Originally Issued: 10/20/2017
HUBER ENGINEERED WOODS, LLC
ZIP SYSTEM'' WALL SHEATHING
CSI Sections:
06 i6 00 Sheathing
07 25 00 Water Resistive Barriers/Weather Barriers
07 27 00 Air Barriers
1.0 RECOGNITION
Huber Engineered Woods ZIP System' Wall Sheathing
described in this report has been evaluated .for water
resistance requirements in accordance with Section 2510.6 of
the IBC and Section R703.7.3 of the IRC, and air leakage in
accordance with Sections C402.5 and R402.5 of •the 2015
IECC or Sections C402.4 and R402,4 of the 2012 IECC, as
applicable, for compliance with the following codes:
• 2015 and 2012 International Building Code' (IBC)
• 2015 and 2012 International Residential Code'
(IRC)
• 2015 and 2012 International Energy Conservation
Code'(IECC)
• 2017 and 2014 Florida Building Code, Building and
Florida Building Code, Residential (FBC, Building
and FBC, Residential) -- see attached supplement
2.0 LIMITATIONS
Use of the ZIP System' Wall Sheathing recognized in this
report is subject to the following limitations:
2.1 The ZIP System1e Wall Sheathing panels shall be installed
in accordance with the applicable code, the manufacturer's
published installation instructions, and this report. Where
there is a conflict, the most restrictive requirements shall
govern.
2.2 The ZIP System' Wall Sheathing panels are limited to
code approved structural use for wood structural panels with
either a 24/16, 32/16, or 40120 span rating, depending upon
the panels thicknesses of V 16, IJ2, and 5?8 inch (11.1, 12.7
and 15.9 mm).
2.3 ZIP System' Wall Sheathing panels are manufactured
by Huber Engineered Woods, LLC in Crystal Hill, Virginia;
Commerce, Georgia; Broken Bow, Oklahoma; Easton,
Maine; Shawinigan, QC, under a quality control program
with inspections by PFS TECO (QUA 1680).
3.0 PRODUCT USE
3.1 General: ZIP System' Wall Sheathing panels are used
as wall sheathing in accordance with Section 2303.1.5 of the
Valid Through: 10/31/2018
2015 IBC, Section R602.1.8 of the 2015 IRC, and the water -
resistive barrier required in accordance with Section 2510.6
and Chapter 14 of the IBC and Chapter 7 of the IRC. The
sheathing is recognized for use in Type V construction in
the IBC and buildings and structures constructed to the IRC,
as applicable. SCANNED
3.2 Installadon: BY
St Lucie County
3.2.1 Installation General: Installation of the ZIP System'
Wall Sheathing panels shall comply with the applicable code,
this report and the manufacturer's published installation
instructions. The installation instructions shall be available
at the jobsite during installation. If there are any conflicts
between the manufacturer's published instructions and this
report, the more stringent requirements shall govern.
3.2.2 Installadon of Sheathing Panel: ZIP System" Wall
Sheathing shall be attached to framing in accordance with
the applicable codes for PS-2 wood structural panels,
Tongue -and -groove and machined panel edges are designed
to provide the correct gap size at the panel edges during
installation. Square -edged panels shall be spaced 1/8-inch
(3.2 mm).
The panel shall be installed with the laminated moisture
barrier facing to the exterior. All ZIP System'' Wall
Sheathing seams shall be sealed with ZIP System' Tape.
Panel surfaces shall be dry and free from any signi ficant
presence of particles, sawdust or other debris or protrusions
prior to installation of the tape. The ZIP System' Tape
edges shall be sealed and the tape is to be centered within
+/- !h inch (12.7 mm) of all panel edge seam centers. The
tape shall extend a minimum of I inch (25.4 mm) past the
panel edge T joint intersections. The tape shall be adhered
to the ZIP System' Wall Sheathing. Wrinkles in the ZIP
System' seam tape are acceptable unless they create a leak
path to the panel seam.
All penetrations of the ZIP System1D Wall Sheathing surface
overlay such as cracking, openings, etc., caused by handling
or construction work, shall be covered with ZIP System'
Tape.
3.2.3 Installation of Second Water -Resistive Barrier
(WRB) Layer: In the two -layer water -resistive barrier
systems (WRB) required by IBC Section 2510.6 or IRC
Section R703.7.3, ZIP System' Wall Sheathing performs as
the first WRB layer. A second WRB layer with performance
equivalent to a layer of ASTM 2556, Typel shall be provided
over the ZIP System' for construction under the 2015 IBC.
A second WRB layer with performance equivalent to a layer
of Grade D paper shall be provided over the ZIP System14 for
construction under the 2012 IBC and the 2015 and 2012 IRC.
The product describod in this Uniram Evaluation Sam-ce (UES) Report has been evaluated as an alternative material, design or method of construction in order to satisfy and campfy w thC�eb
the intent of the provision ofthecode. as notedinthisreport.andforatleastequivalencetothatproscabedinthecodainquality stmngth.oNocbveness.6mmsislanco durabdilyandsolely
as applicable, in accordance with ISC Section f04 It Thrs document shall only be reproduced in its entirety
Copyright m 2017 by International Association of Plumbing and Machantat Offidals. All rights reserved. Printed in the United States. Ph., f-877-71ESRPT - Pax 909.472 4171
web. www.unilam4s.org - 4755 East Philadelphia Street. Ontario. Catiromfo 9176f-2816- USA
Pagel of 4
It I
ups
Originally Issued: 10/20/2017
3.3 Air Permeability: The air barrier assembly includes ZIP
System` Wall Sheathing Panels installed with 2x4 wood
studs spaced at a maximum of 24 inches on center and
sheathed, with a minimum 7116-inch thick ZIP System'
Sheathing panels fastened with 2-inch 6d common nails
spaced at 6 inches on center in the perimeter and 12 inches
on center in the field. The joints between the panels shall be
sealed with ZIP System' Tape. The air barrier assembly has
an air leakage rate of infiltration of 0.006 chn/ft2 (0.0294
Us.-m'-) ,and exfiltration of 0.0061'CfmW (0.0305 Us.=m=)
under a pressure differential of 0.3-inch water gauge (75 Pa)
when tested to ASTM E2357. The assembly meets the
requirements for an air barrier assembly in Section C402.5
and R402.4 of the 2015 IECC and Section C402.4 and R402.4
of the 2012 IECC.
4.0 PRODUCT DESCRIPTION
4.1 ZIP System' Wall Sheathing Panels. The ZIP System"
wall sheathing panels are wood structural panels having a
laminated moisture barrier surface on one side of the panel.
The panels are installed with ZIP System seam scaling tape,
which allows the systems. to be used to meet the water -
resistive barrier requirements in Chapter 14 and Section
2510.6 of the 2015 IBC. The wood structural panel substrate
complies with US DOC PS-2. The moisture barrier surface
on the wood structural panel consist of a medium density
phenolic impregnated overlay. The standard -size panels are
nominally 4 feet by 8 feet (1219 mm by 2438 mm). Panels
longer than 8 feet (2438 mm) in length are also produced. The
panels are available in thicknesses of 7116, 112, and 518 inch
(l 1.1,12.7 and 15.9 mm) with either a self -spacing or square
edge profile and with a tongue -and -groove edge profile also
available,for the 518-inch thick panels.
4.2 ZIP System' Tape. The ZIP System' Tape is a self -
adhering sheet -type membrane consisting of acrylic adhesive
laminated to a polyolefin backing.. The tape is 0.012 inch (0.3
mm) thick with a minimum width of3.75 inches (95 mm) and
comes in rolls of varying lengths.
5.0 IDENTIFICATION
Huber Engineered Woods Zip System' Wall Sheathing is
identified by Huber Engineered Wood's name and
trademark, product name and evaluation report number
(ER 544). The identification includes the IAPMO Uniform
Evaluation Service Mark of Conformity. Either Mark of
Conformity may be used as shown below:
IApMo VES
ES
0O or TM
IAPMO UES ER-544
Valid Through: 10/31/2018
6.0 SUBSTANTIATING DATA
6.1 ICC-ES Acceptance Criteria for Water -Resistive
Membranes Factory -Bonded to Wood -based structural
Sheathing, Used as Water Resistive Barriers (AC310), dated
May 2008, editorially revised August 2015
6.2 Reports of Hygrothermal Analyses.
6.3 Report of testing to ASTM E2357.
7.0 CONTACT INFORMATION
HUBER ENGINEERED WOODS, LLC
10925 David Taylor Drive, Suite 300
Charlotte, North Carolina 28262
(800) 933-9220
www.huberwood.ctnn
8.0 STATEMENT OF RECOGNITION
This evaluation report describes the results of research
carried out by IAPMO Uniform Evaluation Service on Huber
Engineered Woods Zip System' Wall Sheathing to assess
conformance to the codes shown in Section 1.0 of this report,
and serves as documentation of the product certification.
Page 2 of 4
Brian Gerber, P.E., S.E.
Vice President, Technical Operations
Unifo
r
m Evaluation Service
Richard Beck, PE, CBO, MCP
Vice President, Uniform Evaluation Service
e -�)—
GP Russ Chan y
CEO, The IAPMO Group
For additional information about this evaluation report please visit
ua w.uniform-es.ore or email us at infMi uniform-cs.ore
UES'
rµ Originally Issued: 10120/2017
'G
Valid Through: 10/31/2018
FIGURE 1
ZIP SYSTEM"''SHEATING FOR USE WITH EXTERIOR PLASTER
Page 3 of 4
i
W
j
Originally Issued: 10/20/2017
i
FLORIDA SUPPLEMENT
HUBERI ENGINEERED WOODS, LLC
ZIP SYSTEM WALL SHEATHING
CSI Sections:
06 16 00 Sheathing
07 25 00 Water Resistive Barriers/Weather Barriers
07 27 00 Air Barriers
1.0 RECOGNITION
Huber Engineered Woods ZIP System' Wall Sheathing
described in IAPMO UES Evaluation Report ER-544 is a
satisfactory alternative to the sheathing prescribed in the
following codes:
• 20117 and 2014 Florida Building Code, Building (FBC,
Building)
• 2011 and 2014 Florida Building Code, Residential
(FBC, Residential)
• 20117 and 2014 Florida Building Code, Energy (FBC,
Energy)
2.0 LIMITATIONS
2.1 Installation shall be in accordance with the 2015 or 2012
Intemationat Building Code and the 2015 or 2012
International Residential Code, as applicable, as noted in ER-
544, and the manufacturer's published installation
instructions.
2.2 Use of the ZIP System' Wall Sheathing for compliance
with the high -velocity hurricane zone provisions of the FBC,
Building and FBC, Residential has not been evaluated and is
outside the scope of this evaluation report.
2.3 Flashing shall comply with Section 1405.4 of the FBC,
Building and Section 703A of the 2017 FBC, Residential and
703.8 of the 2014 FBC, Residential, as applicable.
2.4 For products falling under Florida Rule 61020-3.008,
verification is required that the report holder's quality
assurance program is audited by a quality assurance entity,
approved by the Florida Building Commission (or the
building official when the report holder does not possess an
approval , by the Commission), to provide oversight and
determine that the products are being manufactured as
described, in this evaluation report to establish continual
product performance.
Valid Through: 10131/2018