NOTICE OF ACCEPTANCE (NOA) w«'w.miamidaae.eov/economy
Extreme Metal Fabricators, LLC CONCEALED FASTENERS OR ATTACHMENTS
216I Poma Drive ARE THE RESPONSIBILITY OF THE
Palm City, FL 34990 CONTRACTOR OR RECORD
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be
used in Miami -Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section
(in Miami -Dade County) and/or the AHJ (in areas other than Miami -Dade County) reserve the right to have this product
or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the
manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use
of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance, if it is
determined by Miami -Dade County Product Control Section that this product or material fails to meet the requirements
of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: DMC 100 NS — 24GA Steel Panel over Plywood Deck
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for
sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of
this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in it's entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA consists of pages I through 6. THESE PLANS AND ALL PROPOSED WORK
The submitted documentation was reviewed by Gaspar J Rodriguez. ARE SUBJECT TO ANY CORRECTIONS
-'6(Zl,t � 1 g 11— b�
MIAMI•DADECOUNTY 6Te0
' • M � • M ST. LUCIE COUNTY BUILDING DIVJk
REVIEWED FOR COMPLIANCE
REVIEWED
DATE IT 4
PLANS ANMIT MUST BE KEPT
SITE OR NO INSPECTIONS) WILL E
REQUIRED BY FIELD INSPECTORS THAT
MAY BE NECESSARY IN ORDER TO
k 0MPLY WITf 1 ALL APPLICABLE CODES.
NOA No.: 15-0309.09
[ON xpiration Date: 09/17/20
Approval Date: 09/17/15
Page I of 6
IJOB
MADE
ROOFING SYSTEM APPROVAL:
Category:
Roofing
Sub;Catmorv:
Metal, Panels (Non -Structural)
Material:
Steel
Deck Type:
Wood
Maximum Desien Pressure
-135 PSF
TRADE NAMES. OF PRODUCTS MANUFACTURED OR LABELED, By APPLICANT:
Test
Product
Product Dimensions
Specifications .
Description
DMC 1.00 NS — 24GA Length: various
TAS 11.0
Corrosion resistant, galvanized steel or
galvalume
Steel Panel Height: 1"
standing seam metal panel with integral
perforated
Width: 16"
fastening strip.
Thickness: 24GA
Min Yield Strength:
50 KSI
Trim Pieces Length: varies
N/A
Corrosion resistant, galvanized steel or
galvalume
Width: varies
standing seam metal panel with integral
perforated
Thickness: 24GA
fastening strip.
Min Yield Strength:
50 KSI
Bostik.70-05A N/A
TAS 110
Heavy duty construction adhesive.
EVIDENCE SUBMITTED:
Test Agency
Test Identifier
Test Name/Report
Date
PRI iConstructions Materials
AKZC-003-02-01
ASTM B 117
05/13/08
Technologies, LLC
AKZC-003-02-02
ASTM B 117
05/13/08
AKZC-003-02-63
ASTM G 26
05/13/08
AKZC-003-02-04
ASTM G 26
05/13/08
DMC-016-02-01
TAS 100
10/24/13
DMC-014-02-01
TAS 125
10/23/13
MIAMI•DADE COUNTY
NOA No.: 15-0309.09
Expiration Date: 09/17/20
Approval Date: 09/17/15
Page 2 of 6
APPROVED ASSEMBLIES:
System A: DMC 100 NS 24GA Steel Panel 16" wide
Deck Type: Wood, Non -insulated
Deck Description: New Construction 19/32" or greater plywood or wood plank.
Slope Range: 2": 12" or greater
Maximum Uplift See Table A below
Pressure:
Deck Attachment: In accordance with applicable Building Code, but in no case shall it be less than 8d annular
ring shank nails spaced 6" OC. In reroofing, where the deck is less than19/32" thick
(Minimum ''/32") the above attachment method must be in addition to existing attachment.
Underlayment:
Minimum tmderl.ayment shall be an ASTM D 226 Type II installed with a minimiun 4"
side -lap and 6" end -laps. Underlayment shall be fastened with corrosion resistant tin -caps
and 12 gauge 1 ''/4" annular ring -shank nails, spaced 6" OC at all laps and two staggered
rows 12" OC in the field of the roll or any approved underlayment having a current NOA.
Fire Barrier Board:
Any approved fire barrier having a current NOA. Refer to a current fire directory listing for
fire ratings of this roofing system assembly as well as the location of the fire barrier within
the assembly. See Limitation # 1.
Valleys:
Valley construction shall be in compliance with Roofing Application Standard RAS 133
and with the current published installation instructions and details in DMC Association of
Regional Manufacturers Installation. Manual.
Metal Panels and
Install the "DMC 100 NS 24GA Steel Panel" including flashing penetrations, valleys, end
Accessories:
laps and accessories in compliance "DMC Association of Regional Manufacturers" current,
published installation instructions and in compliance with the minilntun requirements
detailed in Roofing Application Standard RAS 133.
Field Conditions:
Panels shall be secured along the male rib with corrosion resistant #10-13 x 1" PHW
fasteners of sufficient length to penetrate through the sheathing a minimum of 3/16", and
located at the maximum spacing listed in Table A below. See Detail B herein.
The adjacent panel shall overlap and be secured to each other when the female rib of the
panel is snapped over the male rib of panel.
TABLE A
MAximum DESIGN PRESSURES
Roof Areas
Field
Perimeter and Corner'
Option 1
Perimeter and Corner'
Option 2
Maximum Design Pressures
-97.5 PSF
-120 PSF
-135 PSF
Maximum Screw Spacing
(1) fastener at 10 ''/z"
OC
(1) fastener at 5 '/" OC
(2) fasteners at 5 '/4" OC
Bostik Seam Sealant
None
None
(2)3/ 16" beads
1. EXtrapolation shall not be allowed
I
NOA No.: 15-0309.09
CMIAMI-D�ADECOU=N Expiration Date: 09/17/20
Approval Date: 09/17/15
Page 3 of 6
LIMITATIONS
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials Directory for fire
ratings of this product.
2. The maximum designed pressure listed herein shall be applicable to all roof pressure zones (i.e. field, perimeters,
and corners). Neither rational analysis, nor extrapolation shall be permitted for enhanced fastening at enhanced
pressure zones (i.e. perimeters, extended corners and corners).
3. Panels may be rolls formed in continuous lengths from eave to ridge. Maximum lengths shall be as described in
Roofing Application Standard RAS 133.
4. All panels shall be permanently labeled with the manufacturer's name and/or logo, city and state, and the
following statement: "Miami -Dade County Product Control Approved" or with the Miami -Dade County Product
Control Seal as seen below: All clips shall be permanently labeled with the manufacturer's name and/or logo,
and/or model.
IIAMI•DADE COUNTY
5. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61 G20-3 of the Florida Administrative Code.
6. Panels may be jobsite roll formed with machine model #0290414; 3381213; 4260215; 5960197; 10811107, from
DMC Association of Regional Manufacturers.
NOA No.: 15-0309.09
CM1AM1MDADEC0=UN Expiration Date: 09/17/20
Approval Date: 09/17/15
Page 4 of 6
PROFILE DRAWINGS
DETAIL A
0
DMC MONS - 24GA STEEL PANEL
NOA No.: 15-0309.09
MIAMMADECOUNTY Expiration Date: 09/17/20
Approval Date: 09/17/15
Page 5 of 6
DETAIL B
DMC , 1 DONS PANEL
#10713x1"PHW
(FIELD, PERIMETER, & CORNER CONDITION SEAM DETAIL WITHOUT BOSTIK SEAM. SEALANT
II .
DMC 100NS PANEL
BOSTICK 70-05A (2 - 3116" BEADS)
#10-13x1"PHN,
(PERIMETER, & CORNER CONDITION SEAM DETAIL WITH BOSTIK SEAM SEALANT)
END OF THIS ACCEPTANCE
NOA No.: 15-0309.09
Q-
M[AMMIDMEuNr�r Expiration Date: 09/17/20
Approval Date: 09/17/15
Page 6 of 6