HomeMy WebLinkAboutSCREEN ENCLOSUREDesign Parameters 1. Building Occupancy Category, Paragraph 1604.5 and Table 1604.5: Risk Category 1. 2. Basic Wind Speed, Table 1609C, State of Florida Debris Region & Basic Wind Speed, Paragraph 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Speed, VuLT=150 MPH Exposure Category, Paragraph 1609.4.3 : B Applicable Codes, Regulation and Standards 1. The 6th Edition (2017) Florida Building Code, specifically Chapter 16 Structural Design, Chapter 20 Aluminum, and Chapter 23 Wood. 2. AA ASM 35 and Specifications for Aluminum Structure, Part 1-A of the Aluminum Design Manual prepared by The Aluminum Association, Inc. Washington, D.C., 2010 Edition 3. ASCE 7-10 General Notes: 1. The contractor shall verify all dimensions prior to construction 2. All work shall comply with all local and regional ordinances. 3. Any deviation from this plan shall be reviewed by the engineer of record and is subject to approval. Specifications The following specifications are applicable to this projects: 1. Where concrete specification are required, whether in the screen enclosure scope or not, by one or more regulatory agency, the following specifications are applicable. 1.1. Concrete shall conform to ASTM C94 for following components: 1.1.1. Portland Cement Type 1, -ASTM C 150 1.1.2. Aggregate - Large Aggregate 3/4" max - ASTM C 33 1.1.3. Air entraining +/-1 % - ASTM C 260 1.1.4. Water reducing agent - ASTM C 494 1.1.5. Clean Potable water - 1.1.6. Other admixture not permitted 1.2. Metal accessories shall conform to: 1.2.1. Reinforcing Bars - ASTM A615, grade 60 1.2.2. Welded wire fabric - ASTM A185 1.3. Concrete slump at discharge per chute not less then 3" or more than 5". Water added after batching is not permitted. 1.4. Prepare and place concrete per American Concrete Institute Manual of Standard Practice, Parts 1, 2 and 3 including hot weather recommendations. 1.5. Moist cure or polyethylene curing permitted. 1.6. Prior to placing concrete, treat the entire subsurface area for termites in compliance with the FBC. 1.7. Concrete shall be placed over polyethylene vapor barrier. 1.8. All aluminum components embedded within concrete shall be coated with a bituminous paint or epoxy. 2. Aluminum extrusions shall be 6005 T5 Alloy. 3. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc plate to ASTM B633, or stainless steel series "300". 4. All Self Mating Beam Sections are to be stitched with either #14 screws 6" from end 24" on center or #12 screws 6" from end 12" on center. 5. Screened enclosures containing swimming pools shall comply with the applicable requirements of FBC R4501.17 Residential Swimming Barrier requirements. 6. Door location shall be determined by contractor in the field. 7. When installing pavers over concrete slab or footing which are supporting aluminum members, such as continuous screen tracks or upright, the pavers must be bonded to the concrete with an epoxy, thinset, or 3,000 PSI grout to ensure full positive contact with concrete. 8. All flashing and waterproofing shall be provided by the contractor. 9. Use of these plans acknowledges and accepts a limit of liability not to exceed design and engineering fee. Foundation Design: Existing 8"x8" Footer and 4" Slab Existing concrete. No additional concrete footing is required to resist the loads imposed by the proposed construction if the existing footing is in sound condition, free from structural cracking, spelling, or other deterioration. Roof Type Screen Size MANSARD 18 114 MESH ALUMINUM MEMBERS DIMENSIONS HOLLOW SECTIONS SELF MATING BEAM (SMB) THE PORCH FACTORY BEAM (PFB) 3.75PFB: 2"x3.75'x0.D50" 2 x2: 2"x21xa046" 2x4SMB: 20x4"x D.044" x 0.100" 2 x 3: 2"x 3"x 0.050' 2%SSMB: rx5" x a.050"x0.100" 5.75PFB: rx5.75'x0.055" 2x 4: rx 4'x 0.050' 2x6SMB: 2"x6"x 0.050'x 0.12T 6.75PFB: 21x6.75"x0.057" 2x5: 2'x5"x0.050" 2x7SMB: 2"xrx0.057"x0.120" 2x6SMB: Tx8'x0.072"x0.124- 2x8 SMB: r x G1x0.D721x0.124' KB: KNEE BRACE OPEN BACK SECTIONS 1 x2: 11x 2"x D.040" 2 x 10 SMB: 2"x In0.09r x 0.388" 1 x3: 11x3"x0.045" MINIMUM FASTENER EDGE DISTANCE: MINIMUM FASTENER SPACING: 314" Ire SNAP SECTIONS 2x2Snap: 2'x2"x0.045" CONCRETE SCREW ANCHOR: SHEET MATEL SCREWS(SMS): 2x3Snap: 2"x3"x0.050" 2x48nap: 2x4"x0.045" SIMPOSONTITENHDOREQUIVALENT rWBUILDEXOR EQUIVALENT THESE PLANS AND ALL PROPOSED WORK ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT MAY oBE NECESSARY IN ORDER TO �CI`,�, (ld ITH ALL APPLICABLE CODES. FILE COPY CONCEALED FASTENERS OR ATTACHMENTS ARE THE RESPONSIBILITY OF THE CONTRACTOR OR RECORD IN DIFFERENT LOCATION. MAINTAIN ANGLE PER DETAIL. ED NOV 0 5 2018 5T, w0f., SCra® SCAM �Q Lu�i.C®ulaw nty REVISIONS G1 W NN C J CO) m >` Co ♦ IX N OO to -err a a M IX -J LL - r !0 Z2 c)uEio 0 p LL W W p m � Z LLI 0 W r it y M 'L+ W LL V m CO) a naodhooftfift. No. SHEET A-1 '*NOTE - NOT ALL DETAILS ARE USED FOR THIS PROJECT. SEE PLAN FOR DETAIL CALL OUTS— 1/8" x 2' x 2" EXTRUDED (4) #14 x 3!4"SMS \ 1/8" S.S. CABLE O INTO POST ANGLE 5052 H-32 ALLOY441A 1 114' x 5 5/8" x 118' ALUM. O FLAT -BAR.. 606348ALUNY. °RICK -PAVERS (2) 319" DIA. x 2 3/4" DBL COMPRESSION SLEEVES EMBEDMENT CONCRETE ANCHORS BONDEDTO CONCRETE (9) #14 x 3/4" SMS / 0 m'6063-T6ALUMINUM i=Z 1!8" PLATE ON 45° ANGLE / / BRICK PAVERS. MAY NOT BEWvSLAB/FOOTING PRESENT. FOLLOW ° • e p SEE PLAN a a' - d w / / ANCHOR MINIMUM '•• .,. U • e .d -'• d U CONCRETE EMBEDMENT - O O O O a SIDE VIEW — ___ _ SLAB/FOOTING --- - — O SEE PLAN (4) #14 x 3/4" SMS 2° x 2" DJ EYE BOLT FOR 0 BRICK PAVERS. MAY NOT BE INTO POST CABLE TENSION % 1/B° S.S. CABLE PRESENT. FOLLOW CONCRETE S SCRERE W ANANCHORS _ A ANCHOR MINIMUM (2 1/2" CONC. EMBED) I ��Q 11/4°x55/8'x1/8"ALUM. CONCRETE EMBEDMENT pip FLAT BAR.6063-T6 ALUM. 1"x 2" BASE PLATE INANCHORED TO CONC W/ 114" PERIMETER a • • e ., • CONCRETE SCREW ANCHOR FRAMING I I • • d •� . q • c (MIN. 1 1/4" EMBED) •° . , , O • a 6" MAX EACH SIDE OF POST I • - AND 24' O.C. MAX -' :e d (2) 3/8" DIA. x 3" EMB SLAB/FOOTING FRONT VIEW -- CONC. SCREWANCHOR SEE PLAN DJ-1 DOOR JUMB TO CONCRETE W/PAVERS DETAIL H-2 CABLE CONNECTION AT CORNER H-1 CABLE CONNECTION AT FOUNDATION A-2 SCALE:NTS A-2 SCALE:NTS A-2 SCALE:NTS CORNER POST (2) #10 x l l/2" SMS THRU SCREW BOSSES BRICK PAVERS. MAY NOT BE PRESENT. FOLLOW ANCHOR MINIMUM CONCRETE EMBEDMENT SLAB/FOOTING • d SEE PLAN SIDE VIEW (4) #14 a INTO PC 1"x 2' BASE PLATE ANCHORED TO CONC W/ 1/4" CONCRETE SCREW ANCHOR (MIN. 11/4" EMBED) 6" MAX EACH SIDE OF POST AND 24" O.C. MAX 1"x 2" O.B. FASTENED TO CORNER POST W/ #12x11/2" SMS AT 6" FROM TOP & BOTTOM RAILS. TYPICALLY @ 24" O.C. 1/8" x 2" x 2" EXTRUDED ANGLE 5052 H-32 ALLOY EA CORNER WI (2). #14 x 2" SMS INTO POST & (1) 3/8" DLA. CONCRETE SCREWANCHOR INTO CONCRETE t U W U W zM �w �o �• x N m CONCRETE POST W/ 1-X2" @ BACKSIDE 3/6" x LENGTH AS REQUIRED �— FOR 21/4" EMBED CONCRETE SCREW ANCHOR INTO CONCRETE FRONT VIEW CP-1 CORNER POST TO CONCRETE W/PAVERS DETAIL A-2 SCALE:NTS 1/8"X2"X2" EXTRUDED I I (1) 112' DIA THRU BOLT w/NYLOCK ANGLE 5052 H.32 ALLOY JAM NUT -IN LIEU OF NYLOCK JAM EA SIDE NUT. JAM NUT WITHREADLLOCKER - MAY BE USED BRICK PAVERS TIGHTEN TO CONTACT. DO NOT OVER TIGHTEN BONDED TO CONCRETE • .. a BRICK PAVERS. MAY NOT BE d' PRESENT. FOLLOW n �• ANCHOR MINIMUM • S CONCRETE EMBEDMENT i •. a ' SLABIFOOTING ° •, d . - :° • . SEE PLAN a. a .' ' n E (4)#10xI1PL"SMS SCREW BOI SIDE VIEW SNA (1) 318" DIA CONCRETE SELF -MATING I 1 SCREWANCHORS I TI— BRICK PAVERS rid' BASE PLATE ANCHORED TO CONC W/ 114" CONCRETE SCREW ANCHOR (MIN. 1 114- CONC. EMBED) 6" MAX EACH SIDE OF POST .Q SLAB/FOOTING SEE PLAN a -• A .° �\ FRONT VIEW B \ 2" x 4" OR LARGER UPRIGHT TO CONCRETE W/PAVERS DETAIL p_2 /SCALE:NTS (EMBER C PURLIN OR GIRT BEAM OR POST DETAIL A-2 SCALE:NTS c o REVISIONS m W " c J W /� > f� w♦ l N 0��� .J E c Z AaY o LLj aa10® W p m Z I- -' IL WJA W jcLOL v L) d "O a Cana NO. A-2 j 'NOTE - NOT ALL DETAILS ARE USED FOR THIS PROJECT. SEE PLAN FOR DETAIL CALL OUTS' 6" WIDE x 0.125" 'Z" BRACKET @ EAC NOTE: BEAM ATTACHED TO FASCIA W/ 318 x (2) 3/8" DW x 4° LAG SCREWS FOR 3" LAGS (3 PER BRACKET) AlD (1) 3/8° SPANS GREATER THAN 30'-0" X 3" LAG @ 24° O.C. AT GUTTER NOT NEEDED IF GUTTER HAS SPLIN GROOVE. OTHERWISE, 1"x 2" x 0.044" OPEN BACK W/ (2) 010 x 212°SMS THRU BEAM INTO SCREW BOSSES (1) #10 x 112" SMS 6"� FROM BEAM AND 24" O.C. MATING ELEMENT CONTRACTOR TO VERIFY p 2" x 4" FASCIA- IF LESS 1/8"x2"x2"x2"ALUM. p p THAN 2"x 4" FASCIA, 2"X 4" ANGLE W/ (4) #14 x 3/4" SUB FASCIA SHALL BE SMS EACH FLANGE 5" SUPER PLACED OVER, LENGTHEN EACH SIDE OF BEAWPURLIN GUTTER LAG SCREWS TO FULLY PENETRATE SUB FASCIA, IF OTHER FASCIA, ADD 2" x 4" PT FASCIA w/ 12" LAG BOLTS -112" INTO TRUSS WHEN BEAM/PURLIN IS LARGER THA .062" BACKING PLATE TAILS - COUNTERSINK GUTTER, 21/8" x 1 1/8" x 0.062" (MIN.) ON INSIDE OF GUTTER FLUSH. WHEN INSTALLING ALUM RECEIVING CHANNEL W/ MIN. (2) 12" LAG SCREWS. #12 x 3/4" SMS PRE-DRILLWl3/8" DRILL TO PREVENT SPLITTING G GUTTER BRACE & MATING ELEMENT ATTACHMENT DETAIL A-3 SCALE: NTS MEMBERSIZE EDGE"C" 2X4 12" 2X5 2X6-2X10 112• FLASHING EAVE RAIL (SEE A-1 FOR SIZE) INTERNALLY SCREW THRU BEAM W/(3) #10 x 112" SMS 1"x FASTEN TO EAVE RAIL W/ # 10 x 112" SMS 6" FROM UPRIGHT & 24" O.C. (1)12" DIA. x 21/2" THRU BOLT W/ NYLOCK JAM NUT - IN LIEU OF NYLOCK JUM NUT. JAM NUT W/ THREADLOCKER MAY BE USED INSTALLATION REQUIREMENTS: BOLT IS TO BE INSTALLED AS TO NOT DAMAGE BASE MATERIAL DO NOT OVER TIGHTEN. 2"x SMS BEAM NOTCHED OVER UPRIGHT (SEE A-1 FOR SIZE) WOOD: #10 x 3• WOOD SCREWS, 6" FROM-GIRT_&.@a 2"_O.0- CONC. 1/4" DIA. x 3" CONCRETE SCREW ANCHOR, 6" FROM GIRT & @ 24" O.C. (4) #10 x 112" INTO SCREW BOSS 2" x HOLLOW SECTION GIRT OR PURLIN 1"x 2" C-1 1M TO HOST STRUCTURE DETAIL A-3 SCALE: NTS x 2" HOLLOW SECTION #10 x 3" WOOD SCREWS, 6" FROM GIRT & @ 12" O.C. CONC. V4" DIA. x 3" CONCRETE SCREW ANCHOR, 6" FROM GIRT & @ 24" O.C. Note - Orientation may be different. 3/16" 5052-H32 GUSSET #14 SMS @ 11/4° O.C. 2" x PURLINS ATTACHED TO — BEAM W/MIN (4) #10 x 112" SMS PLACE WASHER UNDER SCREW IN GLIBBEST CORNER 2" x SMS UPRIGHT (SEE A-1 FOR SIZE) NOTES: 1. SEETHE NOTE BELOW FOR SCREWS SPACING. THE NUMBER OF SCREWS SHOWN ARE FOR ILLUSTRATIVE PURPOSES. DO NOT COUNT SCREWS ON DRAWING. 2. GUSSET DIMENSIONS AREA MINIMUM (2) REQ'D - (1) EA SIDE OF BEAM - MAY BE INTERNAL OR EXTERNAL 3. AS BEAM SIZE CHANGES, ADD OR SUBTRACT SCREWS TO MAINTAIN 11/4" C/C SPACING. 4. GUSSET LENGTHS REMAIN CONSTANT WIDTHS CHANGE TO MATCH BEAM SIZE. UPRIGHT TO BEAM CONNECTION A-3 SCALE: NTS E TYPICAL INTERNAL OR EXTERNAL GUSSET DETAIL- RIGID MEDIUM A-3 SCALE: NTS GUSSET PLAT PER ESERIES DETAIL #2 DETAIL #1 SELF MATING BEAM CONTRACTOR TO INSTALL (2) #14 x 2" SMS THRU BRACE INTO BEAM THRU GUSSET NTRACTOR SHALL RUN THRU BOLT TO ATTACH NYLON WASHER & kINLESS STEEL NUT �' 3 ROOF BRACING CONNECTION DETAIL A-3 SCALE: NTS 2 x PURLIN - NOTCH BOTTOM FLANGE TO OVERLAP UPRIGHT EAVE RAIL INTERNALLY SCREWED THRU UPRIGHT WITH (3) #10 x 2" SMS INTO SCREW BOSSES 1"x 2" x 0.044" OPEN BACK INTERNALY- SCREW TO UPRIGHT W/ (2) 010 x 112" SMS & FASTEN TO EAVE RAIL W/ #10 x 112" SMS SPACED 6" FROM UPRIGHT AND AT 24" O.C. 1/8" x 2" x r 6063-T6 ALUMINUM STRAP - WITH (2) #10 x 5/8" SMS EACH SIDE OF BEAM F SLOPED PURLIN CONNECTION DETAIL A-3 SCALE:NTS REVISIONS UP No. A-3 NT LUCRE COvN I r, rLurclu y f`3 ..�t0 T V VACANT ul k.' Q 19.4 T 19.5 y %7YEA SEMENT 565.83' EASEMENT S 8903936" W J 1 6'.2OAK EXISTING } POND 2'0f a-? 20,34 F 8' OAK f 2 t x 20.3 � t f4 � LOTsa*{S #"N.,TTTT- Wz 4 ala r r r¢• "' lJ%V�ER CONSTRUCTI01' g o PROPOSED MINIMUM a2 a0 FFE ! 25.0' w &0 �33' p 0 2Z"' n ND >d ON W.67• 22 00 s 1`.. 19.4 \19.7 I) . 20.3 194 ASEMENT 563.32' AS ME — — — — 89'.3.937 .3 4W 25' T57-!*"-- cap 2013 "L x 20.3 x 20,3'> 5' FARM FENCE 20.37 8' OAK FILE CO