Ft.
Solar Factor
Shading and/or
Sensible
Notes
glass factor
N
0 x
29
x
1
=
0
NE
0 x
42
x
1
=
0
E
404 x
64
x
0.8
=
20,685
SE
0 x
60
x
1
=
0
S
0 x
44
x
1
=
0
SW
0 x
89
x
1
=
0
W
0 x
88
x
1
=
0
NW
0 x
46
x
1
=
0
3. TRANSMISSION GAINS (ENVELOPE)
Equivalent or db
Exposure
Sq. Ft.
U Factor
Temp Diff
Glass all
404 x
1.04
x
16
=
6,723
Walls N
0 x
0.125
x
15
=
0
NE
0 x
0.125
x
26
0
E
101 x
0.125
x
.36
=
455
SE
0 x
0.125
x
34
=
0
S
0 x
0.125
x
23
=
0
SW
0 x
0.125
x
19
=
0
W
505 x
0.125
x
17
=
1,073
NW
0 x
0.125
x
16
=
0
Doors
42 x
0.56
x
16
=
376
0 x
0
x
16
=
0
Partitions
1574 x
0.087
x
16
=
2,191
Floors
x
x
16
=
0
x
x
16
=
0
Clg/Roof
3996 x
0.05
x
35
=
6,993
RA Ceiling
x
x
=
0
4. TRANSMISSION GAINS (OCCUPANTS, LIGHTS & OTHERS)
Latent
a. Occupants
Number
Sensible
Latent
5 x
255
=
1,275
69 x
210
=
14,490
5
x
255
=
1,275
69
x
190
-
13,110
b. Lights & Others
Watts
Incandescent Lights
x
3.4
=
0
Flourescent Lights
1840
x
4.1
=
7,544
Load
Usage
N.P.H.P.
Btuh
Factor
Factor .
Motors
x
x
=
x
x
=
Appliances
Sens
16304
Lat
x
Usage
100%
=
' L 6, 0
0
®�
x
100%
=
0
Other
BTUH
x
100%
=
0
page 1 OF 2
78,108
14,385
SCANNED
BY
Lucie County
v
L
LOAD CALCULATIONS
Cooling & Heating
Sensible
Latent
continued .............. ZONE
WHOLE AREA
78,108
14,385
5.
INFILITRATION
Hieght = 10 ft
Volume =
39960
cu ft
AIR Changes Per Hour= 0.1
CFM =
67
CFM 67 x db Temp Diff
16 x
1.1
=
1,172
CFM 67 x Grains Diff
56.5 x
0.68
=
2,559
6.
SUBTOTAL COOLING LOAD FOR SPACE
79,280
16,944
7.
SUPPLY DUCT HEAT GAIN
Gain Factor 0.03 x Line 6 Sensible Gain
79,280
=
2,378
8.
ZONE DESIGN LOAD
81,659
16,944
This load is used to estimate the cooling CFM
Line 8 Sensible Supply
Temp. Diff.
Cooling CFM
11
81,659 / ( 1.1 x
18 )
=
4,124
9.
VENTILATION
(Outside
air requirements)
1,200 CFM
CFM 1,200 x db Temp Diff
16 x
1.1
=
21,120
CFM 1,200 x Grains Diff
60 x
0.68
=
48,960
10.
TOTAL LOAD ON EQUIPMENT
168,682 BTUH
102,779
65,904
TOTAL LOAD ON EQUIPMENT =
14.1
TON
11.
DESIGN CONDITIONS (HEATING)
Inside db 72 DEG F.
Outside db
45
DEG F.
TEMP. DIFF
27 DEG F.
12.
TRANSMISSION LOSSES
HEATING LOAD
Exposure Sq. Ft.
U Factor
db Temp Diff
Windows all 404 x
0.29
x
27 =
3,163
Walls
N 0 x
0.125
x
27 =
0
NE 0 x
0.125
x
27 =
0
E 101 x
0.125
x
27 =
341
SE 0 x
0.125
x
27 =
0
S 0 x
0.125
x
27 =
0
SW 0 x
0.125
x
27 =
0
W 505 x
0.125
x
27 =
1,704
NW 0 x
0.125
x
27 =
0
Doors
0 42 x
0.56
x
27 =
635
0 0 x
0
x
27 =
0
Partitions x
x
27 =
0
Floors
x
x
27 =
0
Roof
x
x
27 =
0
Roof/Ceiling 3996 x
0.05
x
27 =
5,395
13.
INFILITRATION
Hieght = 10 ft
Volume =
39960
cu ft
AIR Changes Per Hour = 0.1
CFM =
67
CFM 66.6 x db Temp Diff
27 x
1.1
=
1,978
14.
SUBTOTAL COOLING LOAD FOR SPACE
13,216
15.
VENTILATION
INFILTRATION FROM STEP-13 ABOVE =
67 CFM OA RE9D=
1,200 CFM
CFM 1,200 x db Temp Diff
27 x
1.1
=
35,640
16.
SUPPLY DUCT HEAT LOSS
Gain Factor 0.05 x Line 14 Sensible Gain
13,216
=
661
17.
TOTAL HEATING LOAD ON EQUIPMENT
49,517
page 2 OF 2