HomeMy WebLinkAboutRESIDENTIAL HVAC LOADS - 7-9-18Express 1828 Cali Left St Lucie
HVAC Load Calculations
for
Express Homes SCANNED
BY
Si Lucie County
Prepared By:
Kristin Kelly
Florida Breeze
6928 Vickie Circle
West Melbourne
3219518767
Monday, July 9, 2018
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
|
� '" oiect
'
Project Title:
Express 1828 Cali Left St Lucie
Designed By:
Kristin Kelly
Client Na�rne:
Express Homes
Company' Name:
Florida Breeze
I Companj' Representative:
Kristin Kelly
Compan� Address:
6928 Vickie Circle
�
West Melbourne
! Company Phone:
3219518767
|
�
Fo�P�ncef�ndo
'Building Orientation:
Front door faces South
i Daily Range:
Medium
� Latitude:
27
Oa0roea
!
25
ft.
. Altitude Factor:
0.999
|
Outdoor
Outdoor Outdoor Indoor Indoor Grains
Dry Bulb
Wet Bulb Rel.Hum Re8Hum Dry Bulb Difference
Winter: 42
39.4 n/a n/a 70 n/a
' Summer: 90
78 50% 5096 75 61
'
Total Building
/
Square ftl of Room Area:
1,828 Square ft. Per Ton: 689
|
/
� Total Heating Required .Including Ventilation Air: ...... .~. ~..., ~~.
' Total Sensible Gain:
25.467 Btuh 80 96
� Total Latent Gain:
6.390 8tuh 20 96
Total Cooling Required Including Ventilation Air: 31.858 8tuh 2.65 Tons (Based OnSensible +Latent)
Rhvac is an ACCA approved Manual J and Manual D computer program.
| Calculations are performed per ACCA Manual J 8th Edition, Version 2, and pCCA Manual D.
All
| �� buildingdted results are estimates as 'vary.' ~~~~^-oe�ctoon�thatmaet both se'~'~~and latent loads accordingtothe manufacturer's performance data ot
. your design conditions.
Monday, July 9, 2018.1:41PM
i t Rhvai.c Residential 8 ......
irgha Commeecial FtVAG Loatla, _ Elite S6 tware Ddyetvpment,-.tn
(� AtC Service Masters t LC Express 182€§ Gain ! eft St kiac€e
i p#m Say FL 329tl9 ,w Pags 31
_ - --_._ ,
} ; Miscellaneous Report
System 1� ,° � � ' C3utdo�r � :x Outdoor C%ttfdt�or , indoor � , Ir�dao� Gxafinys
I tlntitUata; ! �D+°�$!r let Bulgy: R:1 �Nurr► , RhHum:, CrS.t�fb Q�i#renc_e.
i Winter: 42 39.4 80% n/a 70 nla
Summer: 90 78 59% 50% 75 61.09
D
uctc�zin nests �" -
Main Trunk Runouts
{ Calculates _ Yes Yes
Use Schedule: Yes Yes
j Roughness Factor: 0.01000 0,01000
Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wg./100 ft.
Minimum elocity: 550 ft./min 450 ft./min
Maximums Velocity: 600 ft./min 750 ft.1min
Minimum Height: 0 in. 0 in.
Maximum yHeight:
0 in 0 in
Vuts A{3 ;i.'.7C' MC1 A ;. t sT^ "' T^'L ' 7 ', -�
Winter Summer
Infiltration Specified: 0.380 AC/hr 0.200 AC/hr
100 CFM 52 CFM
j Infiltration Actual 0.380 AC/hr 0.200 AC/hr
Above Grade Volume: X 15,721 Cu.ft. X 15,721 'Cu.ft.
5,974 Cu.ft./hr 3,144 Cu.ft./hr
X 0.0167 X 0.0167
Total Building Infiltration: 100 CFM 52 CFM
Total Building Ventilation: 0 CFM 0 CFM
System 1---
Infiltration & Ventilation Sensible Gain Multiplier. 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference)
Infiltrationj & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference)
Infiltrationj & Ventilation Sensible Loss Multiplier: 30.77 = (1.10 X 0.999 X 28.00 Winter Temp. Difference)
I Winter In Ptration Specified: 0.380 AC/hr (100 CFM), Construction: Average
Summer I pfiltration Specified 0.200 AC/hr (52 CFM) Construction Average
tau COaFc#0ireharrc fog Systems 1S , .{�
DUCt ,SurEe.Ce F111 t
Ty, Locatest �''_ e►I!9'._t , LeakageI`ulation ,4rea T Mi7D:
1 Supply Attic 16B 0.12 8 »mow �554 W -Nou
1 Return Attic 16B 0.12 8 474 No
C:\ ...IEXPRESS 1828 CALI LEFT LUCIE 2018.rh9
Monday, July 9, 2018, 1:41 PM
I
----------- ------- --------- - -
I R Residential 4t L!ghit"p66iMerc1a1.HVAQ Lbad§ Elite Software development, tnc.
A/G Service Masters, LLG Ova:b, C"
Express ' I Cali Left St Lucie
N1613a L�329091��
P,
age
------------- . . ..............
Duct Size Preview
Room or IS.. Mirdmum MaAm Rough.1 Designi SP Duct Ductj Htg Og I Act Duct
Duct Name i I Vebcly! Factor} I 1100i Lossi Vebctyl Length ri— 1 ci— ri—
System 1
SupptyRu icuts
Zone
1-1Nhol]ouse
OtherDucts in system I
I System 1 1
Heating Flow. 369
Cooling Flow 968
Built-in 450 750 0.01 0.1
Bult-In 550 600 0.01 0.1
547.5 369 M
547.5 369 FEW W8
CA ... \EXPRESS 1828 CALI LEFT LUCIE 2018.rh9
Monday, July 9, 2018, 1:41 PM
.. ........ ........
'
--'7--Mite So a'rd-Ddvejoonent Ilc;'
FRiF,q;3'� Ide�
[ A/C 6 MdsWtLLC Express 1828 Cali Left St Luble�,
- ---------
. .....
Pie 6
System I Summary Loads
area
ILD
bWl
a� Aik-
-m-0 lazing -Double pane low-e 0, 60) operable
124.8 1,400
0
2,288
-D
2,288
wind , metal frame no break, u-value 0.4, SHGC
0.31
2A-m-d: Glazing -Double pane low-e (e = 0.60), sliding
40.8 697
0
665
665
glass door, metal frame no break, u-value 0.61,
SHGQ 0.34
11 J: DoorWetal - Fiberglass Core
36.4 612
0
568
568
13AB-Ofcs: Wall -Block, no blanket or board insulation,
1236.1 6,334
0
3,936
3,936
filled core, siding finish
12C-0sw: Wall -Frame, R-13 insulation in 2 x 4 stud
313.1 798
0
612
612
cavityl, no board insulation, siding finish, wood studs
1 6B_ �30: Roof/Ceiling-Under Attic with Insulation on Attic
1828 1,638
0
2,925
2,925
Floor (also use for Knee Was and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asph6lt Shingles or Dark Metal, Tar and Gravel or
Membrane, R-30 insulation
22A-pm: Floor -Slab on grade, No edge insulation, no
199 6,575
0
0
0
insulation below floor, any floor cover, passive, heavy
dry or
light wet soil
Subtotals
for structure:
18,054
0
10,994
10,994
People:
5
1,000
1,150
2,150
Equipment:
850
4,000
4,850
Lighting:
0
0
0
Ductwork:
8,589
2,365
8,459
10,825
Infiltration:
Winter CFM: 100, Summer CFM: 52
3,064
2,175
864
3,039
Ventilatio6:
Winter CFM: 0, Summer CFM: 0
0
0
0
0
System 1
Load Totals.,
29,707
6,390
25,467
31,858
7
Supply CFM: 968
CFM Per Square ft.:
0.529
Square ft] of Room Area: 1,828
Square ft. Per Ton:
689
Volume (ft'): 15,721
Total Heating Required Including Ventilation Air: 29,707 Btuh 29.707 MBH
Total Sensible Gain: 25,467 Btuh 80 %
Total Latent Gain: 6,390 Btuh 20 %
Total Coo'ling Required Including Ventilation Air 31,858 Btuh 2.65 Tons (Based On Sensible + Latent)
@K-2
Rhvec is an ACCA approved Manual J and Manual D computer program.
Calculation
s are performed per ACCA Manual J Sth Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
I
your design conditions.
C:\...\EXP RESS 1828 CALI LEFT LUCIE 2018.rh9
Monday, July 9, 2018, 1:41 PM
- - - - _ - ----- - - - ------- ----------
Rhva Residential &.Light Commercial HVAC toads s Elite ,Software Development; Inc
R!C Service (Masters LCC Express 1$23 Caf'r Left St Eisele
j Palm BAY.'Ft 3�09
_ Page LL8 I
Equipment Data- System 1 ;
Cooling
System Type-
0 tdoor Model:
InZor Model:
j Tradename:
I Outdoor Manufacturer:
j Description:
AHRI Reference No.:
Capacity:
Efficiency:
Heating
Air Source Heat Pump
25HBC536A*030*
FX4DN(B,F)037L
CARRIER AIR CONDITIONING
CARRIER AIR CONDITIONING
Air Source Heat Pump
9155179
36130
15 SEER
System Type: Air Source Heat Pump
. Model: 25HBC536A*030*
Tradename: CARRIER AIR CONDITIONING
Manufacturer. CARRIER AIR CONDITIONING
I Description: Air Source Heat Pump
I Capacity: 34600
Efficiency: 8.5 HSPF
This system's equipment was selected in accordance with ACCA Manual S.
Manual S!equipment sizing data: SODB: 90F, SOWB: 78F, WODB: 42F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen. gain:
25,467 B�'uh, Lat. gain: 6,390 Btuh, Sen. loss: 29,707 Btuh, Entering clg. coil DB: 78.9F, Entering clg. coil WB: 64AF,
Entering htg. coil DB: 66.7F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. cig. airflow: 968 CFM, Req. htg. airflow: 369 CFM
C:1 ... \EXPRESS 1828 CALI LEFT LUCIE 2018.rh9 Monday, July 9, 2018, 1:41 PM
- — _._ ----- - - - -
_ .__._
-
Rh4ac Residential & Light Cornnier6al HVAC Loads
Elite Software Qevelopment, Inc.!
INC Serv3ce'Masters,, t.LC
Express 1828 Gali Left
St Luau
tAalm i3ay; FL 32909•
Page 7 ;
istern I Room Load Summary
_
in
Run' Run Clg
Clg
Nbri .'
Act
Ro�om Area Sens' t Htg
Duct. Duct Sens
La
Ctg
Sys -
F
No< N'alrte Y,F S, .,
l 3i
. ,
CFM
CFM'
---Zone
1---
.
1 W�ole
House 1,828 28,382 369
9-6 548 21,267
4,025
968
968
i D6ct
Latent
482
Return Duct 1,325
4,200
1,883
System 1 total 1,828 29,707 369
25,467
6,390
968
968
System 1 Main Trunk Size: 18 in.
Velocity: 548 ft./min
Loss per 100 ft.: 0.044 in.wg
�Goolinstern,Surr:m
�._
I r '`" Coaling Serslb(eli.atent SensEble Latent Total;;
p,
t Tans .,, Y SAY' Buh
,t � �,r.L,.xv..._,' ?. ,..�.M1i....,..`:.a:v.
13t9 Btuh};
:....'_.....,...._...,
._.x ...-,»:i•..:. ......0 ..._...:3.-Ws. ._.•x....�.�:;L,z—.w. ._.._.ww«t..
Net Required: 2.65 �80% / 20% 25,467
�....c,._s...11_._._..a......h`.
6,390 31,858
Actual: 3.01 80% / 20% 28,919
7,211 36,130
guipment Data
. .
— T
Pleating System
Cooling System
Type: Air Source Heat Pump
Air Source Heat Pump
Model: 25HBC536A*030*
25HBC536A*030*
Indoor Model:
FX4DN(B,F)037L
Brand: � CARRIER AIR CONDITIONING
CARRIER AIR CONDITIONING
Description: Air Source Heat Pump
Air Source Heat Pump
j Efficiency: 8.5 HSPF
15 SEER
j Sound: 1 0
Capacity: 34,600 Btuh
0
36,130 Btuh
Sensible, Capacity: n/a
28,919 Btuh
i Latent Capacity: n/a
7,211 Btuh
AHRI Reference No.: n/a
9155179
i
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 90F, SOWB: 78F, WODB: 42F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen. gain:
25,467 Btuh, Lat. gain: 6,390 Btuh, Sen. loss: 29,707 Btuh, Entering clg. coil DB:
78.9F, Entering clg. coil WB: 64.4F,
Entering
htg. coil DB: 66.7F, Clg. coil TD: 20F, Htg, coil TD: 70F, Req, clg, airflow:
968 CFM, Req. htg. airflow: 369 CFM
i
I
C:\...\EXPIRESS 1828 CALI LEFT LUCIE 2018.rh9 Monday, July 9, 2018, 1:41 PM
arcatitmca�oaa�A�r
Contractor Florida Breeze
Mechanical L cense # CAC1814113
Building Plan #
Home Address
County, Town, Municipality, Jurisdiction
Header Information
REQUIRED ATTACHMENTS'
Manual A Form (and supporting worksheets):
or MAAE Forme (and supporting worksheets):
OEM performance data (treating, cooling, blower):
Manual D Friction Rate Worksheet:
Duct distribution system sketch:
(Street or Lot#, Block, Subdivision)
Winter Design Conditions
Outdoor
temperature
42
OF
Indoor temperature
70
OF
Total hel
t loss
29707
Btu/h
Summer
Design Conditions
Outdoor
temperature
90
OF
Indoor temperature
75
OF
Grains difference 61
A Gr @ 50
% Rh
Sensible heat gain
25467
Btu/h
Latent h i at gain
6390
Bluth
Total heat gain
31858
Btu/h
Equipment type Heat pump
Fumace. Heat pump, Boiler, etc.
Model 25HBC536A" 030*
Heating output capacity 34600 Btu/h
Heat pumps-16pacity et winter design outdoor conditions
Auxiliary heat output capacity Stu/h
Form
RIPER 1.01
8 Mar 10
ATTACHED
Yes Q No ❑
Yes ❑ No
Yes ❑X No ❑
Yes ❑ No FX-
Yes ❑ No 0
Building Construction Information
Building
Orientation (Front door faces)
South
North, East, West, South, Northeast, Northwest, Southeast, Southwest
Number of bedrooms
4
Conditioned floor area
1 828 Sq Ft
Number of occupants
.5
Windows
Roof
Eave overhang depth
2.7 Ft
Internal shade
Eave
Blinds, drapes, etc
Depth Window
Number of skylights
Cooling Eauioment Data
Equipment type
Heat pump
Air conditioner. Heat pump, eta
Model
25HBC536A*030*
Sensible cooling capacity
28919 Btulh
Latent cooling capacity
7211 Btu/h
Total cooling capacity
36130 Btu/h
Design airflow
CFM
Longest supply duct:
External Static Pressure (ESP)
IVVC
Longest return duct:
Component Pressure Losses (CPL)
IWC
Total Effective Length (TEL)
Available Static Pressure (ASP).
IWC
Friction Rate:
ASP = ESP • CPL
Friction Rate = (ASP k 100) +TEL
Contractor's Printed Name Kristin,Kelly
Contractor's Slanature c t./°t-1_1�
Blower Data
Heating CFM 2"�y CFM
Cooling CFM -_-_^ CFM
Ft Duct Materials Used (circle)
Trunk Duct: Duct board, Flex, Sheet metal,
Ft Lined sheet metal, Other (specify)
Ft Branch Duct: Duct board, Flex, Sheet metal,
IWC Lined sheet metal, Other (specify)
Date 7/Q/9f11 R
t ne Atli snatt nave the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions, .
' if abridged versiorj of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions.
Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program.
,.Air Cgnditioning Contractors of America
Manual S (Residential Equipment Selection)
Project
Name:E
City:
Altitude: r ! Altitude Adjustment:-1 AO
Manual JILoad Calculations
Cooling Design Information
Outdoor Design Temp: 91 °F db Summer
Outdoor Design Temp: 43 °F db [Winter
Indoor Design Temp] 75 °F db F 54 %RM 63 °F wb
Total Load Sensible Latent SHR Heat Loss
31858 r7639711.0.799
OEM Information
Airflow Calculations
Design TD for Airflow
r 19,
Design Sensible CFM
F12191
Carrier I • Furnace Model #:I I AFUE:�
Coil or F i n-Coil Model #: FX4DN(B,F)037L Condenser Model #: 25HBC536A'030-
SEER: 15A HSPF: 8.50
(A) Manufacturer's
Cooling Performance Data
Lower
Return Air
Outdoor
Temperature =
95 (F db)
Entering Coil Temperature = 75 (F db) CFM
(F wb)
Total BTUH
Sensible BTUH
Latent BTUH
SHR
Rated CFM @ Rated RA Temperature
65
38,370
25,640
12,770
0.6672
Rated CFM @ Design RA Temperature 1050
63
35,946
27,536
8,410
0.766
Rated CFM @ Rated RA Temperature
F 32,310
30,440
1,870
0.9421
(8) Manufacturer's
Cooling Performance Data
Higher
Retum Air
Outdoor Temperature
F 95 (F db)
Entering Coil Temperature = 75 (F db) CFM
(F wb)
Total BTUH
Sensible BTUH
Latent BTUH
SHR
Rated CFM @ Rated RA Temperature
fi5
377476
28,000
9,470
0.7473
Rated CFM @Design RA Temperature 1550
63
36,492
29,204
7,288
0.8f}03
Rated CFM @Rated RA Temperature
60
35,025
31,010
4,015
4.8854
Manufacturer's
Cooling Performance Data (Interpolated)
Design
Return Air
Outdoor Temperature = 95 (F db)
CFM
(F wb)
Total BTUH
Sensible BTUH
Latent BTUH
SHR
28,098
F77932
0,7777
Excess Latent Capacity Calculation
+ 820
- 825
Capacity @ Design CFM ! RA (F wb) 1218.5
63
m7i30
28,919
77241
0.800 71
Equipment Capacity as a % of Design
113 4-1
113.55%
112- 84°fa
i
Heat Pump Data
Manufactdrer's Furnace Data
Capacity Capacity Balance Supplemental
@ 47 °F db @ 17 °F db Point Heat Required
34,800 18,820 1 -15.87
Input Output
Desired Calculated