HomeMy WebLinkAboutMISC LETTER06/07/2007 08:10 3379061
BLOSSER SHOP
PAGE 03
PAGE 3 OF 6
DetaNs
016-00 1 Designation, LOT #1
SAUARE D STANDARD QED SWITCHBOARD
QED Swltehkyoard
Square D Power Style $tandard Switchboard
Designed and Tasted In accordance with:
UL8911NATIONAL ELECTRIC CODFJNEMA PB-2
System Voltaga' 206Y/1 ZOY 3Ph 4W BOHz
Source Description - Single Main
System Ampaolty - 1600A
Bussing - Capper (plated with Silver
Neutral Bus -100%
Max Available Fault Current (RMS) - 65kA
Enolosure - Type 3R Non-Waik4n
Aacesslbility: Front and Left Side
Exterior Paint Color - ANSI 49
Ground Lug provided for eaoh device
No Horizontal Bus
Dimensions
1a--W' Wide Section(s) -
1 - 59,5" Deep Enclosure(s)
1- Dimensions: 36.W' W X 59.5" D X 91.5"H
Approximate Weight: 906
Incoming Requirements
Suitable for Use As Service Entrance
Entry Point: Through the Bottom
Connection Type: Cable
Mains
1 - 160t)AF/$ PaPe Fused Power Circuit Device,
UL, Manual Trip(Standard Feed), Type SP
3 - KRP-C1600, NEMA Class L Fuse