HomeMy WebLinkAboutLETTER ABOUT SPRINKLER SYSTEM1nr.I IPH T- LATERZA - CONSULTING ENGINEER STRUCTURAL PROFESSIONAL MART BUILDING SUITE 108 C I V I L 3923 LAKE WORTH ROAD LAKE WORTH, FLORIDA 33461 PHONE: 968-1333 Plan Review St. Lucie Building and Zoning 2300 Virginia Ave. Ft. Plierce, Fl. • Feb. 21, RE: WarerSo.!M:ar:k�etAve. 4127 Ft. Pierce, A review of the above referenced project, utilizing Table 400 and the area modification formula in section 402.3.2 of the Standard Building Code, indicates that a sprinkler system is not required for this building. Calculations: I=4/3[100(F/P-0.25)] I=4/3[1Q0(495/590-0.25)] I=78o51 16,000sq.ft. + 78. 1% = 28,561.6 sq.ft. do d o ph T., L-aterza, .E Consulting Engineer 1990 4r{„ 1