HomeMy WebLinkAboutENERGY EFFICIENCY CODEFlorida Energy Efficiency Code For Building Construction
Florida Department of Community Affairs
EnergyGauge FLA/COM 2004 v3.00 --.Form 40OB-2004
Method B: Envelope Trade -Off Compliance for Commercial Buildings
Effective December 8, 2006
PROJECT SUMMARY
Short Desc: TENANT IMPROVE.
Owner: PETE HALL
Addressl: MIDWAY INDUSTIRIAL PARK
Address2:
Description: D A P TENANT IMPI
L o-r i
City: FT. PIERCE
State: FLORIDA
Zip: 0
Type: Office Class: Renovation to existing
Jurisdiction: ST LUCIE COUNTY, ST LUCIE COUNTY, FL (661000)
Cond Area: 375 SF Coud & UnCond Area: 375 SF
No of Storeys: 1 Area entered from Plans 0 SF
Permit No: 0 Max Tonnage 1.5
If different, write in:
10/2007 EnergyGauge FLA/COM 2004 v3.00
EnergyGauge FLAXOM 2004 v3.00
INPUT DATA REPORT
Proiect
Information
Project Name:
TENANT IMPROVE.
Orientation:
North
Project Title:
D A P TENANT IMPROVE. BUILIDING LOT 1 Building Type:
Office
Address:
MIDWAY INDUSTIRIAL PARK
Building Classification:
Renovation to existing building
No.of Storeys:
1
State:
FLORIDA
Zip:
0
GrossArea:
375 SF
Owner:
PETE HALL
Zones
No Acronym Description Type Area Multiplier Total Area
[sfJ [stl
1 OFFICE D A P TENANT CONDITIONED 375.0 1 375.0 ❑
IMPROVE. BUILIND
LOT 1
7/10/2007
" ■
EnergyGauge FLA/COM 2004 v3.00
A ,
• � .x 1
Spaces
No Acronym Description Type
Depth
Width
Height
Multi Total Area
Total Volume
[ft]
[ft]
[ft]
plier [sf]
[cf]
In Zone: OFFICE
1 OFFICE
D A P TENANT Office - Open Plan
15.00
25.00
8.00
1 375.0
3000.0
❑
IMPROVE. BUILIND
LOT-1
-
-
Lighting
No
Type Category
No. of
Watts per
Power
Control Type
No.of
Luminaires
Luminaire
[W]
Ctrl pts
In Zone: OFFICE
In Space: OFFICE
1
Recessed Fluorescent - General Lighting
5
64
320
Manual On/Off
4
❑
No vent
Walls
No Description
Type Width H (Effec) Multi
Area DirectionConductance Heat
Dens. R-Value
[ft]
[ft] plier
[sf]
[Btu/hr. sf. F] Capacity
[lb/cf] [h.sf.F/Btu]
[Btu/sf.F]
In Zone: OFFICE
❑
1 NWALLS
Construct 1032 15.00
8.00 1
120.0
North
0.0697 2.375
47.62 14.3
2 SWALL
Construct 1032 15.00
8.00 1
120.0
North
0.0697 2.375
47.62 14.3
❑
3 EWALL
Construct 1032 25.00
8.00 1
200.0
North
0.0697 2.375
47.62 14.3
❑
4 WWALL
Construct 1031 25.00
8.00 1
200.0
North
0.1693 21.084
107.96 5.9
0
Windows
No
Description Type Shaded U SHGC Vis.Tra
W
H (Effec) Multi
Total Area
- - - -
-- - - ---
-[Btu/hr-sf-F] -
[ft]—
----[ft] plies
[S fj
7/10/2007 EnergyGauge FLA/COM 2004 v3.00
In Zone:
In Wall:
El -
Doors
No Description Type
Shaded? Width H (Effec) Multi
[ft] [ft] plier
Area
[sf]
Cond. Dens. Heat Cap.
[Btu/hr. sf. F] [lb/cf] [Btu/sf. F]
R-Value
[h.sf.FBtu]
In Zone:
In Wall:
Roofs
No Description Type
Width H (Effec) Multi Area
[ft] [ft] plier [sf]
Tilt
[deg]
Cond. , Heat Cap Dens.
[Btu/hr. SE F] [Btu/sf. F] [lb/cf]
R-Value
[h.sf.FBtu]
In Zone: OFFICE
1 ROOF Construct 1030
25.00 15.00 1 375.0
0.00
0.0419 6.16 29.57
23.9
❑
Skylights
No Description Type
U SHGC Vis.Trans
[Btu/hr sf F]
W
[ft]
H (Effec) Multiplier Area
[ft] [sf]
Total Area
[Sf]
In Zone:
In Roof.
Floors
No Description Type
Width H (Effec) Multi Area
IN [ft] plier [sf]
Cond. Heat Cap. Dens. R-Value
[Btu/hr. sf. F] [Btu/sf. F] [lb/cf] [h.sf.FBtu]
jrn—Z&Ce--.— -OFFICE
7/10/2007 EnergyGauge FLA/COM 2004 v3.00
1 FLOOR 4 in. heavyweight 25.00 15.00 1 375.0 3.0030 9.32 140.00 0.33 ❑
concrete
Systems
AC-1 BARRRY'S DELICATESSEN
Constant Volume Packaged System No. Of Units ,1
Component Category
Capacity
Efficiency IPLV
1 Cooling System (Air Cooled < 65000 Btu/h Cooling
Capacity)
2 Heating System (Electric Furnace)
3 Air Handling System -Supply (Air Handler (Supply) -
Constant Volume)
18000.00
6000.00
600.00
13.00 13.00
1.00
0.80
❑
❑
Plant
Equipment Category
Size
Inst.No Eff. IPLV
Lj
Water Heaters
W-Heater Description Capacit3Cap.Unit
I/P Rt.
Efficiency Loss
Ext-Lighting
Description Category No. of Watts per Area/Len/No. of units Control Type Wattage
Luminaires Luminaire [sVft/No] [W]
7/10/2007
EnergyGauge FLA/COM 2004 v3.00
4
No Type
Piping
Operating Insulation
Temperature Conductivity
[F] [ Btu-in/h.sf.F]
Fenestration Used
Name Glass Type No. of Glass SHGC VLT
Panes Conductance
[Btu/h.sf.F]
Materials Used
Nomonal pipe Insulation Is Runout?
Diameter Thickness
[in] [in]
J
Mat No
Acronym
Description
Only R-Value
Used
RValue
[h.sf.FBtu]
Thickness
[ft]
Conductivity
[Btu/h.ft.F]
Density
[lb/cf]
SpecificHeat
[Btu/lb.F]
4
Mat14
Steel siding
No
0.0002
0.0050
26.0000
480.00
0.1000
❑
60
Mat160
Ceiling air space
Yes
1.0000
❑
23
Mat123
6 in. Insulation
No
20.0000
0.5000
0.0250
5.70
0.2000
❑
57
Mat157
3/4 in. Plaster or gypsum
No
0.1488
0.0625
0.4200
100.00
0.2000
❑
21
Matl21
4 in. Insulation
Yes
13.3300
❑
9
Matl9
Air space resistance
Yes
0.9100
❑
40
Mat140
4 in. Heavyweight concrete
No
0.3330
0.3330
1.0000
140.00
0.2000
❑
7
Mat17
Finish
No
0.1738
0.0417
0.2400
78.00
0.2600
❑
2
Mat12
1 in. Stucco
No
0.2082
0.0833
0.4000
16.00
0.2000
❑
18
Mad18
2 in. Wood
No
2.3857
0.1670
0.0700
37.00
0.3900
❑
45
Mat145
8 in. Heavyweight concrete
No
0.6670
0.6670
1.0000
140.00
0.2000
❑
10
Mat110
I in. Insulation
No
3.3200
0.0830
0.0250
200
0.2000
❑
7/10/2007
EnergyGauge FLA/COM 2004 v3.00
s
5
187
Mat1187
GYP OR PLAS
No
0.4533 0.0417
0.0920
50.00
0.2000
❑
BOARD,1/21N
Constructs Used
Simple
Massless Conductance Heat Capacity
Density
RValue
No
Name
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.FBtu]
1016
4 in. heavyweight concrete
No
No 3.00
9.32
140.00
0.3
❑
Layer
Material
Material
Thickness
Framing
No.
IN
Factor
1
40
4 in. Heavyweight concrete
0.3330
0.000
❑
Simple
Massless Conductance Heat Capacity
Density
RValue
No
Name
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.FBtu]
1030
Construct 1030
No
No 0.04
6.16
29.57
23.9
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
7
Finish
0.0417
0.000
❑
2
4
Steel siding
0.0050
0.000
❑
3
60
Ceiling air space
0.000
❑
4
18
2 in. Wood
0.1670
0.000
❑
5
23
6 in. Insulation
0.5000
0.000
❑
6
57
3/4 in. Plaster or gypsum
0.0625
0.000
❑
7
7
Finish
0.0417
0.000
❑
7/10/2007 EnergyGauge FLA/COM 2004 v3.00 6
Simple
Massless
Conductance Heat Capacity
Density
RValue
No Name
Construct
Construct
[Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.FBtu]
1031 Construct 1031
No
No
0.17
'21.08
107.96
5.9
❑
Layer
Material
Material
Thickness
Framing
No.
IN
Factor
1
7
Finish
0.0417
0.000
❑
2
2
1 in. Stucco
0.0833
0.000
❑
3
45
8 in. Heavyweight concrete
0.6670
0.000
❑
4
9
Air space resistance
0.000
❑
5
10
1 in. Insulation
0.0830
0.000
❑
6
187
GYP ORPLAS BOARD,1/21N
0.0417
0.000
❑
7
7
Finish
0.0417
0.000
❑
Simple
Massless
Conductance Heat Capacity
Density
RValue
No Name
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.F/Btu]
1032 Construct 1032
No
No
0.07
2.37
47.62
14.3
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
7
Finish
0.0417
0.000
❑
2
2
1 in. Stucco
0.0833
0.000
❑
3
21
4 in. Insulation
0.3330
0.000
❑
4
187
GYP OR PLAS BOARD,1/21N
0.0417
0.000
❑
5
7
Finish
0.0417
0.000
❑
7/10/2007 EnergyGauge FLA/COM 2004 v3.00 7
Compliance Summary
Component
Design Criteria Result
ENVELOPE
26.2 33.6 PASSES
LIGHTING POWER
320.0 412.5 PASSES
LIGHTING CONTROLS
PASSES
EXTERNAL LIGHTING
None Entered
HVAC SYSTEM
PASSES
PLANT
None Entered
WATER HEATING SYSTEMS
None Entered
PIPING SYSTEMS
None Entered
Met all required compliance from Check List?
Yes/No/NA
RTANT NOTE: An input report of this design building must be submitted
with this Compliance Report.
7h0/2007
i
EnergyGauge FLA/COM 2004 v3.00
ON
i
_CERTIFICATIONS
I hereby certify that the plans and' 'specifications covered by this calculation are in compliance with the
Florida Energy Code
Prepared By:' Building Official:
Date: juL _ Date:
I certify that this building is in compliance with the FLorida Energy Efficiency Code
L
Owner Agent: 0.4—e Date: -7 — i l o %
If Required by Florida law, I hereby certify (*) that the, system design is in compliance with the FLorida
Energy Efficiency Code
Architect: PAUL WELCH INC. Reg No: 29945
Electrical Designer: PAUL WELCH INC. Reg No: 29945
Lighting Designer: PAUL WELCH INC. Reg No: 29945
Mechanical Designer: PAUL WELCH INC. Reg No: 29945
Plumbing Designer: PAUL WELCH INC. Reg No: 29945
(*) Signature is required where Florida Law requires design to be performed by registered design
professionals. Typed names and registration numbers may be used where all relevant information is
contained on signed/sealed plans.
Project: TENANT IMPROVE.
Title: D A P TENANT IMPROVE. BUILIDING LOT 1
Type: Office
(WEA File: DAYTONABEACH.TMY)
Envelope Compliance
Design Load Criteria
Zone Heating Cooling Heating Cooling
Building 16.20 10.00 20.50 13.10
Total Loads: Design =26.2 Criteria =33.6 PASSES
/10/2007 EnergyGauge FLA/COM 2004 v3.00
External Lighting Compliance
Description Category Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (VV)
(Sgft or ft)
None
roject: TENANT IMPROVE.
itle: D A P TENANT IMPROVE. BUILIDING LOT 1
Spe: Office
EA File: DAYTONABEACH.TMY)
Lighting Power Compliance
Space Ashrae Description Area Height No. of Design Effective Allowance
ID (sq.ft) (ft) Spaces (W) (W) (W)
I
OFFICE 16 Office - Open Plan 375 8.0 1 320 320 413
�esign 320 (W) PASSES
Effective: 320 (W)
Allowance: 412.5 M
)project: TENANT IMPROVE.
Title: D A P TENANT IMPROVE. BUILIDING LOT 1
*ype: Office
(WEA File: DAYTONABEACH.TMY)
Lighting Controls Compliance
Acronym Ashrae Description Area No. of Design Min Compli-
ID (sq.ft) Tasks CP CP ance
OFFICE 16 Office - Open Plan 375 1 4 1 PASSES
PASSES
7/j10/2007
I
EnergyGauge FLA/COM 2004 v3.00
Project: TENANT IMPROVE.
Title: D A P TENANT IMPROVE. BUILIDING LOT 1
Type: Office
(W.EA File: DAYTONABEACH.TMY)
'
AC-1
System Report Compliance
Constant Volume Packaged No. of Units
System 1
Component
,
Category Capacity Design Eff
Eff Criteria
Design IPLV Comp-
IPLV Criteria liance
Cooling System
Ieating System
ir Handling
System -Supply
Air Cooled < 65000 Btu/h 13.00 13.00
Cooling Capacity
Electric Furnace 1.00 1.00
Air Handler (Supply) - 0.80 0.90
Constant Volume
13.00 PASSES
PASSES
PASSES
,
I
PASSES
Plant Compliance
i
Description
Installed Size Design Min Design Min Category Comp
No Eff Eff IPLV IPLV liance
None
Water Beater Compliance
description
Type Category Design Min
Eff Eff
Design Max Comp
Loss Loss liance
i
None
7/10/2007 EnergyGauge FLA/COM 2004 v3.00
i
Piping System Compliance
Category Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] .SF.F]
I
I
i
I
None
et: TENANT IMPROVE.
D A P TENANT IMPROVE. BUILIDING LOT 1
Office
File: DAYTONABEACH.TMY)
Other Required Compliance
Category
Section
Requirement (write N/A in box if not applicable)
Check
Infiltration
406.1
Infiltration Criteria have been met
System
407.1
HVAC Load sizing has been performed
Ventilation
409.1
Ventilation criteria have been met
ADS
410.1
Duct sizing and Design have been performed
T & B
410.1
Testing and Balancing will be performed
Motors
414.1
Motor efficiency criteria have been met
Lighting
415.1
Lighting criteria have been met
O & M
102.1
Operation/maintenance manual will be provided to owner
Roof/Ceil
404.1
R 19 for Roof Deck with supply plenums beneath it
Report
101
Input Report Print -Out from EnergyGauge FlaCom attached?
7/� 0/2007
I
EnergyGauge FLA/COM 2004 v3.00
6
PAUL WELCH INC.
MECHANICAL * ELECTRICAL * CIVIL ENGINEERING
19B4 S.W. BILTMORE ST. SUITE#1 14
PORT SAINT LucIE, FL 349B4
PHONE (772) 7B5 - 9BBB
FAX (772) 7B5-9933
I
JUL V L 10 2007 SHEET OF
DATE:
MANUAL "N"
HVAC WORK SHEET
ROOM: D�CdG AREA: 6 �m JOB:
ZONE: 1
e`
N WALL ..........................
S F
X
3. 6 0 =
...............
"0 WALL ...........
SF
X
7.36 =
�
�;. WALL ..................... .....
S F
X
yj WALL ....................
SF
x
6.56 =
GLASS
........................
SF
X
44 =
•
0
SF
X
49 —
GLASS ........................
SF
X
91 =
i� GLASS
........................
SF
X
91
I
(
SF
X
2.2 =
ROOF...I,........................... .....
i
37,,0
W
X
3.41 —
X
500 =
PEOPLE.................................
INFILL ( 62- B9) ....................
�
�'L
CFM X
34 =
SUB TOTAL =
5 % DUCT LOSSES =
TOTAL =
O
�01T I
1'�ao
44 S CFM