EVALUATION REPORT
EXTERIOR RESEARCH & DESIGN, LLC.
Certificate of Authorization #9503
353 Christian Street
Oxford, CT 06478
(203) 262-9245
TRI-BUIL� Materials Group, LLC Evaluation Report A42970.10.12-R2
PO Box 700 SCANNED FL16027-112
Rutherford, NJ 07070 BY Date of Issuance: 10/23/2012
(800) 516-1485 St Lucie County Revision 2: 09/25/2017
SCOPE:
This Evaluation Report is issued under Rule 611320-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliant a with the 6th Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: TRI-BUILT Modified Bitumen Roof Systems
LABELING:1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein. �
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes,'the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity) ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertisinlg literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distrib I tors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 4, plus a 26-page Appendix.
Prepared
$
— y
Robert J.M. Nieminen, P.E.
, �L+ : ? ••f `.� The facsimile seal appearing was authorized by Robert Nieminen,
Florida Registration No. 59166, Florida DCA ANE1983 '�l�r� \�]4 P.E. on 09/25/2017. This does not serve as an electronically signed
document.
CERTIFICATION OF INDEPENDENCE:
1. Exterior Research & Design, LLC. d/b/a Trinity I ERD does not have, nor does it intend to acquire or will it acquire, a financial interest
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, LLC. d/b/a Trinity I ERD is not owned, operated or controlled by any company manufacturing or
distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
E
product.
5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically lly for that purpose.
Entity
Examination
FM Approvals (TST1867)
FM 4470/4474
FM Approvals(TST1867)
FM 4470/4474
FM Approvals(TST1867)
FM 4470/4474
P,RI (TST5878)
Physical Properties
PIRI (TST5878)
Physical Properties
PRI (TST5878)
Physical Properties
PRI (TST5878)
Physical Properties
Miami -Dade (CER1592)
HVHZ Compliance
f I iami-Dade (CER1592)
Proposal for Review
U,L LLC (QUA9625)
Quality Control
UL LLC (QUA9625)
Quality Control
UL LLC (QUA9625)
Quality Control
4. PRODUCT DESCRIPTION:
I
This Evaluation Report covers TRI-BUILT Modified
Materials Group, LLC published installation instn
following membranes make up the subject systems.
UTRiNITY I ERD
Reference
Date
3023458
07/18/2006
3030668
09/12/2007
3032172
06/12/2009
PUSA-062-02-01
12/04/2007
PUSA-061-02-02
01/28/2008
PUSA-064-02-02
02/27/2008
PUSA-062-02-02
12/04/2008
Various NOAs
Various
10-0823
10/12/2010
ML Agreement
02/27/2012
ML Correlation, R27202
08/20/2012
Service Confirmation, R14571
Exp. 10/06/2018
Bitumen Roof Systems installed in accordance with TRI-BUILT
ctions and the Limitations / Conditions of Use herein. The
Table,l: Roll -Goods for TRI BUILT Modified Bitumen Roof Systems
Type
Product
Specification
Reference
Grade
Type
SBS Membranes
TriBuilt SA SBS Base
ASTM D6163, Table 2
S
I
TriBuilt SBS Granular
ASTM D6164
G
I
TriBuilt SA SBS Cap
ASTM D6164
G
I
APP Membranes
i
TriBuilt APP Smooth
ASTM D6222
S
I
TriBuilt APP Granular
ASTM D6222
G
I
TriBuilt SA APP Cap
ASTM D6222
G
I
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Refer to a current Approved Roofing Materials Directory for fire ratings of this product.
5.4 For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance
with FBC 2603.4 unless the exceptions stated in FBC 2603.4.1 and 2603.6 apply.
5.5 The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural
members shall be in accordance with FBC requirements to the satisfaction of the Authority Having
Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC
I
Approval documentation.
5.ti For recover installations, the existing roof shall be examined in accordance with FBC 1511.
537 For mechanically attached insulation or membrane or strip -bonded insulation, the maximum design pressure
for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with
FBC Chapter 16. Zones 2 and 3 shall employ an attachment density designed by a qualified design
professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss
Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS
137. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss
Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
Exterior Rese�rch and Design, I.I.C. Evaluation Report A42970.10.12-112
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL16027-112
�I TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Revision 2: 09/25/2017
Page 3 of 4
TRINITY 1 ERD
APPENDIX 1:'ATiACHMENT,REQUIREMENTS FOR WIND UPLIFT RESISTANCE `'
Table Deck Application Type Description Page
IA-1 Wood New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 4
1A-2 Wood New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 5
1B Wood New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 5
1C Wood New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 6
1D Wood New, Reroof (Tear -Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover 6
1E-1 Wood New or Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 7
1E-2 Wood New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 8
1F Wood New or Reroof (Tear -Off) F Non -Insulated, Bonded Roof Cover 8
2A Steel or Structural concrete New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 9
2B Steel or Structural concrete New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover
2C Steel or Structural concrete New, Reroof (Tear -Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover 1'
3A Structural concrete New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 11-14
3B Structural concrete New or Reroof (Tear -Off) F Non -Insulated, Bonded Roof Cover 14
4A
LWIC New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover
15-16
4B
LWIC New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
16
4C
LWIC New or Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
17-19
5A
CWF New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover
20
5B
CWF New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
21
5C
CWF New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
22
5D
CWF New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover
22
5E
CWF New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
22
6A
Gypsum New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover
23
6B
Gypsum New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
24
6C
Gypsum New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover
24
6D
Gypsum New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
24
7A
Various Recover A-1 Bonded Insulation, Bonded Roof Cover
25-26
7B
Various Recover F Non -Insulated, Bonded Base Sheet, Bonded Roof Cover
2F
The following notes apply to the systems outlined herein:
1.
The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
2.
Insulation / base sheet fasteners shall be of sufficient length for the following deck engagement:
➢ Wood: Minimum 0.75-inch penetration.
➢ Steel: Minimum 0.75-inch penetration and engage the top flute of the steel deck.
➢ Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturer's published installation instructions.
3.
Unless otherwise noted, insulation may be any one layer or combination of polyisocyanurate, polystyrene, wood fiberboard, perlite, gypsum -based roof board or mineral -wool roof board that meets the CIA
requirements of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover.
Exterior Research and Design, LLC. d/b/a Trinity ERD Evaluation Report A42970.10.12-R2 for FL16027-112
Certificate of Authorization #9503 6' EDITION (2017) FBC NON-HVHZ EVALUATION
Revision 2: 09/25/2017
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485
Appendix 1, Page 1 of 26
TPJN IN I ERb .
15. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications.
�: ....:. TABLE 1:-TRI-BUILT ROOF COvi=I
Reference
Layer
Material
Application
BP -AA
Base Ply
FBC Approved ASTM D4601, Type II
(Base and Ply sheets, Asphalt -Applied)
HA at 20-40 Ibs/square
Ply
FBC Approved ASTM D2178, Type IV or VI
SBS-AA
(SBS, Asphalt -Applied)
Cap Ply
TriBuilt SBS Granular
HA at 20-40 Ibs/square
SBS-TA
(SBS, Torch -Applied)
Cap Ply
TriBuilt SBS Granular
Torch -Applied
SBS-SA
Base Ply
TriBuilt SA SBS Base
(SBS, Self -Adhering)
Self Adhering
Cap Ply
TriBuilt SA SBS Cap
APP-TA
Base Ply or Ply
TriBuilt APP Smooth
(APP, Torch -Applied)
Torch -Applied
Cap Ply
TriBuilt APP Smooth, TriBuilt APP Granular
APP-SA
Cap Ply
TriBuilt SA APP Cap
Self -Adhering
(APP, Self -Adhering)
16. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Design Pressure (MDP) limitations. The lesser of the MDP listings below vs. those in Table 3A
applies:
VAPOR BA6RIER OPTIONS; STRUCTURAL CONCRETE DECK; ADHERED INSULATION PER TABLE 3A
Option #
Primer
Vapor Barrier
Insulation Adhesive
MDP (psf)
Type
Attach
VB-1.
ASTM D41
TriBuilt SA SBS Base
Self -Adhering
Inta-Stik or CR-20, 12-inch o.c.
-60.0
VB-2.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
Insta-Stik, 12-inch o.c.
-75.0
VB-3.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
Millennium One Step Foamable Adhesive, 12-inch o.c.
-157.5
VB-4.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
CR-20, 12-inch o.c.
-270.0
VB-5.
ASTM D41
TriBuilt SA SBS Base
Self -Adhering
Millennium One Step Foamable Adhesive, Millennium PG-1 Pump Grade
Adhesive, OlyBond 500 or CR-20, 12-inch o.c.
-290.0
17. Dens Deck shall be field -primed with PG100 prior to self -adhering membrane application. Refer to tables herein for other priming requirements.
18. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads.
Exterior Research and Design, LLC. d/b/a Trinity ) ERD Evaluation Report A42970.10.12-112 for FL16027-112
Certificate of Authorization #9503 6' EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 3 of 26
\I TRINITY ERD
TABLE IA-2: 1N00D:DECKS.- LAEW-CONSTRUCTION; REROOF (TEAR-04�'oR RECOVER '-2�,
SYSTEU TYPE A-2: MECHANICALLY`ATTACHED ANCHOR -SHEET, BONDED INSULATION, BONDED ROOF COVER
System
Deck
Anchor Sheet
Base Insulation
Top Insulation
Roof Cover (Note 15)
MDP
No.
(Note 1)
Type
Fasteners
Attach
Type
Attach
Type
Attach
Base Ply
Ply
Cap Ply
(psf)
Min. 0.25-inch Dens Deck,
Polyglass
12-inch o.c. in 4-
(Optional) FBC
Dens Deck Prime, SECUROCK
Min. 19/32-
Elastobase or
OMG Flat
inch lap and 12-
Approved,
Gypsum -Fiber Roof Board,
W 5
inch plywood
Polyglass
Bottom Plates
inch in two,
ASTM C1289,
HA
Min. 0.75-inch FescoBoard
HA
BP -AA
(Optional)
SBS-AA, SBS-
-60.0
at max. 24-
Elastobase
(square) with
equalllyly spaced,
type II polyiso-
(homogeneous) or min. 0.5-
BP -AA
TA, APP-TA
inch spans
Poly
Roofgrip #12
staggered center
cyanurate
inch Structodek High Density
rows
Fiberboard Roof Insulation
Min. 19/32-.
Polyglass
OMG Flat
inc o.c. in
inch lap and 12-
(Optional) FBC
(Optional)
Elastobase or
Approved,
Min. 0.25-inch Dens Deck,
One or
SBS-SA, APP-
W-6
inch plywood
Polyglass
Bottom Plates
inch o.c. in two,
ASTM C1289,
HA
Dens Deck Prime, SECUROCK
HA
SBS-SA
more SBS-
SA, SBS-TA
-60.0
at max. 24-
Elastobase
(square) with
equally spaced,
type II polyiso-
Gypsum -Fiber Roof Board
SA or APP-
or APP-TA
inch spans
Poly
Roofgrip #12
staggered center
rows
cyanurate
TA
WOAD; DECKS— NEW CONSTRUCTION REROOF`(TMA-OFF) oR RECOVER;
SYSTEM -.TYPE B:"MECHANICALLY,ATT-ACHED:BASE INSULATIONj BONDEDTOP INSULATION BONDED ROOF COVER' '
System
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 15)
MDP
No.
Deck (Note 1)
Type
Fasteners
Attach
Type
Attach
Base Ply
Ply
Cap Ply
(psf)
Min. 19/32-inch
Min. 1.5-inch
Dekfast Hex with
Min. 0.75-inch FescoBoard
(Optional if
(Optional if using
W-7
plywood at max. 24-inch
ENRGY 3, H-Shield
Dekfast #12 or TruFast
1 per z
(homogeneous) or min. 0.5-inch
HA
using AA Ply)
AA Base) One or
SBS-AA, SBS-TA,
-60.0
1.33 ft
Structodek High Density Fiberboard
more BP -AA or
APP-TA
spans
or Polytherm
MP-3 with TruFast DP
Roof Insulation
BP AA
APP-TA
Exterior Research and Design, I.I.C. d/b/a Trinity) ERD Evaluation Report A42970.10.12-R2 for FL16027-R2
Certificate of Authorization #9503 eH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 5 of 26
\4 TRINITY
ERD
TABLE4E 2:=WOOD DECKS- NEW CONSTRUCTION; REROOF (Tl=aa=OFF)'oR`RecoVER -
" SYSTEM TYPE E >NON -INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER —
System
Base Sheet
Roof Cover (Note 15)
MDP
No.
Deck (Note 1)
Base
Fasteners
Attach
Base Ply
Cap Ply
(psf)
Min. 19/32-inch
Polyglass Elastobase, Polyglass Elastobase
OMG Flat Bottom Plates (square) with
12-inch o.c. in 4-inch lap and 12-inch
(Optional) One or
W-1
plywood at max.
Poly, Polyglass G2 Base, J Teed
Roofgrip #14, Dekfast Hex with Dekfast #14
o.c. in two, equally spaced, staggered
more BP -AA or
SBS-AA, SBS-
-52.5
24-inch spans
e, Firestone Base,
Base,
Gy
or TruFast MP-3 with TruFast HD
center rows
APP-TA
TA, APP TA
28, Base AF LAS #
Ply 28, Tamko Glass Base or GAFGLAS #75
Min. 19/32-inch
Polyglass Elastobase or Polyglass
Dekfast Hex with Dekfast #14 or TruFast MP-
12-inch o.c. in 4-inch lap and 12-inch
One or more SBS-
SBS-SA, APP-
W-2
plywood at max.
in two, equally spaced, staggered
SA, SBS TA or
52.5
24-inch spans
Elastobase Poly with poly top surface
3 with TruFast HD
ter rows
center
cen
SA
APP-TA
Min. 19/32-inch
Polyglass Elastobase or Polyglass
OMG Flat Bottom Plates (square) with
12-inch o.c. in 4-inch lap and 12-inch
(Optional) One or
SBS-AA, SBS-
W-3
plywood at max,
Elastobase Poly
Roofgrip #12
o.c. in two, equally spaced, staggered
more BP -AA or
TA, APP TA
-60.0
24-inch spans
center rows
APP-TA
Min. 19/32-inch
Polyglass Elastobase or Polyglass
OMG Flat Bottom Plates (square) with
12-inch o.c. in 4-inch lap and 12-inch
One or more SBS-
SBS-SA, APP-
W-4
plywood at max.
Elastobase Poly with poly top surface
Roofgrip #12
o.c. in two, equally spaced, staggered
SA
SA, SBS-TA or
-60.0*
24-inch spans
I
I
I center rows
APP-TA
TABLE iF: WOOD DECKS- NEW CONSTRUCTION oR REROOF. (TeAR-OFF)
SYSTEM:TYPE F: PION -INSULATED; BONDED"ROOF COVER."' "
System
Roof Cover No
MDP
Deck
prompr
Joint Treatment
Base Ply
Ply
Cap Ply
N
Ps
W 5
Min. 15/32-inch plywood
(Optional) ASTM D41
None
SBS-SA
(Optional) SBS-SA or
SBS-SA, APP-SA, SBS-TA
90.0
at max. 24-inch spans
APP-TA
or APP-TA
W 6
Min. 15 inc p ywoo
(Optional) ASTM D41
ywood joints are covered with 4-inch wide strips of TriBuilt SA
TriBuilt SA SBS Base
(Optional) SBS-SA or
'
97 5
at max. 24-inch spans
SBS Base, rolled into place to create continuous bond.
APP-TA
I or APR -TA
Exterior Research and Design, LLC. d/b/a Trinity) ERD Evaluation Report A42970.10.12-R2 for FL36027-112
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 8 of 26