EVALUATION REPORT
Polyglass USA, Inc. Evaluation Report P12060.02.09-R24
1111 West Newport Center Drive SCANNED FL5259-R28
Deerfield Beach, •FL 33442 BY Date of Issuance: 02/24/2009
(954) 233-1230 1 St Lucie.County Revision 24: 01/24/2018
SCOPE: ,
This Evaluation Report is issued under Rule 611520-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E.
for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products
described herein have been evaluated for compliance with the a Edition (2017) Florida Building Code sections noted
herein.
DESCRIPTION:.Polyglass Roof Underlayments
LABELING: Labeling shall be in -accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named.product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the
product(s), the Quality Assurance or the production facility location(s). NEMOjetc. requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOletc. Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 14.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert Nieminen,
P.E. on 01/24/2018..This does not serve as an electronically
signed document.
CERTIFICATION OF INDEPENDENCE:
1. NEW Ietc. does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMOI etc. is� not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEM01etc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
1. SCOPE:
2.
EI
ONEMOletc.
EVALUATION:
Product Category:
Roofing
Sub -Category:
Underlayment
Compliance Statement: Roof
Underlayments, as produced by Polyglass USA, Inc., have demonstrated
compliance with the
following sections of the 6th
Edition (2017) Florida Building Code through testing in accordance with the
following Standards.
Compliance is subject to the
Installation Requirements and Limitations / Conditions of Use set forth herein.
STANDARDS:
Section
Property Standard
Year
1504.3.1
Wind Uplift FM 4474
2011
1504.3.1
Wind Uplift UL 1897
2012
1507.2.3 / 1507.1.1
Physical Properties ASTM D226
2009
1507.2.4 / 1507.1.1,1507.2.9.2
Physical Properties ASTM D3970
2615
1507.3.3
Physical Properties FRSA/TRI April 2012
2012
1507.11.2
Physical Properties ASTM D6164
2011
1507.11.2
Physical Properties ASTM D6222
2011
TAS 110
Accelerated Weathering ASTM D4798
2011
rST 1867)
NEMO ETC, U.c.
Certificate ofAutharizatian #32455
I
Examination
Reference
Date
Wind Uplift
3004091
01/22/2000
Physical Properties
PR101111
04/08/2002
Physical Properties
PUSA-005-02-01
01/31/2002
Physical Properties
PUSA-013-02-01
12/23/2002
Physical Properties
PUSA-013-02-02
12/23/2002
Physical Properties
PUSA-013-02-03
12/23/2002
Physical Properties
PUSA-018-02-01
07/14/2003
Physical Properties
PUSA-028-02-01
07/13/2005
Physical Properties
PUSA-033-02-01
01/12/2006
Physical Properties _
PUSA-035-02-01
09/29/2006.
Physical Properties
PUSA-055-02-02
12/10/2007
Physical Properties
PUSA-061-02-02
01/28/2008
Physical Properties
PUSA-076-02-01
02/22/2008
Physical Properties
PUSA-083-02-01
04/14/2008
Physical Properties
PUSA-088-02-01
07/29/2009
Physical Properties
JX20H7A
04/01/2008
Physical Properties
RX14E8A
01/29/2009
Physical Properties
11752.06.99-1
02/08/2000
Wind Uplift
11757.08.01-1
08/13/2001
Wind Uplift
11776.06.02
01/26/2003
Physical Properties
02200,07.03
07/14/2003
Wind Uplift
P1740.01.07
01/04/2007
Physical Properties
P5110.04.07-1
04/11/2007
Wind Uplift
P9260.03.08
03/21/2008
Physical Properties
P13450.08.09
08/13/2009
Wind Uplift
P30540.11.09-R1
11/30/2009
Physical Properties.
P11030.11.09-1
11/30/2009
Wind Uplift
P11030A1.09-2
11/30/2009
Physical Properties
P11030.11.09-3
11/30/2009
Physical Properties
P33360.06.10
06/25/2010
Physical Properties
P33370.03.11
03/02/2011
Physical Properties
P33370.04.11
04/26/2011
Physical Properties
P37300.10.11
10/19/2011
Evaluation Report P12060.02:09-1124
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230
Revision 24: 01/24/2018
Page 2 of 14
Entity
ERD (TST 60
ERD (TST.60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST-60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST•60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ERD (TST 60
ICC-ES (EVL
Miami -Dade (CER 1592)
Polyglass USA
Polyglass USA
Polyglass USA
UL, LLC. (Q IA9625)
4. PRODUCT DESCRIPTION:
NNEMO etc.
Examination Reference Date
Physical Properties P40390.C8.12-1 08/06/2012
Physical Properties P40390.08.12-2 08/07/2012
Physical Properties C41420.09.12-3 09/11/2012
Wind Uplift 1339680.08.13 03/04/2013
Physical Properties P45370.04.13 04/26/2013
Wind Uplift P1738.02.07-R2 04/29/2013
Wind Uplift 11757.04.01-1-R1 04/30/2013
Wind Uplift P41630.08.13 08/06/2013
Wind Uplift P11751.05.03-R1 21/26/2013
Wind Uplift P11781.11.03-R1 11/26/2013
Physical Properties P45270.05.14 05/12/2014
Physical Properties 6020.07.14-1 09/08/2014
Physical Properties 6020.09.14-2 09/08/2014
Physical Properties 6020.09.14-3 09/08/2014
Physical Properties 6020.09.14-4 09/08/2024
Physical Properties 6020.09.14-5 09/08/2014
Physical Properties 6020.09.14-6 09/08/2014
Physical Properties P46520.10.14 10/03/2014
Physical Properties P43290.10.14 10/17/2014
Physical Properties PLYG-SC7550.03.15 03/24/2015
Physical Properties P40390.04.15 04/03/2015
Physical Properties P44360.10.14-R3 05/18/2015
Physical Properties . PLYG-SC8080.05.15-1 05/20/2015
Wind Uplift PLYG-SC8905.05.16-1 05/17/2616
Physical Properties PLYG-SC8080.07.16 07/16/2016
Wind Uplift PLYG-SC12025.10.16 . 20/22/2016
Physical Properties PLYG-SC13040.12.16 12/27/2016
Physical Properties PLYG-SC11900.03.17 03/10/2017
Physical Properties PLYG-SC12115.08.17 08/08/2017
IBC Compliance ESR-1697 11/01/2014
HVHZ Compliance N6A.14-0717.08 01/22/2015
Manufacturing Affidavit Products Current 02/18/2009
P/LAflidavit Mule -Hide Cross Ltg 03/01/2008
Materials Affidavit Polystick SA Compound 08/18/2011
Quality Control Service Confirmation Exp.10/05/2018
4.1 Mechapically Fastened Underlayments
4.1.1 Elastobase is a fiberglass reinforced, SBS modified bitumen base sheet.
4.1.2 Elastobase P is a polyester -reinforced, SBS modified bitumen base sheet.
i
4.1.3 Polyglass 62 Base is a fiberglass=reinforced, asphaltic base sheet.
4.14 PolyglassAPP�Base is a fiberglass -reinforced, APP. modified bitumen base sheet:
77777
Adiiering`�)n"derlaytnents �• ; µ 4 fc. ,a:� -
442;1Polystick MTS�or,.Poljrstick MTS PLUS is a nominal 60-mil #hick rubberized asphalt waterproofing=membrarie;agtass:.p
4.2.2 Polystick IR-Xe.is a nominal 60-mil thick rubberized asphalt waterproofing. membrane, glass fiber reinforced, with an
aggregate surface;'meets ASTM D1970.
4.2.3 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane,"glass fiber reinforced, with a
polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012.
NEMO ETC, LLC. 1
Cert(%kate of Autho 1zatron 032455
I
eN EDITION (2017) FBC NON-HVHZ EVALUATION
Polyglass Roof Underlayments; (954) 233-2230
Evaluation Report P12060.02.09-R24
FL5259-R28
Revision 24: 02/24/2018
Page 3 of 14
4.2.4
4.2.5
4.2.6
4.2.7
4.2.8
4.2.9
4.3.1
4.3.2
4.3.3.
5. LIMITAI
5.1
5.2
5.3
5.4
NEMO J etc.
stick. TU P'is a nominal 130=mil thick rubberized asphalt' Waterproofing membrane, glass-fiber/polyester
orced, with a granular surface; meets FRSA/TRI April'2012.
stick TU Max is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/m2 polyester
c surface; meets ASTM D1970 and FRSA/TRI April 2012:
Flex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule=Hide.SA APP Cap Sheet (FR) are polyester
orced, APP modified .bitumen cap sheets; meet FRSA/TRI April 2012.
stick Dual Pro"" is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
orced, with a polyester fabric surface; meets ASTM D1970.
stick Tile Prdnw is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass.
orced, with a polyester fabric surface; rheets ASTM D1970 and FRSA/TRI -April 2012.
stick MU-X' is a nominal 54-mil thick- dual -layer rubberized asphalt, waterproofing membrane, fiberglass
orced, with a polypropylene film surface; meets AC188.and physical requirements of ASTM, D1970 (See Section
hanically Fastened and/or Bonded Underlayments
:oflex G Tll-is a polyester reinforced, modified bitumen tile underlayment composed of a sand -surfaced SBS
ified bitumen back -side and granule -surfaced APP modified bitumen top -side. •Elastoflex G TU is for use as an
nate to "Mineral Surface Roll Roofing"-(ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April
(04-12).beneath mechanically fastened.tile roof systems or Hot Asphalt applied "Cap Sheet" in the `Two Ply
-m" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems.
;oflex 56 G and Elastoflex S6 G FR are polyester reinforced; SBS modified bitumen cap sheets; meet ASTM D6164.
,oflex S6 G and Elastoflex S6 G FR are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380,
1 M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath• mechanically fastened tile roof systems.
:oflex S6 G is for use as- an. alternate.to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI
2012 (04-12) beneath mechanically fastened or adhered tile roof systems. 'Elastoflex S6 G FR is for use as an
pate to Hot -Asphalt applied "Cap Sheet". in the `Two Ply System" from FRSA/TRI. Agri1.2012. (04-12) beneath
hanically fastened tile roof systems. -
Flex G and .Polyflex G. FR are polyester reinforced,. APP. modified bitumen cap sheets; meet ASTM D6222.
Flex G is for use as an alternate to Heat Applied "Cap Sheet" in the "Two Ply System" from _FRSA/TRI April 2012
1.2) beneath mechanically fastened or adhered.tile roof systems. Polyflex G FR is for use as an alternate to Heat
led "Cap. Sheet" in the "Two.Ply System" from FRSA/TRI April 2012 (04712) beneath. mechanically, fastened tile
systems.,
is a building code evaluation. Neither NEMOietc. nor Robert Nieminen, P.E. are, in any, way, the Designer of
ord for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or
gn guidance unless retained specifically for that•purpose.
Evaluation Report is not for use in the HVHZ.
Classification is not:part of this Evaluation Report, refer to current Approved. Roofing Materials Directory for fire
Zgs of this product:
Fglass Roof Underlayments may be used with.any prepared roof cover where the product Is specifically referenced
lin FBC approval documents. If not listed, a request may be made to the. Authority Having Jurisdiction for
roval based on.this evaluation combined with supporting data for the prepared roof covering.. .
NEN10 ETC, LLC.
Certificate ofAuthorizatlon #32455
Evaluation Report P12060.02.09-R24
EDITION (2017) F8C NON-HVHZ EVAWATION FL5259-R28.
Polvglass Roof Underlayments; (M) 233.1230 Revision 24: 01/24/2018
Page 4 of 14
NNEMOjetc.
5.5 Allowable Roof Covers:
Underlayment
Asphalt Shingles
Nall -On Tile
Foam -On Tile
Metal
Wood Shakes
&Shingles'
Slate
Elastobase
Yes
Yes
(Base Sheet In 2-ply system)
Yes
(Base Sheet In 2-ply system)
Yes
Yes
Yes
Elastobase P
Yes
Yes
(Base Sheet In 2-ply system)
Yes
(Base Sheet in 2-ply system)
Yes
Yes
Yes
Polyglass G2Base
I
NO
Yes
(Base Sheet In 2-ply system)
Yes
(Base Sheet In2-plysystem)
No
No
NO
Polyglass AP Base
No
Yes
(Base Sheet In 2-ply system)
Yes
_(Base Sheet in 2-ply system)
No
No
No
Polystic,MTS or1MT5 P�US`wx,
* ry *s>e` �PYes
4 i Wyes ^*4� .
..,T. fVo�w v...
Yes: a< 7;
i • tkYe"s "` t;�{
f wYe�.
Polystick R=X�'__.
Yes
__.....a,.W:.
PolystickTU!P
No
Yes
Yes (See 5.5.1)
No
No
No
Polystick TU, Plus
Yes
Yes
Yes (See 5.5.1)
Yes
Yes
Yes
Polystick TUI Max
No
Yes
Yes (See 5.5.1)
Yes
No
No
Polystick Dubl Pro
Yes
No
No
Yes
Yes
Yes
Polystick Tile Pro
Yes
Yes
Yes (See5.5.1)
Yes
Yes
Yes
Polystick MU-X
Yes
No
No
Yes
Yes
Yes
Elastoflex S6 G
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Elastoflex S6 G FR
Yes
Yes
No
No
Yes
Yes
Elastoflex G TU
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Polyflex G ;
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Polyflex G Fk
Yes
Yes
No
No
Yes
Yes
PolyfiexSAP.orSAPFR
Yes
Yes
Yes (See5.5.1)
No
Yes
Yes
Mule -Hide SA-APP Cap Sheet
or SA-APP Cap Sheet (FR)
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations.
TABLE!*
ALLOINA i1LE ADHESIVE UNDERtA1(N1EN7 COnI)BINATIONS
Adhesive
Florida Product
Underlayments
Approval
DAP Foam Touch in Seal StormBond Roof
FL14506
Polystick TU Plus, Polystick TU Max
Tile Adhesive
Dow TileBond'
FL22525
Polystick TU P, Polystick TU Plus, Polyflex SAP or Tile Pro
Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro,
1CP Adhesives Polyset® AH-160
FL6332
Elastoflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR,
Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR)
Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro,
ICP Adhesives Polyset® RTA-1
FL6276
Elastoflex G TU, Elastoflex 56 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR,
Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR)
z Refer to Tile:Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
NEMO ETC, LLC. Evaluation Report P12060.02.09-R24
certificate afAutharizatian u32455 6tx EDITION (2017) FBC NON-HVHZ EVALUATION FL5259•R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 5 of 14
t
5.6
5.6.1
5.6.2
5.6.3
I l� ` 1\
ti\
EMo a c.
Allowable Substrates:
i
Direct -Bond to Deck:
Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or. SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet
(FR) self -adhered to:
New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing
plywood; New or existing, unprimed OSB; ASTM D41 primed. OSB, Southern Yellow. Pine;, ASTM D41 primed
Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels
(designed and installed to meet wind loads'for project).
ote;. Polyglass does. not require priming of new or existing plywood or OSB sheathing. New or existing plywood or
OSB.sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes.
Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to:
➢ ASTM D41 primed structural concrete..
Polyflex G or, Polyflex G FR torch -applied to:
➢'ASTM'D41 primed structural concrete.
Bond -to -Insulation:
Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered
i
to:
ASTM C1289,. Type II, Class 1 polyisocyanurate or Type V polyisocyanurate-composite insulation; Dens Deck
DuraGuard; Dens Deck Prime; or SECUROCK Gypsum -Fiber Roof Board.
Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt.to:
Dens. Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
Polyflex G or Polyflex G FR torch -applied to: .
ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
For installation under .mechanically attached prepared roof coverings, insulation shall be attached per minimum
requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile
systems, insulation attachment shall be designed by a qualified design professional and installed based on testing of
he insulation/underlayment system in accordance with FBC Section 1504.3.1.
Bond to Mechanically Attached Base Laver:
(Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or
Nile Pro self -adhered to:
➢ ASTM D226, Type I or.11 felt;, Elastobase; Elastobase P or Mule -Hide Nail Base.
!Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to:
➢ ASTM D226, Typed or II felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base.
Polyflex G or Polyflex G FR torch -applied to:
➢ Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass GZ Base. or Polyglass APP'Base.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum
codified requirements. .For installations under foam -on tile systems, base layer shall be attached per minimum
requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in
accordance with FBC Section 1504.3.1.
NEMO ETC, LLC: Evaluation Report 1312060.02.09-1124
0241-te ofAuthorh:ation #32455 E7" EDITION (2017) FBC NON-HVHZ EVALUATION ' FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 6 of 14
IONEMO etc.
5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12) does not
address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment
forms part of the load=path. The following wind uplift limitations apply to underlayment systems that are not
addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure is the
result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure
divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-.
12); Appendix A, Table 1A or FBC 1609 for determination of design wind loads.
#1 Maximum Design Pressure = -90 p5f:
Beck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: None
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TO Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
#2 Maximum Design Pressure = -97.5 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primee PG100 or ASTM D41
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TO Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga: x
1W ring shank nails through 32 ga.,1-5/8" diameter tin caps spaced 12-Inch o.c.
#3 Maximum Design Pressure = =105 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: WB-3000,
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
(Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga: x
IX" ring shank nails through 32 ga.,1-5/8" diameter tin caps spaced 12-inch o.c.
#4 iMaximum Design Pressure = -135 psf:
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: (Optional) PG100 or ASTM D41
1Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Joints: Min. 4-inch wide strips of Elastoflex SA-V over all plywood joints.
!Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
#5 I Maximum Design Pressure = -315 psf
I Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: PG100 or ASTM D41
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Tile Pro, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap
Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered..
#6 Maximum Design Pressure = -622.5 psf:
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: PG100 or ASTM D41
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied.
#7 Maximum Design Pressure = -30.,0 psf*:.
Deck:' Min. 15/32-Inch OSB to meet project requirements to satisfaction of Authority Having Jurisdiction:
Base Sheet: Elastobase or Mule -Hide Nall Base (poly -film top surface)
Fasteners:- 11 ga. x 1.25-inch long x 1-inch head diameter round metal cap nails
Spacing: 6-inch o.c. at the 3-inch wide side laps and 6-inch c.c. at two (2) equally spaced staggered centerrows.
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self=adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP- Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self=adhered.
NEMO ETC, LLC. Evaluation Report P12060.02.09-R24
cert!/rcate ofAuthorizatlonH32455 6" EDITION (2027) FBC NON-HVHZ EVALUATION FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
. Page 7 of 14
ONEMOletc.
#8 Maximum Design Pressure = -37.5 psf*:
Deck: Min. 15/32-inch plywood•to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: 11 ga. x 1.25-inch long x 1-inch head diameter round metal cap nails
Spacing: 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c: at two (2) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS, or Polystick MTS PLUS,.self-adhered.
Underlayment: Polystick TU .P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule-Hide'SA-APP Cap Sheet (FR), self -adhered.
#9 Maximum Design Pressure = -37.5 psf*:
Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: One (1) or two (2) layers ASTM D226, Type II felt
Fasteners: 11 ga. x 1.25-inch long x 1-inch head diameter round metal cap nails
Spacing:. 6-inch o.c. at the 3-inch wide side laps and 12-inch o.c. at two (2). equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt.
#10 Maximum Design Pressure=-45 psf*:
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
iBase Sheet: .On,
(1) layer ASTM D226, Type II felt
Fasteners: 11 ga. x 1,254rich x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
(Spacing: 4-inch o.c. at the 2-inch wide side laps and 4-inch o.c. at two (2) equally spaced staggered center rows.
1Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS. PLUS, self -adhered.
IUnderiayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), seff-adhered or Elastoflex G TU,'appiled In full mopping of hot asphalt.
#11 Maximum Design Pressure = -45 psf*:
Deck: - Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. .
Base Sheet: Two (2) layers ASTM D226, Type II felt
Fasteners: 11 ga..x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1=5/8-Inch diameter tin caps
Spacing: 9-inch o.c. at the 2-inch wide side.laps and 9-inch o.c. at two (2) equally spaced staggered center rows.
Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus", Polystick TU Max; Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot
asphalt.
#12 1 Maximum Design Pressure = -45 psf:
Deck:
Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet:
Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners:
Simplex MAXX Cap Fasteners
Spacing:
9.1nch o.c. at the 2-inch wide side laps and 18-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#13 Maximum Design Pressure = -52.5 psf:
Deck:
Min. 15/32-inch plywood to meet project requirements to satisfaction.of Authority Having Jurisdiction.
Base Sheet:
Elastobase (sanded top surface. for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners:
Simplex MAXX Cap Fasteners
Spacing:
9-inch o.c. at the 2-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows.
G, torch
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt.or Polyflex -applied.
#14. Maximum Design Pressure = -52.5 psf:
Deck:
Min:15/32-inch'plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet:
Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: Simplex Original Cap Nails
Spacing: 6-Inch o.c. at the 3-inch wide'side laps and 6-inch o.c. at four (4) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TO P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
NEMO ETC, LLC. Evaluation Report P12060.02.09-1124
Certbkate ofAuthpdzation #32455 a EDITION (2017) FBC NON-HVHZ EVALUATION _ FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2028
j - - Page-8 of 14
NEMO I etc.
#15 Maximum Design Pressure = -52.5 DO:
beck:
Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet:
Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners:
SimplexOriginal.CapNails
Spacing:
6-inch o.c. at the 3-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#16 Maximum Design Pressure = -60 Dsf:
Deck:
Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet:
Elastobase (sanded top surface.for hot -asphalt or torch -applied cap or poly-fllm surface for torch -applied cap)
Fasteners:
11 ga. x 1.25-inch long x 3/84nch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
Spacing:
8-inch o.c. at the 4-Inch wide side laps and 8-inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex GTU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#17 MaximumDesign Pressure = -60 Dsf:
Deck:
Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet:
Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners:
OMG #12 Standard Roofgrip with OMG Flat Bottom Metal Plates .
Spacing:
12-inch o.c. at the 4-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied -in full mopping of hot asphalt or Polyflex G, torch -applied.
#18 Maximum Design Pressure = -67.5 nsf:
Deck: Min. .15/324nch'plywood to meet project requirements to satisfaction of Authority.Having Jurisdiction.
Base Sheet: Polyglass G2.Base or Polyglass APP Base (requires use of torch -applied underlayment)
Fasteners: 12 ga: x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
Spacing:• 8-inch,o.c. at the 4-16ch wide side laps and 8-inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Elastoflex G TU.or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
#19 Maximum Design Pressure = 75 Dsf
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Polyglass G2. Base or Polyglass APP Base (requires use of torch -applied underlayment)
Fasteners: Dekfast #14 with Dekfast Hex plates, CMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with
OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAXX Cap
Fasteners
Spacing: 10-inch o.c. at the 4-inch wide side laps and 10-inch o.c. at three (3) equally spaced staggered center rows,
Underlayment: Elastofexc G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
#20 Maximum Design Pressure = -90 Dsf:
Deck: Min. 15/32-inch plywood to meet'project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 6-inch o.c. at the 2-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows.
Underlavment:. Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied.
#21 Maximum Design Pressure = -90 Dsf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt ortorch-applied cap or poly -film surface for torch -applied cap)
Fasteners: 0MG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal
Plates
Spacing: 6-inch- o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G,, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#22 Maximum Design Pressure = -UU DST:
Deck: Min:15/32-inch plywood to meet project requirements to satisfaction of'Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface)
Fasteners: Trufast #12 DP or Trufast #14 HD with Trufast3" Metal Insulation Plates
Spacing: 6-inch o.c. at'the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows:
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt.
NEMO ETC, LLC I Evaluation Report P12060.02.09 R24
Certificate ofAuthorizatton #32455 6EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
i
Page 9 of 14
I
i
f0NEM0 etc.
#23 Maximum Design Pressure = -90 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
ease Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment)
Fasteners: Dekfast #14 with Dekfast Hex plates,. OMG #14 HD with CMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with
CMG Flat Bottom Plates (AccuTrac),.Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAXX Cap .
Fasteners
Spacing: 9-inch o.c, at the 4-inch wide side laps and 9-inch o.c. at four (4). equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex 56 G, applied. in full mopping of hot asphalt or torch -applied or Polyflex G,-torch-
applied.
#24 Maximum Design Pressure =-97.5 psf:
Deck:. Min.19/32-inch, plywood to. meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: 11 ga. x 1.25-Inch x 3/8-Inch head diameter annular ring shank roofing nails at 1-5/871nch diameter tin caps
Spacing: 4-inch o.c. at the 4-Inch wide side laps and 4-inch.o.c. at four (4).equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment:. Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
#25 Maximum Design Pressure = -105 W.
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 6-inch o.c. at the 2-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows,
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or, Polyflex G, torch-applied-
#26 Maximum Design Pressure = -112.5 psf:
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority'Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: 11 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
Spacing: 6-inch o.c, at the 4-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows.
Primer: P6100 or ASTM D41 primer at all tin -caps
Base Ply: Polystick MTS or Polystick MTS PLUS, self -adhered
lnderlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA APP Cap Sheet (FR), self -adhered.
#27 Maximum Design Pressure = -120 psf:
Deck:. Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase.(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners:, CMG #12 Standard, Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal
Plates .
Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#28 Maximum Design Pressure = -120 psf:
Deck: 'Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface)
Fasteners: Trufast #12 DP or Trufast #14 HD with Trufast 3" Metal Insulation Plates
Spacing: 6-inch.o.c. at the 4-inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows.
tnderlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt.
5.6.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on tile systems carry a Maximum
Design Pressure of -45 psf.
NEMO ETC, LLC, i Evaluation Report P12060.02.09-R24
Cerrlticate ofAuthorization #32455 e" EDITION (2017) FBC NON-WH2,EVALUATION FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 10 of 14
t.o-NEM0j,etc'.
5.6.4.2 For mechanically'attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed
that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A..
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design
pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density
designed; by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are
ANSI/SPRI WD1, FM Loss Prevention Data.Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked
with an asterisk's carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January
2016) for Zone 2/3 enhancements:
5.7 Exposure Limitations:
Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APR Base shall not be left exposed for longer than 30-days
after installation.
Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after Installation.
Polystick MTS, (NITS PLUS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastoflex G.TU shall not be left exposed for
longer than 180-days after installation.,
Polyflex SAP or SAP' FR, or Mule -Hide SA-APP Cap Sheet. or SA-APP Cap Sheet (FR). does not have an .exposure
limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30
days.
Elastoflex S6 G or Elastoflex S6 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the
prepared roof covering is,to be adhesive -set tile (Elastoflex S6 G or Polyflex G only), in which case the maximum
exposure is 190 days.
5.8 {Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226
roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as
set forth in Section 4.3, Note 1 of ASTM D1970-15, should be established as to slip resistance.
5.9 Tle Slippage Limitations (FRSA/TRI April 2012 (04-12)):
jWhen loading roof tiles on the underlayment in direct -deck Mile assemblies, the maximum roof slope shall be as
!follows. These slope' limitations can only be exceeded by using battens during loading of the roof tiles.
TABLE 2: TILE,SLIPPAGE LIMITATIONS FOR DIRECT• DECK TILEINSTAWITIONS..
Underlayment
Tile Profile
Staging Method
Maximum Slope
I
Elastoflex G TU
Flat
10-tile stack
7:12
Lugged
8-tile stack (6 over 2)
6:12
Elastoflex S6 G or S6 G FR
Flat or Lugged
&tile stack (4 over 2) -
4:12
Polystick MTS or MTS PLUS
Flat
6-tile stack (4 over 2)
5:12
Lugged
6-tile stack (4 over 2)
4:12
Polystick Tle Pro
Flat or Lugged .
6-tile stack (4 over 2)
7:12
Polystick TIU Max
Flat
6-tile stack (4 over 2) or 10-tile stack
7:12
Lugged
6-tile stack (4 over 2)
7:12
Lugged
10-tile stack
6:12.
I
PolystickTU P
Flat
6-tile stack (4 over 2)
6:12
Lugged
6-tile stack (4 over 2)
4:12
I
Polystick TU Plus
Flat or Lugged
6-tile stack (4 over 2) ,
7:22
Flat or Lugged
10-tile stack
6:12
Polyflex.Glor G FR
Flat or Lugged.
6-tile stack (4 over 2)
.4:12
Polyflex SA P or SA P FR
Flat or Lugged
6-tile stack (4 over 2)
4:12
NEMO ETC, LLC .
Certirnte of AotA0d..t1a11 #32455
If" EDITION (2017) FBC NON-HVHZ EVALUATION'
Polygiass Roof Underlayments; (954) 233-1230
Evaluation Report P32060.02.09-1124
FL5259-R28
Revision 24: 01/24/2018
Page 11 of 24
O,NE . mo'j etc.
6. INSTALLATION:
6.1 Polyglass.Roof Underlayments shall be installed in accordance with Polyglass published installation requirements
subject to the Limitations set forth in Section 5 herein and the specifics.noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove .
any. dust and debris.prior to application, and prime the substrate (if applicable).
16.3` Elastobase Elaid ase P or:Mule-HIde'Nail:Base:..
6.3.1 Non -Tile Applications:
Shall be installed in compliance with the codifled .requirements for ASTM D226, Type 11. underlayment in FBC Table
1507.1.1 for the type of prepared roof covering.to be installed.
Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polystick, Polyflex SAP, Polyflex SA
P FR, Mule -Hide -SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastoflex G TU, Elastoflex S6 G or
Elastoflex S6 G FR in hot asphalt or Polyflex G or Polyflex G FR, torch applied. Roof cover limitations are those are
those associated with the top -layer underlayment, es set forth in Table 1..
6.3.2 Tile Applications:
Elastobase, Elastobase P or Mule -Hide Nail Base -are limited to use as a mechanically attached base sheet in the `Two.
i
Ply System" from FRSA/TRI April 2012 (04-12). Reference is made to Table 1 and Section 5.6.4 herein, coupled with
FRSA/TRI April 2012 (04-12) Installation Manual
6.4 Polystick MTS, MTS PlUS,1R=Xe, TU :P, TU Plusy TU Max, Dua( Pro, -Tile Pra or MU X or Polyflex SAP, PolyfleX SAP FR; I
..• .
Mule -tilde SA APP Cap Sheet or M61 Hide SA APP Cap Sheen{pR)
6.4.1 Shall be installed in compliance with the codified requirements for ASTM D1970.(except Polystick TU P) underlayment
In' FBC Table 1507.1A for the type of prepared roof covering to be installed.
6.4.2
All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP OR and Mule -Hide SA-APP
Cap Sheet or SA-APP Cap Sheet (FR) should be back -nailed in selvage edge seam in. accordance with Polyglass / Mule -
Hide back nailing guidelines. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 1-inch
diameter metal disk or Simplex -type metal cap nail; at. a minimum rate of 12" o.c.' Polystick TU Plus should be back -
nailed using the above noted fasteners and spacing, in area marked "nail area, area para claval" on the face of
membrane. The head lap membrane is to cover the area being back -nailed.
All seal -lap seams (selvage laps) must be
firmly rolled with a minimum 28 lb. hand
roller to ensure full contact and adhesion.
For Dual Pro and Tile Pro, align the edge of
the top sheet to the end of the,glue pattern
(the sheet will overlap the fabric).
View of Ovelap Seam of Dual Pro and Tile Pro
All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus-50 Premium Modified .
Wet/DryCement or,Polyglass PG500 Modified Cement applied in between the application of the lap.
Polystick TU Plus, Dual Pro and Tile. Pro may not be used in any exposed application such as crickets, exposed valleys,
Or exposed roof.to wall details
NEMO:ETC, LLC. Evaluation Report P12060:02.09-R24
Cert/jlcate of Authorization #32455 a EDITION (2027) FBC NON-HVHZ EVALUATION FL5259-RZB
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 12 of 14
6.4.3
fONEMOjetc.
lair of Polystick membranes is to be accomplished by applying Polyplus 50 PremiumModified Wet/Dry Cement or
yglass PG500 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 inch patch of the
ystick material of like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be
:alled in a water shedding manner.
Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a
iimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 40-lbs of load applied
the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28 lb roller) or small areas of the
f that are not accessible to a large roller or broom.
!rence is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions
ad above as a guideline.
mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base
et fastening shall be not less than FRSA/TRI April 2012 (04-12), Table 1.
adhesive -set tile applications, refer to Section 5.6.4 herein.
6.4.4 Two (2) Ply Underlayment Systems:
PIalystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Polyflex
SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with
the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired.
P� lystick MTS or MTS PLUS followed by Polystick TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use
under foam -on tile systems. Limits of use are those associated with the top -layer material. This is not a requirement,
brut is allowable If a 2-o1v underlavment system is desired.
6.5.1 Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be installed in compliance with current Polyglass published
installation requirements. For use in tile applications:
✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single
Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or
adhered tile roof systems.
Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply
System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or
adhered tile roof systems.
Elastoflex S6 G FR is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single
Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap -Sheer in the `Two Ply System" from FRSA/TRI April 2012 (04-22) beneath mechanically fastened tile
roof systems.
6.5.2 For hot -asphalt -applications, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be fully asphalt -applied to the
substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-inch wide, off -set
minimum 3 feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt
I
ith asphalt extending approximately 3/8-inch beyond the. lap edge.
6.6 PolyFlex G orPolyflex G FR
6.6.1 P� Iyflex G or Polyflex G FR shall be installed in compliance with current Polyglass published installation requirements.
For use in tile applications:
Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April
2012 (04-12) beneath mechanically fastened or adhered tile roof systems (Base Sheet Limited per 5.6.3).
Polyflex G FR is for use as an alternate to the Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI.
April 2012 (04-12) beneath mechanically fastened tile roof systems (Base Sheet Limited per 5.6.3).
NEW ETC, I.I.C. Evaluation Report P12060.02.09-R24
Certryrcate ofAuthodiatian #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-RZS
j Polyglass Roof Underlayments; (954) 233-2230 Revision 24: 01/24/2018
Page 13 of 14
N
8.
ONEMO etc.
6.6.2 Polyflex G or Polyflex G FR shall be fully torch -applied to the substrates noted In Section 5.6. Side laps shall be
minimum 3-Inch and end -laps minimum 6-Inch wide, off -set minimum 3 feet from course to course. Side and end
laps shall be fully heat -welded and respected to ensure minimum 3/8-inch flow of modified compound beyond the lap
edge.
6.7 T)le Staging:
i
6.7.1 Tie shall be loaded and staged In a manner that prevents file slippage and/or damage to the underlayment: Refer to
Table 2 herein, and Polyglass published requirements for tile staging.
6.7.2 Battens and/or Counter -battens, as required by the tile. manufacturer and FRSA/TRI April 2012 (04-12) must be used
0o all roof slopes greater than 7:12. Precautions should be taken .as needed, such as the use of battens or nail-
boards,•to prevent file siiding-and/or damage to the underlayment during the loading process.
6.7.3 Polyglass specifies the .minimum cure time after installation of self -adhering membranes and before loading of
roofing tiles is forty-eight (48) hours.
BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product.
MANUFACTURING PLANTS:
Contact the noted QA agency for information on product locations covered for F.A.C. 61G20-3 QA requirements. The following
plants havel qualified products under their respective physical properties specifications.
.Plant<.. �.. .. :.. ;:
Soeciflcatlon :.:° .. ..... ..: ....
Product s ;..:... :.
Fernley, NV; Hazleton, PA & Winter Haven, FL
ASTM D1970
Polystick MU-X
Hazleton, PA
M-D 13-0004.
Elastoflex G TU
Hazleton, PA & Winter Haven, FL
ASTM D1970
Polystick IR-Xe
ASTM D1970 & FRSA/TRI April 2012
'Polystick TU Plus
ASTM D1970 & FRSA/TRI April 2012
Polystick TU Max,
Tuscaloosa,; AL
ASTM D4601, Type II
Polyglass G2 Base
{ .
Winter Haven, FL
I
1
ASTM D226 (physicals)
Elastobase, Elastobase P
ASTM D6509
Polyglass APP Base, - .
FRSA/TRI April 2612
Polystick MTS, Polystick MTS PLUS
FRSA/TRI April 2012
PolystickTU P
FRSA/TR1 April 2012
Polyflex SAP, Polyflex SA P FR
ASTM D1970
Polystick Dual Pro
ASTM D1970.& FRSA/TRI April 2012
Polystick Tile Pro
ASTM D6164
Elastoflex S6, Elastoflex S6 G FR
ASTM D6222'
Polyflex G, Polyflex G FR
9. QUALITYASSURANCE ENTITY:
UL, LLC—QPA9625; (314) 578-3406; k.chancellor@us.ul.com
END OF EVALUATION REPORT -