HomeMy WebLinkAboutSOIL NUCLEAR GAUGE REPORTS - 3 TOTALU-J;Iti`—
��o
V
Port St. Lucie
FBPECA#4930
.-46 607NWCommodity Cove
��
Port St. Lucie, FL 34986
Q
Phone: 772-924-3575 1 Fax:
772-924-3580
•
Soil Nuclear Gauge
Report Date: 2/12/2019
Test Method: ASTM D 6938
Client:
Southern City Development, LLC
5900 Silver Oak Drive
Fort Pierce, FL 34982
Project:
19-1153.00
Southern City Development 2019 Master
Agreement
Various Locations
FL
Test Results
Test #
Retest
Of
Test
Date
Proctor ID
Method
Soil
Classification
Optimum
Moisture
N
Maximum
Dry Density
(pcf)
In Place
Moisture
N
In Place
Dry Density
(pcf)
Probe
Depth
(in)
Percent
Compaction
Min/Max
Comp.
N
Remark
51
2/8/19
8816 D1557
N/A
11.1
105.5
9.9
104.4
12
99
95 / 105
Pass
52
2/12/19
8816 D1557
N/A
11.1
105.5
10.0
102.7
12
97
95 / 105
Pass
53
2/12/19
8816 D1557
N/A
11.1
1 105.5
1 8.6
1 102.8
1 12
1 97
1 95 / 105 1
Pass
54
2/12/19
8816 D1557
N/A
11.1
1 105.5
1 9.2
1 103.0
1 12
1 98
1 95 / 105 1
Pass
Test Information
Test #
Test Location
Elevation
Reference
Gauge
Make / Model / SN / Calibrated
Field Technician
51
Above Stripped Surface: Dixieland Town homes, Building 3, 265 & 267 Dixieland
Drive, Ft Pierce, Center.
2-3'
Troxler / T3430 / 34784 /
Evans, Amber
52
Above Stripped Surface: Dixieland Town homes, Building 3, 265 & 267 Dixieland
Drive, Ft Pierce, SW corner.
3-4'
Troxler / T3430 / 34784 /
Evans, Amber
53
Above Stripped Surface: Dixieland Town homes, Building 3, 265 & 267 Dixieland
Drive, Ft Pierce, NE comer.
3-4'
Troxler / T3430 / 34784 /
Evans, Amber
54
JAbove Stripped Surface: Dixieland Town homes, Building 3, 265 & 267 Dixieland
Drive, Ft Pierce, Center.
3-4'
Troxler / T3430 / 34784 /
Evans, Amber
Remarks
Comments
Pass: Tests results comply with specifications
Tests are "Direct Transmission" (Method A) unless probe depth is noted as
1"Backscatter". Gauge calibration data on file with the testing agency.
\111111111/////
.�`���O�N• KFNT�'%
� ••�ICENSF %
6 18 �
= r I}2/1212019
--------------
ri• Ken ; P.E.
P s�fe4ionai*lgirieer#E� 8
sra
ONAL �\\G�`
0111111j1
Test Reports shall not be reproduced, except in full, without the written approval of GFA International Inc.
Digitally signed printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
Page 2 of 2
3 �.r•••woc F
Port St. Lucie _
FBPE CA # 4930
607 NW Commodity Cove
Port St. Lucie, FL 34986
Phone: 772-924-3575 1 Fax: 772-924-3580
Soil Nuclear Gauge
Report Date: 3/19/2019
Test Method: ASTM D 6938
Client:
Southern City Development, LLC
5900 Silver Oak Drive
Fort Pierce, FL 34982
Project:
19-1153.00
Southern City Development 2019 Master
Agreement
Various Locations
FL
Test Results
Test #
Retest
Of
Test
Date
Proctor ID
Method
Soil
Classification
Optimum
Moisture
N
Maximum
Dry Density
(pcf)
In Place
Moisture
N
In Place
Dry Density
(pcf)
Probe
Depth
(in)
Percent
Compaction
Min/Max
Comp.
M)
Remark
76
3/18/19
8866 - T180
N/A
10.6
114.6
8.8
113.9
12
99
98 / 105
Pass
77
3/18/19
8866 - T180
N/A
10.6
114.6
10.4
113.2
12
99
98 / 105
Pass
78
3/18/19
8866 - T180
N/A
10.6
114.6
9.8
114.1
1 12
100
98 / 105
Pass
79
1 3/18/19
8866 - T180
N/A
10.6
114.6
8.9
113.9
12
99
98 / 105
Pass
Test
Information
Test #
Test Location
Elevation
Reference
Gauge
Make / Model / SN / Calibrated
Field Technician
76
Footing: Dixieland, Building 3, Permit 18100712, E Side
0-1
Troxler / T3430 / 36304 /
Smith, Johnnie
77
Footing: Dixieland, Building 3, Permit 18100712, W Side
0-1
Troxler / T3430 / 36304 /
Smith, Johnnie
78
Footing: Dixieland, Building 3, Permit 18100712, N Side
0-1
Troxler / T3430 136304 /
Smith, Johnnie
79
Footing: Dixieland, Building 3, Permit 18100712, S Side
1
10-1
Troxler / T3430 136304 /
Smith, Johnnie
Remarks
Comments
P1,) 1 \-- 'o
Pass: Tests results comply with specifications
Tests are "Direct Transmission" (Method A) unless probe depth is noted as
"Backscatter". Gauge calibration data on file with the testing agency.
c-t
G�0 d
�ONN• KEiVT
No 632 _
4AJAKent,V.E.
03/19f2019
Vftisiorv%Wfi +oeer•# -�j298
ZONAL `E
Test Reports shall not be reproduced, except in full, without the written approval of GFA International Inc.
Digitally signed printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
Page 1 of 1
l
R�roll"®
Soil Nuclear Gauge
eQan',teport Date: 4/1/2019
e Est i� ie___ _ Co lest Method: ASTM D 6938
FBPE CA # 4930
607 NW Commodity Cove
Port St. Lucie, FL 34986
Phone: 772-924-35761 Fax: 772-924-3580
/ e / t? - 0 ) 12--,
Client:
Southern City Development, LLC
5900 Silver Oak Drive
Fort Pierce, FL 34982
Project:
19-1153.00
Southern City Development 2019 Master
Agreement
Various Locations
FL
Test Results
Test #
Retest
Of
Test
Date
Proctor ID
Method
Soil
Classification
Optimum
Moisture
N
Maximum
Dry Density
(pcf)
In Place
Moisture
N
In Place
Dry Density
(pcf)
Probe
Depth
(in)
Percent
Compaction
Min/Max
Comp.
(°/,)
Remark
43
2/6119
8816 D1557
N/A
11.1
105.5
9.0
104.1
12
99
95 / 105
Pass
44
2/6/19
8816 D1557
N/A
11.1
105.5
9.6
104.0
12
99
95 / 105
Pass
45
2/6/19
8816 D1557
N/A
11.1
105.5
9.4
103.9
12
98
95 / 105
Pass
46
2/7/19
8816 D1557
N/A
11.1
105.5
9.3
103.6
12
98
95 / 105
Pass
47
2/7119
8816 D1557
N/A
11.1
105.5
10.6
104.0
12
99
95 / 105
Pass
48
217/19
8816 D1557
N/A
11.1
105.5
9.5
104.4
12
99
95 / 105
Pass
49
2/8/19
8816 D1557
N/A
11.1
105.5
10.0
104.3
12
99
95 / 105
Pass
50
2/8/19
8816 D1557
N/A
11.1
1 105.5
9.0
103.9
12
98
1 95 / 105 1
Pass
Test
Information
Test #
Test Location
Elevation
Reference
Gauge
Make / Model / SN / Calibrated
Field Technician
43
Above Stripped Surface: Dixieland Town homes, Building 3, 265 & 267 Dixieland
Drive, Ft Pierce, NE corner. Permit 18100712
0-1'
Troxler / T3430 / 34784 /
Evans, Amber
44
Above Stripped Surface: Dixieland Town homes, Building 3, 265 & 267 Dixieland
Drive, Ft Pierce, SW corner. Permit 18100712
0-1'
Troxler / T3430 / 34784 /
Evans, Amber
45
Above Stripped Surface: Dixieland Town homes, Building 3, 265 & 2679 Dixieland
Drive, Ft Pierce, Center. Permit 18100712
0-1'
Troxler / T3430 / 34784 /
Evans, Amber
46
Above Stripped Surface: Dixieland Town homes, Building 3, 265 & 267 Dixieland
Drive, Ft Pierce, Center. Permit 18100712
1-2'
Troxler / T3430 134784 /
Evans, Amber
47
Above Stripped Surface: Dixieland Town homes, Building 3, 265 & 267 Dixieland
Drive, Ft Pierce, NW comer. Permit 18100712
1-2'
Troxler / T3430 / 34784 /
Evans, Amber
48
Above Stripped Surface: Dixieland Town homes, Building 3, 265 & 267 Dixieland
Drive, Ff Pierce, SE comer. Permit 18100712
1-2'
Troxler / T3430 / 34784 /
Evans, Amber
49
Above Stripped Surface: Dixieland Town homes, Building 3, 265 & 267 Dixieland
Drive, Ft Pierce, SW corner. Permit 18100712
2-3'
Troxler / T3430 / 34784 /
Evans, Amber
50
Above Stripped Surface: Dixieland Town homes, Building 3, 265 & 267 Dixieland
Drive, Ft Pierce, NE comer. Permit 18100712
2-3'
Troxler / T3430 / 34784 /
Evans, Amber
Remarks
Comments
Pass: Tests results comply with specifications
Tests are "Direct Transmission" (Method A) unless probe depth is noted as
"Backscatter". Gauge calibration data on file with the testing agency.
Test Reports shall not be reproduced, except in full, without the written approval of GFA International Inc. Page 1 of 2
Digitally signed printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
%-1
•