HomeMy WebLinkAboutRESIDENTIAL HVAC LOADS - ELITE SOFTWAREExpress 1828 Cali Right St Lucie 2019
HVAC Load Calculations
for
Express Homes
ED
. • . , .. St LUCID County,
Prepared By:
Kristin Kelly
Florida Breeze
6928 Vickie Circle
West Melbourne
3219518767
Monday, January 14, 2019
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations ale performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
i
Designed By:
Kristin Kelly
Project Date:
Friday, January 11, 2019
Client Name:
Express Homes
Company Name:
Florida Breeze
Company Representative:
Kristin Kelly
Company Address:
6928 Vickie Circle
Company City:
West Melbourne
Company Phone:
3219518767
Designta"
Reference City:
St Lucie, Florida
Building Orientation:
Front door faces South
Daily Temperature Range:
Medium
Latitude:
27 Degrees
Elevation:
25 ft.
Altitude Factor:..
0.999
Outdoor Outdoor Outdoor
Indoor
Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum
Dry Bulb Difference
Winter:
42 39.4 n/a
n/a
70 n/a
Summer:
95 78 47%
50%
75 53
CCGk iufs
Total Building Supply CFM:
988
CFM Per Square ft.: 0.541
Square ft. of , oom Area:
1,828
Square ft.
Per Ton: 689
Volume (ft'):
15,721
l3u�je3�nL�a� ..a
Total Heating Required Including Ventilation Air. 29,568
Btuh
29.568 MBH
Total Sensible Gain:
26,355
Btuh
83 %
Total Latent Gain:
5,478
Btuh
17 %
Total Cooling Required Including Ventilation Air: 31,833
Btuh
2.65 Tons (Based On Sensible + Latent)
vac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to seect a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
i
C:1... \Express 1828 Cali Right St Lucie 2019.rh9
I
E
Monday, January 14, 2019, 3:48 PM
I
Rh ac Residential.8, Lq, Gbmmeicia.t t#VAG "odds Eli Soffiware De etopmerat,
Florida Breeze Exp 1828r°Rrght St'Lucie,20 i 8
ess
Wes(Velbou ex Ft., 32904
Miscellaheous Report
,
Oe mart
putaa�
t DI ere
Winter: 42
39.4
80% n/a 70 n/a
Summer: 95
78
47% 50% 75 52.90
r DuG%Sa,�z, i�p to
Main Trunk
Runouts
Calculate: Yes
Yes =
Use Schedule: Yes
Yes '
Roughness Factor: 0.01000
0.01000
Pressure Drop:. 0.1000 in.wg./100
ft.
in.wg./l00 ft.
Minimum Velocity: 550 ft:/min
.0.1000
450 ft./min
Maximum Velocity: 600 ft./min
750 ft./min
Minimum HdIight: 0 in.
0 in.
Maximum Height: 0 in,
0 in.
Clutsl.e%r C)afa
-Winter
_
Sdrnnjer
Infiltration Specified: -0.380
AC/hr
0.200 AC/hr
100
CFM
52 CFM
Infiltration Actual: 0.380
AC/hr
0.200 AC/hr
Above Grade Volume: X 15,721
Cu.ft.
X 15,721 Cu.ft.
5,974
Cu.ft./hr
3,144 Cu.ft./hr
X 0.0167
X 0.0167
Total Building Infiltration: 100
CFM
52 CFM
Total Building Ventilation: 0
i
CFM
0 CFM
---System 1---
Infiltration & Ventilation Sensible Gain Multiplier:
21.98
= (1.10 X 0.999 X 20.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier:
35.94
= (0.68 X 0.999 X 52.90 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier:
30.77
= (1.10 X 0.999 X 28.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.380 AC/hr (100 CFM), Construction: Average
Summer Infiltration Specified: 0.200 AC/hr (52 CFM), Construction: Average
1 Return
Attic
C:1... \Express 1828 Cali Right St Lucie 2019.rh9
i
0.12 8 554 No
b:12 8 474 No
Y
1
t
Monday, January 14, 2019, 3:48 PM
' ' Rhvac; jResidentIaf�& Light Gomme c[al VAG Loads
Florida• Breeze
Elite Software pa efopmant;�lncR,
Exp ess 1'8ix8 Cali fight St l ucie J
,
;West Melbaurite Fi: ,32:i ,
age4- I
.w-+�.._...-------------
—
1�
Room or
DuctName
Y�
hAinlmum
Veb
Ma>�micn
Vebbty
Rough,
Factor
kDesi�
L/100
SP
Lass
Duct
Veto
Duct
I errgfh
F Ffo Fl ��
ySimDLIct
{
i
--�
System 1
Supply Runouts
__
Zone 1
1-Whole House BUIWn 450
750 0,01
0.1
559.3; 367 988 9-6
OtherDuds in Systeml
i
SupplyMainTank Built In 550
600 0.01
0.11
559.3; 367 988 18
Summery
System 1-
Heating Flow.' • 367
Cooling Flaw: 988
CA ...\Express �1828 Cali Right St Lucie 2019.rh9
Monday, January 14, 2019, 3:48.PM
2A-v-o: Glazing -Double pane low-e (e = 0.60), operable
window, vinyl frame, U-value 0.35, SHGC 0.29
2A-v-d: Glazing -Double pane low-e (e = 0.60), sliding
glass door, vinyl frame, U-value 0,61, SHGC 0.34
2B-v-o: Glazing -Double pane low-e (e = 0;60), fixed sash,
vinyl frame, 6-value 0.35, SHGC 0.29
11 J: Door -Metal - Fiberglass Core, U-value 0.6
11 D: Door -Wood - Solid Core, U-value 0.39
13AB-Ofcs: Wall -Block, no blanket or board insulation,
. filled core', siding finish, U-value 0.183
12C-Osw: Wall -Frame, R-13 insulation in 2 x 4 stud
cavity, no board insulation, siding finish, wood studs,
U-value 0.091
16B-30: Roof/Ceiling-Under Attic with Insulation on Attic
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Singles or Dark Metal, Tar and Gravel or
Membrane, R-30 insulation, U-value 0.032
22A-pm: Floor-Siab on grade, No edge insulation, no
insulation, below floor, any floor cover, passive, heavy
dry or light wet soil, U-value 1.18
Subtotals forjstructure:
People: I
Equipment:
Lighting:
Ductwork:
Infiltration: Winter CFM: 100, Summer CFM: 52
Ventilation: Winter CFM: 0, Summer CFM: 0
System 1 Load Totals:
Supply CFM: 988
Square ft. of Room Area: 1,828
Volume (ft3): ' 15,721
•40.8
2.5
. 20.4
19
1237.1
317.1
ve prn�nf,.lnc
htjSt ztucie 2019
Page 5,
1,224
0
2,312
2,312
697
0
790
790
24
0
33
33
343
0
379
379
208
0
230
230
6,340
0
5,072
5,072
808
0
765
765 ,
1828 1,638
200 6,608
17,890
5
0
8,614
3,064
0
29,568
CFM Per Square ft.
Square ft. Per Ton:
0 3,217
0 0
0
1,000
500
2,095
1,883
0
5,478
12,798
1,150
2,100
0
9,155
1,152
0
26,355
3,217
X
12,798
2,150
2,600
0
11,250
3,035
0
31,833
Total Heating Required Including Ventilation Air:- 29,568 Btuh '29.568 MBH
Total Sensible Gain: 26,355 Btuh 83 %
Total Latent Gain: 5,478 Btuh 17 %
Total Cooling, Required Including Ventilation Air: 31,833 Btuh 2.65 Tons (Based On Sensible + Latent)
Hhvac Is an AUC:A approves Manual u, U and 5 computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed 'results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\ ...\Express 1828 Cali Right St Lucie 2019.rh9
Monday, January 14, 2019, 3:48 PM
Rh ' Residential "'-A1Lja9hfR
Bredz6'
West Melbourne FL 32 04
,4'qqip nt-Data,-
Cooling
Systeri,i Type:
Outdoor Model:
Indoor,Model:
Manufacturer:
on:
Air Source Heat Pump
R4H436(A,G)KC"
FXM4X36**AL
14 SEER R SERIES R410A HP
COMFORTMAKER-
Air Source Heat Pump
AHRI Reference No;:
10142182
Capacity:,
34,327
Efficiency:
Efficien'
15 SEER
Heating
System Type:
Air Source Heat Pump
Model:1
R4H436(A,G)KC*
Traderiame:
14 SEER R SERIES R410A HP
Manufacturer:
COMFORTMAKER.
Description:
Air Source Heat Pump
Capacity:
33,800
Efficiency.:.
8.5 HSPF
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment
sizing data:
SODS: 95F, SOWB: 78F, WODb: 42F, SIDB: 75F, SIRH:'50%, WIDB: 70F, Sen. gain:
26,355 Btuh,
Lat. gain: 5,478 Btuh,
Sen, loss-, 29,568 Btuh, Entering cIg. coil DB: 79.3F, Entering c1g, coil WB: 64F,
Entering htg.
coil DB: 66.7F, CIg.
I
coil TD: 20F, Htg. coil TD: 70F, Req. c1g. airflow; 988 CFM, Req. htg. airflow: 367 CFM
C:\ ... \ExpressI1828 Cali Right St Lucie 2019.rh9
Monday, January 14, 2019, 3:48 PM
1 Whole House 1,828
.28,240 367
Duct Lal tent
Returnbu6t
1,328
I total 1,828 Systenl . . .
.29,568 367
System I Mah Trunk Size:
18 In.
Velocity.
.559 ft./min
Loss per 1001 ft.:
0.045 in.wg
Actual:
2.86 - - , 82%/18%
9-6 659 21,722 3,383
454
4,633 1,641
26,13551, 5,478
ONEWOM
=m
Type:
Air Source Heat Pump
Air Source Heat Pump
Model-
R4H436(A,G)KC-
R4H436(A,G)KC*
Indoor Modelt
FXM4X36**AL
Brand.
14 SEER R SERIES R410A HP
14 SEER R SERIES R410A HP
Description:
Air Source Heat Pump
Air Source Heat Pump
Efficiency:
8.5 HSPF
15 SEER
Sound-,
0
0
Capacity:
33,800 Btuh
34,327 Btuh
Sensible Capacity:
n/a
28,198 Btuh
Latent Capa ity:
n/a
6,129 Stuh
AHRI Referenice No.:
n/a
10142182
This systern' s equipment was selected in accordance with ACCA Manual S.
'
Manual S equipment sizing data:
SODS: 95F, SOWB: 78F, WODB: 42F, SIDE: 75F, SIRH: 50%, WIDB: 70F, Sen. gain:
26,355 Btuh, ILat. gain: 5,478 Btuh, Sen. loss: 29,568 Btuh, Entering c1g. coil DB: 79.317, Entering c1g. coil WB., 64F,
Entering htg. coil DB: 66,717, CIg.
coil TD: 20F, Htg. coil TD: 70F, Req. c1g. airflow: 988 CFM, Req. htg. airflow: 367 CFM
C:\ ... \Expressil 828 Cali Right St Lucie 2019. rh9
Monday, January 14, 2019, 3:48 PM
411
County, Town, Municipality, Jurisdiction
Header Information
Contractor Florida Breeze REQUIRED ATTACHMENTS'
Manual A Form (and supporting worksheets):
Mechanical License # CAC1814113 or MJ1AE Farm= (and supporting worksheets):
OEM performance data (heating, cooling, blower):
Building Plan # Manual D Friction Rate Worksheet:
Duct distribution system sketch:
Home Address (Sheet or Lot#, Block, Subdivision)
Form
RPER 1.01
8 Mar 10
ATTACHED
Yes XX No ❑
Yes ❑ No ZX
Yes [X No ❑
Yes ❑ No pX
Yes f-1 No []X
Winter Design Conditions
Building
Outdoor temperature
42=
OF
Orientation (Front door faces)'
Soutt,
Indoor temperiature
70'
of
North, East, West, South, Northeast, Northwest, Southeast, Southwest
Total heat lost
29568
Btu/h
Number of bedrooms
4
Summer Design Conditions
'Gonditioned floor area
1828 Sq Ft '
Outdoor temperature
95
OF
Number of occupants
Indoor temperature
7
` OF
Windows
Grains difference 53
A Gr @ 50
% Rh
Eave overhang depth
Roof
-711 $ Ft
Sensible heat gam
26355
Btu/h
Internet shade
Eave
Latent heat g lin
5478
Btu/h
Blinds, drapes, etc
Depth Window
Total heat gain
31833
Btulh
Number of skylights
4
Heating Equiprriient.Data
Cooling Equipment Data
Blower Data
Equipment type
Furnace, Heat pump Boiler, etc.
Heat pump
Equipment type
Air Conditioner, Heat pump, etc
Heat pump
Heating CFM. CFM
Model I
R4H436(A,G)KC-
Model
R4H436(A,G)KC
Cooling CFM�� CFM
Heating output capacity
33800 Btu/h
Sensible cooling capacity
2819$ Btu/h
Heat pumps • cepacit at winter design outdoor conditions
Latent cooling capacity
61 2 Btu/tt
Auxiliary heat ,out piut capacity
Btu/h
Total cooling capacity
34 327 Btu/h
rt 11
i 60
Design airflow,
9 I
CFM
Longest supply duct:
Duct Materials Used (circle)
Ft
I
Trunk Duct: Duct board, Flex, Sheet metal,
External Static Pressure (ESP)
IWC
Longest return duct:
Ft
Lined sheet metal, Other (specify)
Component Pressureli Losses (CPL) IWC
Total Effective Length (TEL)
Ft
Branch Duct: Duct board, Flex, Sheet metal,
Available Static Pressure (ASP)
IWC
Friction Rate:
IWC
Lined speed metal, Other (specify)
ASP = ESP - CPL
Friction Rate = (ASP ■ 100) � TEL
declare the load calculation,equipment
sele6tidn.and
duct design were, rigorouslyperfbrmedbased on - building plan listed
above,, I understand the claimsimade
on •
be subject to review and,verification.
Contractor's Printed Name
Kristin Kelly
Date
1 /'I 1 /2019
Contractors Signature
A1LtYa— kOf 0►r
f he AHJ shall have the discretion to accept Required Attachments printed from approved'ACCA software vendors, see list on psge2 of Instructions.
' if abridged version of Ma�ual J Is used for toad calcination, then verify residence meets requlrements, see Abridged Edition Chec€tilst on page 13 of instructions,
Form generated by ACCA approved Manual J Eighth Edition Version 2 Elite Software Rhvac program.
s I
Air Conditioning Contractors of America
Manual S (Residential Equipment Selection)
/- Project Information
Name:
City:
State: ❑ Altitude: Altitude Adjustment: 1.00
Manual J Loed Calculations
& I" I
'a h1t.&Z —d IL
Loosng uesign +nrornauon _
Outdoor Design Temp: 91 OF db
Summer
Outdoor Design Temp:® OF db
(Winter
Indoor Design Temp: 75 OF db
®%RH ® OF wb
Total Losdl Sensible Latent SHR Heat Loss
31833 r 26355 15478 0.828 C�
Airflow Calculations
Design TO for Airflow
19
Design Sensible CFM
1261
' OEM Information
i
Manufacturoir JCOMF6RTMAKER
Furnace Model,#E: AFUE;�
Coil or Fan -Coil Model #k FXM4X36"AL Condenser Model #: R4H4 A,G)KC" SEER: 15.0 HSPF: 8.20
I
I
- (A) ManufactI urer's Cooling Performance Data
Entering Coil Temperature = 75 (F db)
Lower
CFM
Return Air Outdoor Temperature =
(F wb) Total BTUH Sensible BTUH
95 (F db)
Latent BTUH SHR
Rated CFM 0 Rated RA Temperature
85 34,370 23,6W
10,770
0.6886
Rated CFM 0 Design RA Temperature
1 550
83 327746 26,336
6,410
0.8043
Rafed CFM 0 Rated RA Temperature
i
® 30,310 30,440
-130
1.0043
i
' (B) Manufacturers Cooling Performance Data
Entering Coil Temperature = 75 (F db)
Higher
CFM
Return Air Outdoor Temperature =
(F wb) Total BTUH Sensible BTUH
95 (F db)
� UH
SHR
Rated CFM Q Rated RA Temperature
® 37,470 28,000
9,470
0.7473
Rated CFM ®Design RA Temperature
1550
® 36,492 29,204
7,288
0.8003
Rated CFM 91 Rated RA Temperature
I
® 35,025 31,010
4,015
0.8854
i
Manufacturers Cooling Performance Data (Interpolated)
Design
Return Air Outdoor Temperature = 95 (F db)
CFM
(F wb) Total BTUH Sensible BTUH
Latent BTUH
SHR
27,548
6,781
0.8025
Excess Latent Capacity Calculation
+ 651
- 651
CapalCity Design CFM / RA (F wb)
1281
® 34.327 28,198
6,129
0.821
Equipment Capacity as a of Design
107.8396 106.9996r
111.69—R
Manufacturer I Heat Pump Data
Capacity
Capacity Balance Supplemental
47 OF db 17 OF db Point Heat Required
34,800 18,820 1 -18.3 -15.87
Manufacturers Furnace Data
i
Input Output
Desired Calculated