HomeMy WebLinkAboutENERGY EFFICIENCY CODE CHECKLISTFORM R405-2017
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2017 Florida Building Code, Energy Conservation via the
residential Simulated Performance Method shall include:
This checklist
SCANNEV
BY
St Lucie County
El A Form R405 report that documents that the Proposed Design complies with Section
R405.3 of the Florida Energy Code. This form shall include a -summary page
indicating home address, a -ratio and the pass or fail status along with summary
areas and types of components, whether the home was simulated as a worst -case
orientation, name and version of the compliance software tool, name of individual
completing the compliance report (one page) and an input summary checklist that can
be used for held verification (usually four pages/may be greater).
I,' Energy Performance Level (EPL) Display Card (one page)
HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
2" Mandatory Requirements (five pages)
Required prior to CO for the Performance Method:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 -
one page)
❑ A completed Envelope Leakage Test Report (usually one page)
i
❑ If Form R405 duct leakage
g type indicates anything other than "default leakage" then a completed
j Form R405 Duct Leakage Test Report (usually one page)
I �C(j — i)c)g 9
8/M/2018 10:57:08 AM EnergyGauge@ USA 6.0.02 - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
FORM R405-2017
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
' Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: RENAR BERMUDA 1796
Builder Name: RENAR HOMES
Street: i 9312 WINDRIFT CIRCLE
Permit Office: FT PIERCE
City, State, Zip: FT PIERCE, FL,
Permit Number:
Owner:
Jurisdiction: 661100
Design Location: FL, Fort Pierce
County: St. Lucie (Florida Climate Zone 2 )
1. New con struction or existing New (From Plans)
9. Wall Types (1672.0 sqft.)
Insulation Area
2. Single family or multiple family Single-family
a. Concrete Block - Int Insul, Exterior
R=4.2 736.00 ft2
b. Concrete Block - Int Insul, Exterior
R=13.0 488.00 ft2
3. Number of units, if multiple family 1
c. Concrete Block - Int Insul, Exterior
R=4.1 360.00 ft2
4. Number of Bedrooms 4
d. other (see details)
R= 88.00 ft2
10. Ceiling Types (2205.0 sqft.)
Insulation Area
5. Is this alworst case? No
a. Under Attic (Vented)
R=30.0 2205.00 ft2
6. Conditioned floor area above grade (ft2) 2205
b. N/A
R= ft2
Conditioned floor area below grade (ft2) 0
c. N/A
R= ft2
11. Ducts
R ft2
7. Windows(319.3 sqft.) Description Area
a. Sup: Attic, Ret: Attic, AH: Garage
6 131
a. U-Factor: Sgl, U=0.54 266.00 ft2
SHGC: SHGC=0.25
b. U-Factor: Sgl, U=0.61 53.33 ft2
12. Cooling systems
kBtu/hr Efficiency
SHGC: SHGC=0.23
a. Central Unit
34.2 SEER:14.00
b. Central Unit
17.2 SEER:19.20
c. U-Factor: N/A ft2
SHGC:
13. Heating systems
kBtu/hr Efficiency
d. U-Factor: N/A ft2
a. Electric Heat Pump
33.8 HSPF:8.20
SHGC:
b. Electric Heat Pump
21.6 HSPF:9.50
Area Weighted Average Overhang Depth: 1.333 ft.
Area Weighted Average SHGC: 0.247
14. Hot water systems
a. Electric
Cap: 40 gallons
8. Floor Types (2205.0 sqft.) Insulation Area
EF: 0.920
a. Slab -On -Grade Edge Insulation R=0.0 2205.00 ft2
9
b. Conservation features
b. N/A R= ft2
None
c. N/A R= ft2
15. Credits
Pstat
i
Glass/Floor Area: 0.145 Total Proposed Modified Loads: 67.34
PASS
Total Baseline Loads: 70.48
I hereby certify that the plans and specifications covered by
Review of the plans -and
SHE STq��
this calculation are in compliance with the Florida Energy
specifications covered by this
O _ - O
Code.
calculation indicates compliance
with the Florida Energy Code.
BY:
Before construction is completed
��-
DATE- - -
this building will be inspected for
c9 ""'i""�`
compliance with Section 553.908
I hereby certify that this b •Iding, as designe , is in compliance
Florida Statutes.
y�
with the Florida Energy . de.
G'OD WE
�'
OWNER/AGENT:
BUILDING OFFICIAL:
DATE. -
DATE:
I
- Compliance requires certification by the air handier unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.3.2.1.
- Compli Ince requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope Ileakage test report with envelope leakage no greater than 7.00 ACH50 (R402.4.1.2).
8/23/2016 10:57 AM EnergyGauge® USA Section R405.4.1 Compliant Software Page 1 of 5
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title:
RENAR BERMUDA 1796
Bedrooms: 4
Address Type:
Street Address
Building Type:
User
Conditioned Area: 2205
Lot #
Owner Name:
Total Stories: 1
Block/Subdivision:
# of Units:!
1
Worst Case: No
PlatBook:
Builder Name:
RENAR HOMES
Rotate Angle: 270
Street:
9312 WINDRIFT CIRCL
Permit Office:
FT PIERCE
Cross Ventilation:
County:
St. Lucie
Jurisdiction:
661100
Whole House Fan:
City, State, Zip:
FT PIERCE,
Family Type:
Single-family
FL,
New/Existing:
New (From Plans)
Comment:'
CLIMATE
/
Design Temp
Int Design Temp Heating
Design Daily Temp
V Design Location TMY Site
97.5 % 2.5 %
Winter
Summer Degree Days Moisture
Range
FL, Fort Pierce FL_VERO_BEACH_MUNI 39 90
70
75 299
62
Low
BLOCKS
Number
Name Area
Volume
1
Blockl 1796
14368
2
Block2 409
4090
SPACES
Number
Name Area Volume Kitchen Occupants
Bedrooms
InfilID Finished Cooled
Heated
1
Main 1796 14368 Yes 8
4
1 Yes
Yes
Yes
2
SALES 409 4090 No 10
0
1 Yes
Yes
Yes
FLOORS
Floor Type Space
Perimeter Perimeter R-Value
Area
Joist R-Value
Tile' Wood
Carpet
1 Slab -On -Grade Edge Insulatio Main
162 ft 0
1796 ft2
----
0 0
1
2 Slab -On -Grade Edge Insulatio SALES
43 ft 0
409 ft2
----
0 0
1
ROOF
/
Roof Gable Roof
Solar
SA Emitt
Emitt Deck
Pitch
#
Type Materials
Area Area Color
Absor.
Tested
Tested Insul.
(deg)
11
Gable or shed Composition shingles
2388 ft2 458 ft2 Light
0.96
No 0.9
No 0
22.6
ATTIC
V/
#
Type Ventilation
Vent Ratio (1 in)
Area
RBS IRCC
1
Full attic Vented
150 2205 ft2
N N
8/2312018110:57 AM EnergyGauge® USA Section R405.4.1 Compliant Software Page 2 of 5
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
CEILING
F#
Ceiling Type
Space
R-Value
Ins Type
Area
Framing Frac Truss Type
,-
1 Under Attic (Vented)
Main
30
Blown
1796 ft2
0.11
Wood
2 Under Attic (Vented)
SALES
30
Blown
409 ft2
0.11
Wood
WALLS
Adjacent
Space
Cavity Width
Height
Sheathing Framing
Solar Below
0
_ 1
N=>W Exterior
Concrete Block - Int Insul
Main
4.2 38
8
304.0 ft2
0
0.3
0
2
E=>N Exterior
Concrete Block - Int Insul
Main
4.2 44
8
352.0 ft2
0
0.3
0
_ 3
SE=>NE Exterior
Concrete Block - Int Insul
Main
4.2 5
8
40.0 ft2
0
0.3
0
-4
SE=>NE Exterior
Frame - Wood
Main
11 3
8
24.0 ft2
0.5
0.3
0
5
S=>E Exterior
Concrete Block - Int Insul
Main
13 5
8
40.0 ft2
0
0
0.3
0
_ 6
SW=>SE Exterior
Concrete Block - Int Insul
Main
4.2 5
8
40.0 ft2
0
0.3
0
7
SW=>SE Exterior
Frame - Wood
SALES
11 3
8
24.0 ft2
0.5
0.3
0
_ 8
W=>S Exterior
Concrete Block - Int Insul
Main
13 56
8
448.0 ft2
0
0
0.3
0
_ 9
S=>E Exterior
Frame - Wood
Main
11 5
8
40.0 ft2
0
0.5
0.3
0
10
W=>S Exterior
Concrete Block - Int Insul
SALES
4.0999 7
8
56.0 ft2
0 .0.75
0
-11
S=>E Exterior
Concrete Block - Int Insul
SALES
4.0999 19
8
152.0 ft2
0
0.75
0
_ 12
E=>N Exterior
Concrete Block - Int Insul SALES
4.0999 19
8
152.0 ft2
0
0.75
0
DOORS
# Ornt
Door Type Space
Storms
U-Value
Width
Height
Area
Ft
In
Ft In
1 E=>N
Insulated Main
None
.46
3
6 8
20 ft2
WINDOWS
Orientation shown is the entered orientation => changed to As Built rotated 270 degrees).
Wall
Overhang
#1 Ornt ID
Frame Panes NFRC
U-Factor SHGC
Imp
Area
Depth
Separation
Int Shade
Screening
11 N=>W 1
Metal Single (Tinted)
Yes
0.61 0.23
N
53.3 ft2
1 ft 4 in
1 ft 0 in
None
None
2! N=>W 1
Metal Single (Tinted)
Yes
0.54 0.25
N
15.0 ft2
1 ft 4 in
1 ft 0 in
None
None
31 N=>W 1
Metal Single (Tinted)
Yes
0.54 0.25
N
15.0 ft2
1. ft 4 in
1 ft 0 in
None
None
4, E=>N 2
Metal Single (Tinted)
Yes
0.64 0.25
N
15.0 ft2
1 ft 4 in
1 ft 0 in
None
None
5 E=>N 2
Metal Single (Tinted)
Yes
0.54 0.25
N
15.0 ft2
1 ft 4 in
1 ft 0 in
None
None
6 E=>N 2
Metal Single (Tinted)
Yes
0.54 0.25
N
15.0 ft2
1 ft 4 in
1 ft 0 in
None
None
71 SE=>NE 4
Metal Single (Tinted)
Yes
0.54 0.25
N
12.0 ft2
1 ft 4 in
1 ft 0 in
None
None
8 SE=>NE 3
Metal Single (Tinted)
Yes
0.54 0.25
N
18.0 ft2
1 ft 4 in
1 ft 0 in
None
None
9 i S=>E 5
Metal Single (Tinted)
Yes
0.54 0.25
N
18.0 ft2
1 ft 4 in
1 ft 0 in
None
None
10 SW=>SE 6
Metal Single (Tinted)
Yes
0.54 0.25
N
18.0 ft2
1 ft 4 in
1 ft 0 in
None
None
111 W=>S 8
Metal Single (Tinted)
Yes
0.54 0.25
N
22.5 ft2
1 ft 4 in
1 ft 0 in
None
None
12 W=>S 8
Metal Single (Tinted)
Yes
0.54 0.25
N
22.5 ft2
1 ft 4 in
1 ft 0 in
None
None
13; S=>E 11
Metal Single (Tinted)
Yes
0.54 0.25
N
80.0 ft2
1 ft 4 in
1 ft 0 in
None
None
8/23/2018 10:57 AM EnergyGaugeO USA Section R405.4.1 Compliant Software Page 3 of 5
INPUT SUMMARY CHECKLIST REPORT
FORM R405-2017
GARAGE
#
Floor Area Ceiling Area
Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation
1
440 ft2
440 ft2
64 ft 6 ft 1
INFILTRATION
# Scope
Method
SLA
CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse
Proposed ACH(50)
.000372
2153.4 118.22 222.33 .2735 7
HEATING SYSTEM
#
System Type
Subtype
Efficiency Capacity Block
Ducts
1
2
Electric Heat Pump/
Electric Heat Pump/
None
None
HSPF:8.2 33.8 kBtu/hr 1
HSPF:9.5 21.6 kBtu/hr 2
sys#1
Ductless
COOLING SYSTEM
#
System Type
Subtype
Efficiency Capacity Air Flow SHR Block
Ducts
1
2
Central Unit/
Central Unit/
None
None
SEER: 14 34.2 kBtu/hr 1026 cfm 0.75 1
SEER: 19.217.2 kBtu/hr 516 cfm 0.75 2
sys#1
Ductless
HOT WATER SYSTEM
#
System Type SubTpe
Location
EF Cap Use SetPnt Conservation
1
Electric None
Garage
0.92 40 gal 60 gal 120 deg None
SOLAR HOT WATER SYSTEM
!FSEC
Cert # Company Name
Collector Storage
System Model # Collector Model # Area Volume
FEF
None
None
DUCTS
/
V 1 #
— Supply —
Location R-Value Area
— Return — - Air CFM 25 CFM25
Location Area Leakage Type Handler TOT OUT QN RLF
HVAC #
Heat Cool
1 1
Attic 6 131 ft2
Attic
54 ft2 Default Leakage Garage (Default) (Default)
1 1
8/23/2018 10:57 AM EnergyGauge® USA Section R405.4.1 Compliant Software Page 4 of 5
I
i
rnonn 0nnk_')n17
INIPI IT CI IMMARY CHFCKI_IST RFPnRT
TEMPERATURES
Programable Thermostat: Y
Ceiling Fans:
Heating Jan Feb
Mar
Apr
May r]
Jun
[[ jj
[X] Jul
Aug
rl
rj
Sep
0 ct
L.Oc
Nov
Nov
Dec
DecVenting
Jan
Feb
XMar
CApr
May
Jun
(( ]] Jul
Aug
Sep lx
Thermostat Schedule: HERS 2006 Reference
Hours
Schedule Type
1
2
3
4
5
6
7
8
9
10
11
12
Cooling (WD)
AM
PM
78
80.
78
80
78
78
78
78
78
78
78
78
78
78
78
78
80
78
80
78
80
78
80
78
Cooling (WEH)
AM
PM
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
Heating (WQ)
AM
PM
66
68
66
68
66
68
66
68
66
68
68
68
68
68
68
68
68
68
68
68
68
66
68
66
Heating (WEH)
AM
PM
66
68
66
68
66
68
66
68
66
68
68
68 .
68
68
68
68
68
68
68
68
68
66
68
66
MECHANICAL VENTILATION
Type
Supply CFM
Exhaust CFM
Fan Wafts
HRV Heating System
Run Time Cooling System
None
0
0
0
0
1 - Electric Heat Pump
0%
1 - Central
Unit
None
0
0
0
2 - Electric Heat Pump
0%
2 - Central Unit
MASS
Mass Type
Area
Thickness Furniture Fraction
Space
Default(8 Ibs/sq.ft.
0 ft2
0 ft
0.3
Main
Default 8 Ibs/s .ft.
0 ftz
Oft
0.3
SALES
Name:
!Rating Compant:
Signature:
Date:
8/23/2018 10:57 AM EnergyGauge® USA Section R405.4.1 Compliant Software Page 5 of 5
2017 EPL DISPLAY CARD
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 96
The lower the Energy Performance Index,
the more efficient the home.
i
1. New home or, addition
1. New (From Plans)
12. Ducts, location &` insulation level
a) Supply ducts R
6.0
2. Single-family or multiple -family
2. Single-family
b) Return ducts R
6.0
c) AHU location Attic/Attic
3. No. of units (if multiple -family)
3. 1
4. Number of bedrooms
4. 4
13. Cooling system: Capacity
51.4
a) Split system SEER
5. Is this a worst case? (yes/no)
5. No
b) Single package SEER
c) Ground/water source SEER/COP
6. Conditioned floor area (sq. ft.)
6. 2205
d) Room unit/PTAC EER
e) Other
varies
7. Windows, type and area
a) U-factor:(weighted average)
7a. 0.552
b) Solar Heat Gain Coefficient (SHGC)
7b. 0.247
14. Heating system: Capacity
55.4
c) Area
7c. 319.3
a) Split system heat pump HSPF
b) Single package heat pump HSPF
8. Skylights
c) Electric resistance COP
a) U-factor:(weighted average)
8a. NA
d) Gas furnace, natural gas AFUE
b) Solar Heat Gain Coefficient (SHGC)
8b. NA
e) Gas furnace, LPG AFUE
f) Other
varies
9. Floor type, insulation level:
a) Slab -on -grade (R-value)
9a. 0.0
b) Wood, raised (R-value)
9b.
15. Water heating system
c) Concrete, raised (R-value)
9c.
a) Electric resistance EF
0.92
b) Gas fired, natural gas EF
10. Wall type and insulation:
c) Gas fired, LPG EF
A. Exterior:
d) Solar system with tank EF
1. Wood frame (Insulation R-value)
10A1. 11.0
e) Dedicated heat pump with tank EF
2. Masonry (Insulation R-value)
10A2. varies
0 Heat recovery unit HeatRec%
B. Adjacent:
g) Other
1. Wood frame (Insulation R-value)
10131.
2. Masonry (Insulation R-value)
10132.
Ceiling
16. HVAC credits claimed (Performance Method)
11. type and insulation level
a) Ceiling fans
a) Under attic
11a. 30.0
b) Cross ventilation
No
6) Single assembly
11 b.
c) Whole house fan
No
c) Knee walls/skylight walls
11 c.
d) Multizone cooling credit
d) Radiant barrier installed
11d. No
e) Multizone heating credit
0 Programmable thermostat
Yes
*Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy
saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL
display card will be completed based on installed code compliant features.
I
Builder Signature: 2ADate:
Address of New Home: 9312 WINDRIFT CIRCLE City/FL Zip: FT PIERCE, FL
I
8/23/2018 10:57:13 AM EnergyGauge® USA 6.0.02 - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 6th Edition (2017)
atory Reauirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS,: 9312 WINDRIFT CIRCLE Permit Number:
FT PIERCE, FL,
MANDATORY REQUIREMENTS See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory). The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonprdsold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can -be found in Appendix RD.
R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
i
R402.4.1 Building thermal envelojibe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.
The sealing methods between dissimilar materials shall allow for differential expansion. and contraction.
R402.4.1.1 Installation.The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
I
ith the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as: set forth in Section 489.105(3)(0, (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
I
uildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
R402.4I.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplacee. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
R402.4I.3 Fenestration air Ieakage.Windows, skylights and sliding glass doors shall have an .air infiltration rate of no more than 0.3 cfm per
squarelfoot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/iWDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
I
I
I
8123/20i18 10:57 AM EnergyGauge® USA - FBC 6th Edition (2017) Compliant Software
Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
�11462.4.4' Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed;in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
R402.4.5IRecessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
R403.1 Controls. SECTION R403 SYSTEMS
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R4031.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
thi t, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the
manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test.
Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the
entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the
test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
❑R403.3.5lBuilding cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
F-1R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41`C)
or below i 5"F (13°C) shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). Heated water circulation systems shall be in
accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2.
t utomatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return
pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the
occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems
shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water is used in the occupancy.
8/23/2018 10:57 AM EnergyGauge® USA - FBC 6th Edition (2017) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 31/ inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 60°C).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water -heating systems to be turned off.
R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
R403 i6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
!R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where whole -house mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be
powered by an electronically commutated motor.
R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
ishall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawispaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.j7 Heating and cooling equipment (Mandatory).
R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and
indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that
affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMUIV
(CFM)
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For!Sl: 1 cfm = 28.3 Umin.
When tested in accordance with HVI Standard 916
8/23/201810:57 AM
EnergyGauge® USA - FBC 6th Edition (2017) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
❑R,403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than thelcalculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
ratures shall be for the indoor dry bulb and relative humidity used for the load
Design values for entering wet -bulb and dry-bulb tempe
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by aFlorida-registered engineer, in attached single- and multiple -family units, the capacity o
equipment may be sized in accordance with good design practice.
R403.7:1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
11403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10'C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ JR403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
❑ R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
i
8/23/201 8 10:57 AM EnergyGauge® USA - FBC 6th Edition (2017) Compliant Software Page 4 of 5
i
• t403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.111 Portable spas (MandatoryChe energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
I
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 l ighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be
high -efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain -only high -efficacy lamps.
Exception: Low -voltage lighting.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
i
8/23/2018 10:57 AM EnergyGauge® USA - FBC 6th Edition (2017) Compliant Software Page 6 of 5
2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: RENAR BERMUDA 1796 Builder Name: RENAR HOMES
Street: 1 9312 WINDRIFT CIRCLE Permit Office: FT PIERCE
City, State, Zip: FT PIERCE, FL, Permit Number:
Y
U
Owner: Jurisdiction: 661100
=
Design location: FL, Fort Pierce
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
requirements
Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
Ceiling/attic
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
I
The junction of the foundation and sill plate shall .be sealed.
Cavities within corners and headers of frame walls
Walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
and doors i
skylights and framing shall be sealed.
Rim joists;
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
i
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cad ities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
Ds.
Recessed; lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the drywall.
thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
Aytpnd behind piping and wirong-
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior] wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub -floor or drywall.
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers,
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cover plater, and walls or ceilffinas-
a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400.
8/23/2018 110:57 AM EnergyGauge® USA FBC 6th Edition (2017) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ER1 Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction: 661100 Permit #:
' a h } "� ' a z ' aadC r �;� � des � �� a �a at8 ��+ 'r"�� y .�"'.� t7" ,c i. "+ �u„.,� •� a � y+r ..� c � 'YI f`'� e<� r a v : x
mow...
_.. t.u.
Builder: RENAR HOMES Community: Lot: NA
Address: 9312 WINDRIFT CIRCLE
City: FT PIERCE State: FL Zip:
S
., i .i 'R F x 5` R'A` 1. L N LSi'+2➢ '' ''S' *-. d
Y A�� Leakaga 'FestResulfs � pass�ng�i�su/ts m�Cst�me�terther fhe Performance, Prescnphve, arERl Method
-
'
� zPRESCRIPTIVE ME'HOD� T6ebuilding ard3ire`i�rig and �i1a11 be�ested and verrfiect as3having an4air leakage rate of notexceed�ng 7 air
F .Y
changesperhourata=pressu(e,of02'inch"vwg�,�;�(iPascais)'ir�Il�mate�Zories1 an:d2 a' � ;
�� £ �;f� t
' "A � i 4. a.l
z"Fr ..� ,r ": . ��@. �., f x-.F i. vVu d a ✓.4ie.'i,.�'�.i�i... ..:5.. ...s2< .kl� _ ..;( .,
PERFORM�4NCE�or�E 1 METHOD�The�bu�dirg ordpveiGng�un�t shall ;be�tested and verified as�havtngan air leakage rate of.not exceeding;
ACH(50) o�R�4}OF 201`7 (ERIy'sechon�labeled as,infiltration, sub=section AC}i50
�.t��¢
seleded valueas�showa�on Fom�R�0f7��Pe�farm�'nce�
5k� �� �aC�(50�spec�eil�oa�rm R�O�''r2097`Ener�sGatc (Pe►foanancepor��4fJ�6-2017 (EREJ y� 7.000
" r � ��� `
x
.+Kurt,. I-.�.�'. .4x+,+Ta nn 3 n' �wy;'kx ,-tY ..l:u^..�-�2 wM• � ..�%`�.k"'3'�,a-r +�"�wr'ut�",i'dl+�,w+r,S ��'+'(er_ , T e -,� �} ,^c ¢': `i$. F... .:vim,
x 60 _ 18458 = Method for calculating building volume.
CFM(50) Building Volume ACH(50) O Retrieved from architectural plans
F-1 PASS 0 Code software calculated
0 When ACH(50) is less than 3, Mechanical Ventilation installation 0 Field measured and calculated
must be verified by building department.
R402.41.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing' shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f) (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control (measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
3
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
8/23/2018, 10:57:17 AM EnergyGauge® USA 6.0.02 - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
Renar Homes Bermuda 1 796 9312 Windrift Circle
HVAC Load Calculations
for
Renar Homes
w-&HvAc. RZeizZwMkL
HVAC LOAD$
Prepared By:
Preferred Air Conditioning & Mechanical
1643 Donna Road
West Palm Beach, FI. 33409
561-689-1093
Thursday, August 23, 2018
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
RFvac Residential Irght Comm®real H1/AC Loads t t:Ute Software Developmen 'Inc.
Pre#erred Air';Conditro in &Much r Renar Nomes Bermuda 1796 9312 Wmdrift Circle-
WestPalroBeach FL`e33409? °`PaeZ
Project Report
t,.
Project Title: Renar Homes Bermuda 1796 9312 Windrift Circle
Designed By: Preferred Air Cinditioning & Mechanical
Project Date: 08-20-2018
Client Name: Renar Homes
Company Name: Preferred Air Conditioning & Mechanical
Company Address: 1643 Donna Road
Company City: West Palm Beach, FI. 33409
Company Phone: 561-689-1093
Company E-Mail Address:
Company Website: GETCOLD.NET
Desi n;"Datat ti a
Reference City: Fort Pierce, Florida
Building Orientation: Front door faces East
Daily Temperature Range: Medium
Latitude:, 27 Degrees
Elevation: 25 ft.
Altitude Factor: 0.999
i
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference
Winter: 42 39.4 n/a n/a 70 n/a
Summer 90 78 59% 50% 75 61
Total Building Supply CFM: 1,441 CFM Per Square ft.: 0.726
Square ft. of Room Area: 1,984 Square ft. Per Ton: 501
Volume (ft3): 15,872
Total Heating Required Including Ventilation Air: 31,409 Btuh 31.409 MBH
Total Sensible Gain: 34,224 Btuh 72 %
Total Latent Gain: 13,292 Btuh 28 %
Total Cooling Required Including Ventilation Air: 47,516 Btuh 3.96 Tons (Based On Sensible + Latent)
i
Rhvac isan ACCA approved Manual J and Manual D computer program. _
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. -
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your
design conditions.
i
i
i
C:1... \RENAR BURMUDA 1796.rh9 Thursday, August 23, 2018, 9:31 AM
i
Rhvac Restdent�al 8r Light Commercial HVAG Loads_:Elite
Software
Development, Inca
Preferred Aq,'Conditiomng & Mech r' Renar Homes Bermuda,1796 93121Nindrift Circle
Pa e.,3
West=Palm Beach .:..
Total jBuildin Summary Loads
a a,�z zLat Sen: Total'.
omSen x
"Co
`.....::
_. yGain .Gain., Gain.
RENAR SGD: Glazing-SGD .61 / .23, u-value 0.61, 52.8
902 0
739 739
SHGC 0.23
RENAR SGH: Glazing-RENAR SINGLE HUNG, u-value 53
1,604 0
2,795 2,795
1.08; SHGC 0.49
RENAR FIXED: Glazing -FIXED .47 / .24, u-value 0.47, 77
1,012 0
1,223 1,223
SHGC 0.24
RENAR SINGLE: Glazing-SHG .54 / .25, u-value 0.54, 67.5
1,021 0
1,851 1,851
SHGC 0.25
10A-w: Glazing -French door, single pane clear glass, 79.2
1,818 0
1,724 1,724
wood frame, u-value 0.82, SHGC 0.45
11 P: Door -Metal - Polyurethane Core 19.8
161 0
149 149
STUCCO BLOCK R-4.1: Wall -Custom, BLOCK4.1 1201.7
4,004 0
1;902 1,902
1213-0bw: Wall -Frame, R-11 insulation in 2 x 4 stud 72
195 0
89 89
cavity, no board insulation, brick finish, wood studs
R-4.2: Wall -Custom, STUCCO BLOCK R4.2 DRYWALL 65
1,063 0
661 661
1613-30: Roof/Ceiling-Under Attic with Insulation on Attic 1948
1,746 0
3,118 3,118
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane, R-30 insulation
16A-30: Roof/Ceiling-Under Attic with Insulation on Attic 36
32 0
81 81
Floor (also use for Knee Walls and Partition
Ceilings), Unvented Attic, No Radiant Barrier, Any
Roofing Material, Any Roof Color, R-30 insulation
22A-ph: ',Floor -Slab on grade, No edge insulation, no 205
7,794 0
0 0
insulation below floor, any floor cover, passive, heavy
moist soil
CustomFloor3: Floor -Slab on grade, Custom, My third 6
213 0
0 0
example custom floor _
_
Subtota�ls for structure:
21,565 0
14,332 14,332
People:! 27
5,400
6,210 11,610
Equipment:
1,131
6,700 7,831
Lighting: 281
958 958
Ductwork:
5,779 1,426
3,905 5,331
Infiltration: Winter CFM: 7, Summer CFM: 4
218 147
58 205
Ventilation: Winter CFM: 125, Summer CFM: 125
3,847 _ 5,188 _ .__.
2,061_ _ 7,249
_ _ _
Total Building Load Totals:
31,409 13,292
34,224 47,516
Total Building Supply CFM: 1,441 CFM Per
Square ft.:
0.726
Square ft. of Room Area: 1,984 Square ft. Per Ton:
501
Volume (fN): 15,872
�x+rw. .r•,. ,T J ...� ._`.ih+m _t >s � H- z.„"f+-.3 t ..., .. s" ,.., „+Ls_�... ....� ..,. ., , .`
Total Heating Required Including Ventilation Air: 31,409 Btuh
31.409 MBH
Total Sensible Gain: 34,224 Btuh
72 %
Total Latent Gain: 13,292 Btuh
28 %
Total Cooling Required Including Ventilation Air: 47,516 Btuh
3.96 Tons (Based On Sensible + Latent)
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and
ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according
to the manufacturer's performance
data at your
design Iconditions.
C:\ ... \RENAR BURMUDA 1796.rh9 Thursday, August 23, 2018, 9:31 AM
Rhvac ResidentialA Li htCommercial HVAC Loads
9
Software Development, Inc.,
RenarH mes Bermuda.1796 9312 Winddit i
Preferred AVQ6hddioning SMech o i C rcle
West Palm`Beach FLrJ 469., -
Page 4
System I Room Load Summary
Room
No t m
Na
---Zone 1---
1 Family 221 3,373 44 559
2,414 0 110 110
2 Kitchen / Breakfast 234 2,346 30 499
4,847 1,531 221 . 221
3 Liv!ing/ Dining 280 5,263 68 535
4,103 0 187 187
4 Master Bath 90 499 6 193
371 0 17 17
5 Master Bedroom 225 1,796 23 535
3,141 400 143 143
6 Wi'c 50 53 1 48
91 0 4 4
7 Bedroom 2 100 2,339 30 505
2,177 200 99 99
8 Laundry 36 38 0 319
611 0 28 28
9 Bath 2 126 133 2 115
221 0 10 10
10 Bedroom 3 121 2,011 26 579
1,110 200 50 50
11 Bedroom 4 121 1,592 21 627
. _.-.._...__.._.__.....--. �_----.-----_-----
1,202 200 55 55
_...____._........_.__.._.---...._-__..._-_..--.__._._.__
Ventilation 3,847
2,061 5,188
Duct Latent
659
Return Duct 84 _.-_.._.._._._.___------.-------------_._-.._.........._.
250 -96
_._._......._.___-._.....-_ ...
..............
Svstem 1 total 1,604 23,373 253
22,598 8,474 923 - 923
System 1 Main Trunk Size: 12x14 in.
Velocity: 791 ft./min
Loss per 100 ft.: 0.101 in.wg
Coolln Senslble/Latent t' Sensible
gg
Latent ' s Total
ti �x
F , Tans k<..m S Ilt .. ... mBtuh, sr ....'' 13tuh .° Btul-.
Net Required: 2.59 73% / 27% 22,598
8,474 31,072
Actual: 2.85 75% / 25% 25,650
8,550 34,200
-
Heating System
Cooling System
Type: Air Source Heat Pump
Air Source Heat Pump
Model: CH14NB036*0**B*
CH14NB036*0**B*
Indoor Model:
FB4CNP042L
Brand: CARRIER AIR CONDITIONING
CARRIER AIR CONDITIONING
Description: Air Source Heat Pump
Air Source Heat Pump
Efficiency: 8.2 HSPF
14.5 SEER
Sound: 0
0
Capacity: 33800 Btuh
34200 Btuh
Sensible i Capacity: n/a
25,650 Btuh
Latent Capacity: n/a
8,550 Btuh
AHRI Reference No.: n/a
9162515
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 90F, SOWB: 78F, WODB: 42F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen. gain:
22,598 Btuh, Lat. gain: 8,474 Btuh, Sen. loss: 23,373 Btuh, Entering clg. coil DB: 77.3F, Entering clg. coil WB: 65F, Entering
htg. coil DB: 56F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 923 CFM, Req. htg. airflow: 253 CFM
7
C:\ ...\RENAR BURMUDA 1796.rh9 Thursday, August 23, 2018, 9:31 AM