Series TY-FRH, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and'instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a isprinkler system or its compo-
nents and cause the sprinkler to fail
to, operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in la web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/
series-ty-frb-5-6K
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet
arelquick response, standard coverage,
decorative 3 mm glass bulb -type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series
TY'. FRB Pendent Sprinkler, where
applicable, is intended for use in areas
with a finished ceiling. This recessed
Page I of 4
I
pendent sprinkler uses one of the
following:
• A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 in. (15,9 mm) from
the flush pendent position.
• A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 in. (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
KW
The TYCO Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY313.... Upright 5.6K,1/2 in. NPT
TY323.... Pendent 5.6K,1/2 in. NPT
Technical
Data
Approvals
Refer to Table A
NOVEMBER 2021
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)'
The maximum working pressure of 250 psi (17.2 bar)
only applies to the listing by Underwriters Laborato-
ries, Inc. (UL).
Discharge Coefficient
K=5.6 GPM/psi''/, (80,6 LPM/bar/2)
Temperature Rating
Refer to Table A
Finishes
Sprinkler: Refer to Table B
Recessed Escutcheon: White Coated,
Black Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
Frame ............................Bronze
Button......................Brass/Copper
Sealing Assembly ... Stainless Steel w/TEFLON
Bulb...............................Glass
Compression Screw ................. Bronze
Deflector..........................Bronze
TFP172
I
I
TFP172
Page 2 of 4
1
Components:
1 - Frame
12 - Button
13 - Sealing
I Assembly
4 - Bulb
5 - Compression
Screw
6 - Deflector*
* Temperature rating is ** Pipe thread connections per ISO 7-1
indicated on Deflector, can be provided on special request.
DEFLECTOR*
STYLE 15 or 20
ESCUTCHEON PLATE
1/2" 7/16" (11,1 mm) RECESSED
SEATING SURFACE
NPT** NOMINAL MAKE -IN ESCUTCHEON
7/16"
(11,1 mm)
NOMINAL 2" 0 0
MAKE -IN (50,8 mm)
2" 1-3/8"
50,8 mm) (34,9 mm)
/ WFI
1/2" NPT** DEFLECTOR* �_-- 2-7/8" (73,0 mm) DIA.
UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 112 INCH NPT, QUICK RESPONSE
WRENCH RECESS
(USE ONLY
END "A")
FIGURE 2
W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
i
1
1 �
I
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3
W-TYPE 7 RECESSED
1 SPRINKLER WRENCH
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
FACE OF (57,2 mm)
SPRINKLER
FITTING 5/8" (15,9 mm)
FLUSH
3/8t5/16" T I 7
(9,5t7,9 mm)
MOUNTING 1/8
SURFACE (3,2 mm)
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TY-FRB PLATE 3/4" (19,1 mm)
FIGURE 4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 518 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
2-7/8" DIA.
(73,0 mm)
FACE OF
SPRINKLER 2-1/4" DIA.
FITTING (57,2 mm)
5/16t1/4" 1/2" (12,7 mm)
(7,9t6,4 mm) FLUSH
17,
MOUNTING e(3,
"
SURFACEm)
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TY-FRB PLATE 7/8" (22,2 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
is I:
13,
20
for
TFP172
Page 3 of 4
SPRINKLER FINISH (See Note 7)
K
FACTOR
TYPE
TEMPERATURE
BULB LIQUID
COLOR
NATURAL
BRASS
CHROME
PLATED
POLYESTER -
135°F (57°C)
Orange
UPRIGHT
(TY313)
and
1, 2, 3, 4, 5, 6
155°F (68°C)
Red
175°F (79°C)
Yellow
5.6
1/2 in. NPT
PENDENT
(TY323)
200°F (93°C)
Green
286°F (141°C)
Blue
135°F (57°C)
Orange
RECESSED
PENDENT
(TY323)
Figures 4a and 5b
1, 2, 3, 4
155°F (68°C)
Red
175°F (79°C)
Yellow
200°F (93°C)
Green
Notes:
1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-54-428-3377.)
6. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion -Resistant Sprinklers.
a. Installed with Style 15 (1/2 in. NPT) 5/8 in. Total Adjustment Recessed Escutcheon, as applicable.
b. Installed with Style 20 (1/2 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
C. Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORYLISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
eration
glass bulb contains a fluid which
ands when exposed to heat. When
rated temperature is reached, the
expands sufficiently to shatter the
,s bulb, allowing the sprinkler to
rate and water to flow.
n
TYCO Series TY-FRB, 5.6 K factor,
ight (TY313) and Pendent (TY323)
inklers are intended for fire protec-
systems designed in accordance
i the standard installation rules
)gnized by the applicable Listing or
troval agency (such as, UL Listing
ased on the requirements of NFPA
and FM Approval is based on the
iirements of FM% Loss Prevention
a Sheets). Only the Style 15 or Style
Recessed Escutcheon is to be used
-ecessed pendent installations.
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb -type sprin-
kler if the bulb is cracked or there is
a loss of liquid from the bulb. With the
sprinkler held horizontally, a small air
bubble should be present. The diam-
eter of the air bubble is approximately
1/16 in. (1,6 mm) for the 135°F (57°C) and
3/32 in. (2,4 mm) for the 286°F (1 41°C)
temperature ratings.
A leak -tight 1/2 in. NPT sprinkler joint
should be obtained by applying a
minimum to maximum torque of 7 to
14 lb-ft (9,5 to 19,0 N•m). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over -tightening
the sprinkler. Re -adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Step 1. Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe -thread sealant
applied to the pipe threads, hand -
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 lb-ft (9,5 to
19,0 N•m).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15
or Style 20 Mounting Plate over the
sprinkler threads, and with pipe -thread
sealant applied to the pipe threads,
hand -tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 lb-ft (9,5 to 19,0 N•m).
Step C. After ceiling installation and
finishing, slide on the Style 15 or Style
20 Closure over the Series TY FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
T TFP172
Page 4 of 4
P/Na 77 — XXX — X — XXX
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
1 1 370 1 5.6K UPRIGHT (1/2 1n.NPT) I TY313
1 371 1 5.6K PENDENT (1/2 in.NPT) I TY323
Notes:
a. Use suffix "I" for ISO 7-1 connection; for example,
77-370-4-175-1
Care and
1 1 1 NATURAL BRASS
3 PURE WHITE (RAL9010)a
POLYESTER
4 SIGNAL WHITE (RAL9003)
POLYESTER
5 JET BLACK (RAL9005)
POLYESTER
9 1 CHROME PLATED
Notes:
a. Eastern Hemisphere sales only
TABLE B
SERIES TY-FRB UPR/GHTAND PENDENT SPRINKLERS
PART NUMBER SELECTION
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non -
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a clofh or
by brushing it with a soft bristle brush.
PA 19446
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
+1-215-362-0700
135
135°F(57°C)
155
155°F (68°C)
175
175°F (79°C)
200
200°F (93°C)
286
286°F (141°C)
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB Upright or
Pendent (specify) Sprinkler, SIN
(specify), K=5.6, Quick Response,
(specify) temperature rating, (specify)
finish, P/N (specify, refer to Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
Johnson Controls. Alf rights reeemd. All specifications and other Information shown were current as of document rmislon date and are subject to change without notice.
FIRE PROTECTION ASSOCIATION and NFPA arc registered tntdemarko of Nadonal F.Pmtectl°n Asa°clatlon;
a trademark of The Chemous Company FC, LLO
Johnson
Controls
• Made with Teks' self -drilling fasteners - no pre -drilling required.
• Installs into steel range from 20 gauge —1/2" thicknesses.
• A standard screwgun with a depth sensitive nosepiece should be used to
install Teks. For optimal fastener performance, the screwgun should be a
minimum of 6 amps and have an RPM range of 0-2500.
• Saves time from traditional methods.
• Reduces installation costs.
• Quick to install using the Sammys Nut Driver with an
View our
18V cordless drilVdriver.
installation videos!
• Asembled in the U.S.A.
MuTube
318"
8050957 SWD 10
1/4-14 x 1" TEKS 3
1477 (16 ga.)
.060"-16 ga
3/16"
25
125
IQw O
3!8"
8052957 SWD 20
1/4-14 x 2' TEKS 3
1477 (16 ga.)
i .060"-16 ga
3/16" 25 125
3/8"
8055957 SWDR 1 •
114-20 x 1" TEKS 3
1900 (20 ga.) 1500
1475 .036"-20 ga
3/16'
25
125
!i 0_3/8"
8054957 SWDt21-1/2' 12-24x1-1/2"TEKS5 42375
—
(3/16") __. 1500
_
M1475 .188"-3/16"
+
1/2"
25
^125]
3/8"
8056957 SWDR 516'
5/16-18 x 1-1/4" TEKS 3
2480 (20 ga.) 1500
1475 .036"-20 ga
3/16"
25
125
'Includes retaining nut
#14 SW Red
Nut Driver
Part # 8114910
SAM' MYS SWIVEL HEADTMFOR STEEL - Swivel Application
-r
z
#14 Black
Nut Driver —
Part # 8113910
I
i
#14 SH Orange
Nut Driver
Part # 8273910
3/8" 8137957 SH-DSTR 1' 1/4-20TEK X 1"
TEKS 3
?- 3/8" 8268957 SH-TEK 50 12-24 x 1-5/8"
TEKS 5
'Does not comply with ROHS requirements /Includes retaining nut
• Eliminates distortion of threaded rod in sloped roof applications.
• Accommodates 3-1/2 x 12 pitch.
• Installs into angled z-purlin; allows threaded rod to hang plumb.
• Allows 17° deflection from vertical.
• Asembled in the U.S.A.
3220 (3/16") 1500
2368 (1/2" steel Vertical)
1306 (45• off Vertical) 1500 (Vertical)
2281 (3/16" HSS) 850 (45" off Vertical)
1585 (3/16" HSS 45" off Vertical)
View our
installation videos!
ClYo tTub®
1475 .035" 3/16" 25 125
4" 3/16" 1/2" 25 125
2-1 IT