HomeMy WebLinkAboutPROJECT SUMMARYRF�FIVFD Project Summary MOP Job. 527 Air Calcs, LLC J rY No �I P P018 Date: Nov19,2018 Entire House errnit Vicki . By: Lynne Barenberg Air Caics, LLC St. Cu s Depart ent 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: viddlyme@aircalks.cem i Project Information I For. Muse Residence 5821 Mustange Circle, Port St Lucie, FL 34953 SCANNED BY Notes: St Lucie County Weather: St Lucie Co Intl, FL, US Winter Design Conditions Outside db 41 OF Inside db 70 OF Design TD 29 OF Heating Summary Structure 26855 Btuh Ducts 7858 Btuh Central vent (53 cfm) 1703 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 36416 Btuh Infiltration Method Construction quality Fireplaces Area (ftl) Volume (ft3) Air'jchanges/hour Equiv AVF (cfm) Simplified Average 0 He23n4g Coo234 30067 30067 0.32 0.16 160 80 Heating Equipment Summary Make n/a Trade n/a Model n/a AHRI ref n/a Efficiency n/a Heating input Heating output 0 Btuh Temperature rise 0 OF Actual airflow 0 afm Airflowfactor 0 cfm/Btuh Static pressure 0 in H2O Space thermostat n/a Summer Design Conditions Outside db 90 OF Inside db 75 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 grAb Sensible Cooling Equipment Load Sizing Structure 18577 Bt-ih Ducts 13730 Btuh Central vent (53 cfm) 904 Btuh Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 31684 Btuh Latent Cooling Equipment Load Sizing Structure 3898 Btuh Ducts 2879 Btuh Central vent (53 dm) 2064 Btuh Equipment latent load 6777 Btuh Equipment Total Load (Sen+Lat) 38461 Btuh Req. total capacity at 0.70 SHR 3.8 ton Cooling Equipment Summary Make n/a Trade n/a Cond n/a Coil n/a AHRI ref n/a Efficiency n/a Sensible cooling 0 Btuh Latentcooling 0 Btuh Total cooling 0 Btuh Actual airflow 0 cfm Airflowfaclor 0 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -411- wrigFvtsoft' 2018-Nov-2012:56:04 RigR-Sute®Uriversa1201818.0.31 RSU27054 Pagel _JulDoamertslWrigHsoftHVACWseResidenoe.nQ Calc=MJB FrartDoorface I LE CO PDEYC1 8 201B Job: 527 Air Calcs, LLC Project Summary Date: Nov19, 2018 (Rest of House) By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vicldlyrne@aircalcs.com For. Muse Residence 5821 Mustange Circle, Port St Lucie, FL 34953 Notes: Weather. St Lucie Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 gr4b Heating Summary Structure 26855 Btuh Ducts 7858 Btuh Central vent (53 cfm) 1703 Btuh Outside air Humidification Piping Equipment load Infiltration Method Construction quality Fireplaces 0 Btuh 0 Btuh 36416 Btuh Simplified Average 0 He 23'n4g Coo21�g Area Volume (fP) 300677 300677 Airchanges/hour 0.32 0.16 Equiv. AVF (cim) 160 80 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat 100 EFF 10.3 kW 35185 Btuh 20 0 1567 cfm 0.045 cim/Btuh 0.60 in H2O Sensible Cooling Equipment Load Sizing Structure 18577 Btuh Ducts 13730 Btuh Central vent (53 cfm) 904 Btuh Outside air Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 31684 Btuh Latent Cooling Equipment Load Sizing Structure 3898 Btuh Ducts 2879 Btuh Central vent (53 cfm) 2064 Btuh Outside air Equipment latent load 8842 Btuh Equipment Total Load (Sen+Lat) 40526 Btuh Req. total capacity at 0.70 SHR 3.8 ton Cooling Equipment Summary Make Lennox Trade LENNOX Cond 14ACX-047-230* Coil CBA27UHE-048-230*++TDR AHRI ref 10259382 Efficiency 13.0 EER,16 SEER Sensible cooling 32900 Btuh Latent cooling 14100 Btuh Total cooling 47000 Btuh Actual air flow 1567 cfi-n Air flow factor 0.048 ctrn/Btuh Static pressure 0.60 in H2O Load sensible heat ratio 0.79 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -F- wr1ghtsoft- 2018-Nov2012:56:04 �� Rigtt-Sate® Uriversal201818.0.31 RSU27054 Page 2 Iuooame&XWngttsoftWACIMrseResiderce.np Calc=MJ8 Frort Door faces: NW Project Summary Job: 527 Air Calks LLC J rY Date: Nov19, 2018 (Unconditioned By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach FL32966 Phone: 772.800.8413 Email: viddlyme@aircalcs.com For. Muse Residence 5821 Mustange Circle, Port St Lucie, FL 34953 Notes: Design Information Weather: St Lucie Co Intl, FL, US Winter Design Conditions Outside db 41 OF Inside db 70 OF Design TD 29 OF Heating Summary Structure 0 Btuh Ducts 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 0 Btuh Infiltration Method Simplified Construction quality Fir Average i places 0 Area (ft� Heating U Cooling 0 Volume (fP) 0 0 Airchangeslhour 0 0 Equiv AVF (cfm) 0 0 Heating Equipment Summary Make n/a Trade n/a Model n/a AHRI ref n/a Efficiency Heating Input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat Summer Design Conditions Outside db 90 OF Inside db 75 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 grAb Sensible Cooling Equipment Load Sizing Structure 0 Btuh Ducts 0 Btuh Central vent (0 cfm) 0 Btuh Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 0 Btuh Latent Cooling Equipment Load Sizing Structure 0 Btuh Ducts 0 Btuh Central vent (0 cfm) 0 Btuh Equipment latent load 0 Btuh Equipment Total Load (Sen+Lat) 0 Btuh Req. total capacity at 0.70 SHR 0 ton Cooling Equipment Summary Make n/a Trade n/a Cond n/a Coil n/a AHRI ref n/a n/a Efficiency 0 Btuh Sensible cooling 0 Btuh Latentcooling 0 OF Total cooling 0 cfm Actual airflow 0 cfm/Btuh Airflowfactor 0 in H2O Static pressure Load sensible heat ratio Calculations approved byACCA to meet all requirements of Manual J 8th Ed. n/a 0 Btuh 0 Btuh 0 cfm 0 cfm/Btuh 0 in H2O 0 wr14ghtsoft- 2018-Nov-2012:56:04 Right -Sate® Uriversal201818.0.31 RSU27054 Page 3 _JuVbcunerislWdgtisoftHVAC\MuseResidence.rLp Calc=MJB Front Door faces: NW Air Calcs, LLC Right-J® Worksheet Entire House Air Calcs, LLC 7550 Hidden Hammodc LR Vero Beach, FL32966 Phone: 772.800.8413 Email: viddlyme@aircalcs.com Job: 527 Date: Nov19, 2018 By: Vicki Lynne Barenberg 1 Room name Entire House (RestofHouse) 2 E)posed wall 284.3 ft 218.3 It 3 Room height 12.7 ft 12.8 ft 4 Room dimensions 5 Room area 2852.5 T 2342 5 T Ty' Consbuclion U-value Or HTM Area (tt=) Load Area Load number (BtuhAt;-°F) (Btuh1Rn or perimeter (fl) (Btuh) or perimeter (f8 (Btuh) Heat Cool Gross N/PIS Heat Cool Gross NIP/5 Heat Cool 6 G 13A5ocs 1* Windom ` .0.125 0.300, ne ne 2.76 _ _;8.70 1.12 16.34,,,- 896 .36 - -666 0 - - - 2374 .- . _ 313 1482 ,- ,586 691 „-. 36 - 655 _ 0 M 313 1482 588 IW - 11 13A-5ocs MVWlndows_- 13A5ocs 10A-c. Mir Windows *Windows 0.125 0.300 0:126 0.300 0.300 0.300 , e _ e.. se se se se 3.63 _ ... 8.70 2.63 8.70 8.70 8.70 226 -- 20.77 1,64 11.74 15.68 8.93 42 - _ _ 17 484 48, ' 18 _ 27 25 - 0 263 4 2 27 92 -_ - ---148 692 418 157 231 58 - -- - _353 432 563 282 237 42 -- --..- 17 284 48 18 27 25 -- ------- 0 191 4 2 27 92 .. --- .148 692 418 157 231 58 -- -- 353 432 563 282 237 W i' 11N0 0.350 .se:. ., 0.00 -, 0.00' .,. '128 128 ._.. 0.. 0 ., .0 .,., 0 0 _ 0 W 1 13A-5ocs r* ndcm.. .._.. 13A5ocs My Windows 0.125 0.300 0.125 0.300 s s - sw sw 3.63 . - _8.70 2-55 8.70 226 _- . -8.93 1.59. 13.97 46 . -_..-. ---17 891 - 9 29 - _ . - _ 17 864 ' 3 105 - „ 148 2201 81 66 - _ _ 152 1377 130 46 _ 17 636 9 29 - 17 609 3 105 _ 148 M01 81 66 .. - 152 1377 130 W. Nty Windows 0.300 sw_, .. _ 8.70, 15.68 18 - 2 ... . '157 _ 282 18 2 , _ 157 282 IV 13A5ocs . 10A-c 0.125 0.300 nw nw 3.63 8.70 226 8.17 594 48 425 0 1540 418 961 392 594 48 425 0 1540 418 961 392 *Windom 0.300 nw 8.70 10.81 32 0 278 346 32 0 278 346 NV Windom 0.300 nw 8.70 16.34 36 0 313 588 36 0 313 588 WWlndows._ 0.300 _nw- - 8.70 16.34 _ . _ ._465._. _,... $74 ..- -5<1 ---. - --.._ -_0..- _ .-....465 _ ....874 P -- -, - 126-0sw . 0.097 - _ 2:81 ... 1.60 _ ..._._64 _ 250_ .__ .. _0 _ _ ,. 250 . _ _ M3 _ 400 250 250 _ 703 40Q C _ 16xi"ml 0.408 - 1.35 1.05 3429 3429 4645 3587 2828 4645 3587 F 22Atpl - 6.989.. _ 2202 . _ 0.00 _ _. 2853 � - 284 .. 6260 - -_ 0 _-. 2343 _2828 _ .218 6260 - 0 6 c) AED emersion 250 250 Envelope loss/gain 21744 13400 21744 13400 12 a) Infiltration 5111 1357 5111 1357 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 4 920 4 920 ' ApplianceVother 2900 2900 Subtotal (lines 6to 13) 26855 18577 26855 18577 Less external load Lesstransfer 0 0 0 0 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 26855 18577 26855 18577 15 Ductloads 29% 74% 7858 13730 29% 74% 7858 13730 Total room load 34713 32307 34713 32307 Air required (clm) 1567 1567 1567 1567 Calculations approved NACCA to meet all reouirements of Manual J 8th Ed. -Fj- w�igF.tsoTtt� 2018-Nov-2012:56:04 .1- A& ..'r...- Right-Sute®Universal 201818.0.31RSU27054 Pagel lu)Doaments\WdgtboftWACIMrseResidence.nip Catc=MJB Front Door faces: NW Air Calcs, LLC Right-M Worksheet Job. 527 Date: Nov 19, 2018 Entire House By- Vicki Lynne Barenberg Air Calm, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: viddlyme@aircalcs.com 1 Room name (Unconditioned) 2 E):posecl%dl 66.0 ft 3 Room height 12.3 ft 4 Room dimensions 5 Room area 510.0 fP Ty I Construction U-value Or HTM Area (ft) Load Area Load number (BtuWF) (Bbih/M or perimeter (fi) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross NIPS Heat Cool 6 W. L--G' 13A5ocs Nth Windows_ 6.125 0.306 ne ' ' ne 2:7'6 8.70 1.72 16.34 205 , 0 205 0 0 0 -0 0 W , 13A-50cs 0.125 a 3.63 226 0 0 0 0 11 U *Windom 13A5ocs 0.300 0.125 . e . se _ 8.70 2.63 . - 20.77 , 1.64 - 0 . 200 -. - 0 72 - -- 0 0 - --0 0 - W ' , M-c ?4Windows NyWlndovs 0.300 0.300 0.300 se se se 8.70 8.70 8.70 11.74 15.68 8.93 0 0 0 A 0 0 . 0 0 0 0 0 0 11 NO ... - . 0.350 ,-. se. 0.00 0.00 . 128, 128 . 0 - 0 WI - 13A-5ocs W Windows 13A-5ocs 0.125 0.300 0.125 s s sw 3.63 8.70 255 226 - 8.93 1.59 0 0 255 0 . - . 0 . • 255 0 0 0 0 0 0 VU I Ny Window 0.300 sN 6.70' 13.97 0 0 0 0 -G WVVind. 13A5ocs 0.300 0.125 sw . nw 8.70 3.63 - 15.68 226 - 0 0 0 0 _ 0, 0 0 0 W 10A-c 0.300 nw 8.70 8.17 0 0 0 0 WWlndows 0.300 nw 8.70 10.81 0 0 0 0 WVVIndows 0.300 nw 8.70 16.34 0 0 0 0 NNWlndovs 8.70 16.34 0 0 _ .0 _... -0 P • . t _ . .. _ 126-0sw _ . --,,0.300,--nw- 0.097 . - C 16X19-Oml OA08 - 1.35 1.05 601 6.01 0 F l 22A 1p1 - 0.989 -:. 2202 0.00 a 510 66 0 _0 0 6 c) AED emersion 0 Envelopelosslgain 0 0 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains Occupants@ 230 0 0 Appiiancesrother 0 Subtotal (lines 6 to 13) 0 0 Less 6demalload 0 0 Lesstransfer 0 0 Redistribution 0 0 14 Subtotal 0 0 15 Du oa 10% 0-/.l 0 0 Total room load 0 0 Air reclbred(dm) 0 0 Calculations approved NACCA to meet all reauirements of Manual J 8th Ed. -FPI- 2018-Nov-2012:56:04 „..._, Rigtt-SuteOUriversa1201818.0.31 RSU27054 Page ACCA _.kflDoamerds\WrigitsoftHVACWhseResidence.np Calc=MJ8 Front Door faces: NW OP i N 0 9D O N 0 CD rn CD O W A CnA W N CA �• W CnA WNW —a 0 T '0 -8�- a � Ma 2 �; �`r �� q c� o Q rC o• N W- W Z A3 - W o. r ;E H c� o �..—CD 3 Q n g a o � g g g go=3 E3 EEii AA 3: l9 o. v •S� S� Si Si Si r5i o 000a0000p000000000;0000'� a W(W W:..�.W fd �0 W'O BOO OOO NO O'NO N(A O NO N.ON, mm 4 0 a 0 noocnocnOogScnotn'ocnCD �J �541 yyCD I CD: W O OD OD OD W co m�• �DV V YI V'pi �I V bi'�I p� O V V V �.V p� V m; 1p'A• :O OOO W o O,WO W OOOO WO WOW' �_ W O O 01 O 0D N C7t W N W N O� OD 8 =t N — to ! o' m' !D 00 oNioNomof�iN;�N ., o�o�'�i��rnw�.rnwrnowaD.Arn, rn rn. N CD - OND•Ni O'.. .. 'N Cn ((nnWW,,pp �Cpp .... wC�D� .. N�Apppp�AWWCOi (D N N o A - CD O:A 0IN OD A(A OW,V OV(-CO CD .. :a o 0; O OOOCn N.N :. co � O NA c0` co t0•V COV�OCn OC11! co .. . _ to S. (Cnn 0I m�f pppp aUf pppp C7t � � ,p C� (Df NN N •mA"O�•Q1�V�A�tnWO�A O(M., ..W CTA V W 00 CM O O O Cn O� O (T W.f11 W M N O V� �1 00 O—V (n W V CifO - N WC� Cn- nA!CW 8K3 V V VOO 0 O O -OVNNyW, co W oA C.N! OVOONw OO N Cn O o o f08'O o o Ob O O'O OO �: �'_ N W (O OD o •_ - V. OHO OOO 9'0 O D'O O'0 O'O0 O'O OO" V x cn co CO O(A Cns ((nn A�OOO O OCn O V A C�nD AWN' !� CO i ' W m0C71O000DO 0AO OO OOO O'O OHO: W �. O S 8 SOD OOND 9 'O,WOA W'.00 � OOO OND O0 00 OOO oOC 0000,0 OO m g 3 I Air Calcs, LLC Right-J® Worksheet Job: 527 (Rest of House) Date: Nov19, 2018 Air Calcs, LLC By: Vicki Lynne Barenberg 7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone: 772.800.8413 Email: viddlyme@aircalcs.com 1 Room name r&ster Bath WrR CST 2 Exiiosedwell 11.0 It 3.5 It 3 4 Room height Room dimensions 12.3 ft heaticool 1.0 x 124.3 ft 12.3 ft heat/cool 7.0 x 3.5 ft 5 Room area 124.3 � 24.5 ff= Tyi Construction U-value Or HTM Area (f Load Area (it) Load number (Btuhffl',) (BtuhM or perimeter (il) (Mh) or perimeter (ft) (Btuh) Heat Cool Gross N/PIS Heat Cool Gross N/PIS Heat Cool 6 V# ). 13A-5ocs 0.125 ne 3.63 226, 0 .... - 0 0 6 ... _0 .. , 0 0 0 lW Windows -. ,. ;- -, _ _ 0.300 _ne 810 16.34 . 0 0 _ 0 _ _ 0, _ _ '0 0 - _ a- 0 WI - �--(� 13A 5= 0.125 a 3.63 226 0 0 0 0 0 0 0 0 11 *Wind. - _ 13A5ocs _ 0.300 0.125 __e_ se 8.70 3.63 . 2077 226 -0- 0 -0 0 _- .0 0 _ _ _ 0 0 _ 0 0 -_ .0 0 _ _ 0 0 _ 0 0 W I -.LG 10A c W Wlndows 0.300 0.300 se se 8.70 8.70 11.74 15.68 0 0. 0 0 0 0 0 0 0 0 0 0 0 0 0 0. W Windows 0.300 se 8.70 8.93 0 0 0 0 0 0 0 0 11NO ,,. -... _.0.350 -se ... .0.00. 0.00:. .;. -0 0 ., 0. _ 0. ._: 1_0 _.0 0 0 WI� � U 13A5ocs 11MWIndows 0.125 _.0.300 s S 3.63 8.70 226 _..8.93 0 0 0 .0 0 0 0 .. 0 0 -- 0 0 _ . 0 0 0 0 0 ... ..... 13A5ocs 0.125 id 3.63 _ 226 ` 110 101 365 228 35 -. 35 127 79 My Windows My Windows 0.300 0.300 sw sw 8.70 8.70 13.97. 15.68 9 0 3 0 81 0 130 0 0 . 0 0 0 0. 0 0 0 W 13A5ors 0.125 nw 3.63 226 _ 0 0 0 0 _ _- 0 0 _ 0 0 10AC 0.300 nw 8.70 8.17 0 0 0 0 0 0 0 0 My Windows 0.300 nw 8.70 10.81 0 0 0 0 0 0 0 0 NVWindows 0.300 nw 8.70 16.34 0 0 0 0 0 0 0 0 NVWindows 0.300 16.34 0.._ 0 0 0 ... 0 0 0 0 P' C ._ 12B-0sw- 097 .0 _nvv •_- _ _8.70 2.81 1.60'... _ _ _ - 0 ... 0 . _.... _ 0 .. ._ .. 0- .__ _ .. 0 -- - _ 0 - - 0 0 C 16X19-0ml OA08 - 1.64 127 146 146 240 ,` 186 29 29 47 - 37 F 22A-tpl 6.989 _ - 28.68 _ 0.00 124 -11 315 _ , .., 0 . '25 - , . _ 4 _ 100 0 6 c) AED excursion 23 -8 Envelope Ioss(gain 1002 566 275 107 12 a) Infiltration 245 65 78 21 b) Room ventilation 0 0 0 0 13 Internal gains Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1247 631 353 128 Less external load 0 0 0 0 Less transfer 0 0 0 0 14 Redistribution Subtotal 0 1247 0 631 0 353 0 128 15 Ductloads 291 74 o 365 466 29% 74% 103 95 Total room load Air required (dm) 1612 73 1098 53 456 21 223 11 Calculations approved WACCA to meet all reauirements of Manual J 8th Ed. _ -Fp- wrigt�tsoTt 2018-Nov-2012:56:04 A^ `A Right-SkileO Uriversa1201818.0.31 RSU27054 Page 4 ki Doamerts\Wdgttsoft WACW1kse Residenoe.nip Calc= MJ8 Front Door toes: NW Air Calcs, LLC i Right-JO Worksheet (Rest of House) Air Caics, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: viddlyme@aircalcs.com Job: 527 Date: Nov 19, 2018 By: Vicki Lynne Barenberg 1 Room name WIC Bed 2 2 Exposed%dl 0 ft 16.0 ft 3 Room height 12.3 ft heat/000l 12.3 ft heat/cool 4 5 Room dimensions Room area 1.0 x 111.6 It 111.6 ft, 1.0 x 186.8 It 186.8 fF Ty Construction U-value Or HTM Area (T) Load Area (11 Load number (Btuhlft�-*I (BtlihAt� or perimeter (f0 (Btuh) or perime (ft) (Btuh) Heat Cod Gross N/P/5 Heat Cool Gross N/P/S Heat Cool 6 ITI , 13A-SoCs 0.125 ne 3.63 226 6 0 0 0 0 0. 0 0 l_G WWindows.. 0.300 ne.:. _ _ 8.70 . ,. 16.34 ..' _` 0 . _. A .... _ 0' - _'- - 0 .. _ . - 0 _ 0 0 _0 W 13A-50ks I*WIndows 0.125 0.300 a e 3.63 8.70 226 20.77 0 0 0 0 0 0 0 0 0 0 0 W' 1 11 13Ar5ocs 10Ac NV Wlndam 0.125 0.300 0.300 _ se se se 3.63 8.70 8.70 226 11.74 15.68 0 0 '. 0 - 0 0 0 _ ---0 0 0 0 -----.0-- 0 0 0 -------_ 0 0 0 ..--- ----p 0 0 0 .0 0 0 0 -- - - .0. 0 0 0 *Windows 0.300 se 8.70 8.93 0 0 0 0 0 0 0 0 b ,11 N0. - ... ._ s � 0.350 se 0.00 ... 0.00 0 .0 .. 0 . - _. , . 0, _0 .. .,.. 0 0 0 W LI-G, 13A5ocs 0.125 s 3.63 226 0 0 0 0 0 0 0 0 W Wlndov s .._.. ._ ._ 13A5oCs 0.300 0.125 ._ S ... sw .,8.70 3.63 _ .. 8.93 226 0 0 . 0"'.... 0 0 0 _ .. _ 0 0 , 0 ' 160 0 142 _... 0 515 _ .... 0 321 W i W WlndOws 0.300 sw 8.70 13.97 0, 0 0 0 0 0 0 0 *Windows - 0.300 sw 8.70 15.68 „° , 0 0 0, 0 18 2 157 • 282 W 13A5ocs 0.125 nw 3.63 _ 226 0 0 0 0 0 0 0 0 10Ac 0.300 nw 8.70 8.17 0 0 0 0 0 0 0 0 W Windows 0.300 nw 8.70 10.81 0 0 0 0 0 0 0 0 W Windows 0.300 nw 8.70 16.34 0 0 0 0 0 0 0 0 MV Windows - 0.300 - nw _ 8.70 16.34 . 0 0 0 -0 .. -0 0 P 12B-0sw .. _ - 0.097 : -- � , 281 - .1.60 ',_ . 0 0 _ 0 0 135 - 135 386 . 216 C 16X19-0mi 0.408 - 1.64 127 132 132 216 167 220 220 361 279 F 2wpl ,. 0.989 .- _ 28.68 woo 112 0 - 0 - -0 _ , 187 16 459 0 6 c) AED excursion -10 31 Envelope loss/gain 216 157 1871 1130 12 a) Infiltration 0 0 357 95 b) Room ventilation 0 0 0 0 13 1 Internal gains Oc upants@ 230 0 0 1 230 Appliancesrother 0 0 Subtotal (lines6 to 13) 216 157 2228 1455 Less e�emal load Lesstransfer 0 0 0 0 0 0 0 0 Redisbibution 6 4 0 0 14 Subtotal 222 161 2228 1455 15 Dudloads 29% 74% 65 119 29% 740/6 652 1075 Total r6om load 1 287 280 2880 2530 Air required (dm) 113 141 130 123 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed. �i wrightsoTtA 2018-Nov-2012:56:04 ACC:K RigYtSute®Urtversa1201818.0.31 RSU27054 Pages ki Doamerts\WdgtboftHVACIMuse Residence.np Calc= MJ8 Front Door faces: NW Air Calcs, LLC RighW@ Worksheet Job: 527 (Rest of House) Date: Nov19, 2018 Air Calcs, LLC By: Vicki Lynne Barenberg 7550 Hidden Hammock LR Vero Beach, FL32966 Plane: 772.800.8413 Email: viddlyme@aircalcs.cem 1 2 Room name Exposed wall Bath 2 O ft Linen O ft 3 4 5 Room height Room dimensions Room area 12.3 it heaycool 10.5 x 5.5 ItIt3.0 57.8 � 12.3 ft heat/cool x 5.5 16.5 tF Ty Consbucion U-value Or HTM Area fl�Load Area I number (BhuhAt--°� (BtuhM or perimefer (f4 (13 h) or perimeetter (i) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PIS Heat Cool 6 { 13A5ocs 0.125 ne 3.63 226 0 0 0 0 0 0 0 0 L, r NyWlndaws _ 0.300 ne_ 870 16.34 0 0 0 0 0 W I 13A-50cs 0.125 a 3.63 226 0 0 0 0 0 0 _ _ 0 0 11 NNWindows _ _ 13A50M 10Ac WWindows My Windows 0.300 0.125 0.300 0.300 0.300 a se se se se 8.70 3.63. 8.70 8.70 8.70 _ 20.77 226 11.74 15.68. 8.93 _ , 0 0 0 0 0 0 0 0 0 0 0 0 0 0 _ _ __ -0 0 0 0 0 _ 0 0 0 0 0 0 0 0 0 0 _ 0 0 0 0 0 0 0 0 0 0 W f i V)/ �- 11N0 ... - _ 13A5ocs .0.350 0.125 .. se s 0.00 3.63 - '0.00 226 - .0 0 .. 0- 0 .. -0 0 - _ 0, 0 ..,- 0 0 0 0 .. 0 0 0 0 NNWlndows __ 13A5ocs .0.300 0.125 _-s._. sw 8.70. 3:63 8.93 226 0 ' 0 _ _. 0 0 - 0.- 0 _-- 0 0 0 - 0 --. 0 0 0 0 0 0 . 0.300 sw 8.70 13.97 0 0 0 0 0 0 0 0 .Windows Windows 0.300 sw 8.70 0 0 0 0 0 0 0 0 W _- 13A 90M 0.125 nw 3.63 _ _15.68 226 0 6 0 0 0 0 0 0 1OAc 0.300 nw 8.70 8.17 0 0 0 0 0 0 0 0 WVVIndows WVvindows 0.300 0.300 rw nw 8.70 8.70 10.81 16.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 M✓ Windows 16.34 0 0 0 o 0 0 0 P I- - 12B-Osw, , .- . . _0.300 9.097 -nw - - -. . _8.70 . 2.81 _ 1.60 . - _ , 0 0 - -- 0 - - . 0' - - - - . .. ,. 0 0 - .0 .01 _ _ 0 C 16X19-0_ ml OA08 1.64 127 _ 68 68 112 _ 86 20 20 32 25 F -I:. _ _ 22A-tpl 0.989 _ _ - . _ ... 28.66 _ 0.00 _ . 58 .. 0 - 0 - - 0 _ 17 0 '0 0 6 c) AED excursion -5 -2 Envelope Iosslgain 112 81 32 23 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Applianceslother 0 0 Subtotal( lines6to13) 112 81 32 23 14 Less eidemal load Lesstransfer RediWibution Subtotal 0 0 10 122 0 0 8 88 0 0 -32 0 0 0 -23 0 15 Ductioads 29% 74% 36 65 29% 74% 0 0 Total room load Airrequired(dm) 158 7 154 7 0 0 0 0 Calculations approved NACCA to meet all reauirements of Manual J 8th Ed. wrigF�tsoft� 2018-Nov-2012:56:04 12igttSrite®Uriversa1201818.0.31 RSU27054 Page6 IalDoamn eris\WdgftsoftHVACIMuseResiderce.p Calc=MJ8 Front Door faces: NW Air Calcs, LLc RighW@ Worksheet (Rest of House) Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Emajl:,Addlpm@aircaics.com Job: 527 Data: Nov19, 2018 By: Vicki Lynne Barenberg 1 Room name Laundry Den/Study 2 EVosed wall 0 ft 11.0 ft 3 4 5 Room height Room dimensions Room area 123 ft heat/cool 6.5 x 8.0 ft 52.0 flz 12.3 ft heat/tool 11.0 x 13.0 ft 143.0 fP Ty Const dion U-value Or HTM Area (il=j Load Area (T) Load number (BtuhF-'q (BbrhM or perimeter (ft) (Bbih) or perimeter (to (Bbih) Heat Cod Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A5oks .. - -- 0.125 ne 3.63 - 226 0 0 _.. 0 0 ._ -.. ..0 .. 0 - 0 - 0 11 L-=C MyWlndows 13A5s o *Wndows. _ 13A5ocs 10A-c 'WtyWindows Wy Windows 0.300 0.125 _ 0.300 0.125 0.300 0.300 0.300 ne: a "._e se se se se - 8.70 3.63 _8.70 3.63 8.70 8.70 8.70 16.34 226 - _ 20.77 226 11.74 16.68 8.93 _ 0 0 0 0 0 0 0 1.0 0 0 0 0 0 0 "- _ . - _ 0 0 0 0 0 0 0 _0 0 _ , 0 0 0 0 0 0 0 _ - - 0 110 0 0 27 0 0 _- _ 0 84 0 0 27 0 0 _ 0 303 0 0 231 0 0 _ 0 189 0 0 237 I W _ �---G W ? 11N0 .. _ 0.350 se - ..0.00 '_ . 0.00 0 - .0- .. 0 __ . - ,0 . .01. .: 0 ,. 0 . _ .0 W ,W I 13A5oks WbWindow5 - _ 13A5oks 0.125 . 0.300 0.125 s - s sw 3.63 8.70 3.63 226 8.93_- 226 0 - 0 0 0 _ _- - 0- 0 0 .0 0. 0 - _ 0 0. 0 _ - _-_ 0 0 0 _ 0 0 0 - 0 0 0 0 0 W Windows 0.300 sw 8.70 1.97 0 0 0 0 0 0 0 0 L:_ W 1 Windows 13A5as 0.300 0.125 sw, nw 8.70 3.63 13.97 226 0_ 0 0 0 0, 0 ,. 0 0 0--. 0 _ 0 0 0 0 0 0 10A-c 0.300 nw 8.70 8.17 0 0 0 0 0 0 0 0 NV Windows NyWindows 0.300 0.300 nw nw 8.70 8.70 10.81 16.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNWindows nw 8.70 0 0.__0 0 0 R. 126-)sw. .. . ---0.300 0.097 - - 2:81, ..16.34 1.60 . _: _ . 65 65 .. , 183 -- ... 104 .. .._ . 50 .--.0- 50 - -0 _ 141 --0 80 C 16X19-0ml 0A08 - 1.64 127 61 61 101 78 173 173 284 219 F 22A-tpI 0.989 _ - 28.68 0.00 52 0 0. ,_0 143- 11 _ _ 315 _ 0 6 0) AED excursion -42 -49 Envelope loss/gain 283 140 1273 676 12 a) Infiltration 0 0 245 65 b) Room ventilation 0 0 0 0 13 Internal gains Occupants@ 230 0 0 0 0 Appiiances(other 500 0 Subtotal (lines6 to 13) 283 640 1518 741 Less odemal load 0 0 0 0 14 Less transfer Redisfibution Subtotal 0 0 283 0 0 640 0 0 1518 0 0 741 15 Dud loads 29% 74% 83 473 29% 74% 444 548 Total room load Air required(clm) 366 17 1113 54 1963 89 1289 63 Calculations approved bVACCA to meet all requirements of Manual J 8th Ed. �?- wrGghtsoft� .4C'TGP� Rigtd SJte@ Uriversal 201818.0.31 RSU27054 2018 Nov 201 Pa6e 7 JdlDoamertslWdgtboftWACIMiseResidenoe.rLp CaIc=MJ8 Front Door faces: NW 9 Air Calm, LLC Right-M Worksheet (Rest of House) Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicidlyme@aircalks.com Job: 527 Date: Nov19, 2018 By. Vicki Lynne Barenberg 1 Room name Foyer Bed 3 2 Exposed Hall 8.5 It 39.3 ft 3 4 5 Room height Room dimensions Room area 13.3 ft heat/cool 8.5 x 13.0 It 110.5 ft2 12.3 ft heatI000l 1.0 x 221.3 ft 221.3 T Ty I Construclion U-value Or HTM Area (ft?) Load Area (if) Load number (BbhlfF-g (BtuhM or perimeter (f8 (Btrrh) or perimeter (ft) (Btrrh) Heat Cool Gross N/P/S Heat Cool Gross NIPIS Heat Cool 6 W, I 13Ar5oks 0.125 ne- 3.63 .226 0 0 - -0 - 0 135 _ .. 135 489 305 L-=G •WVWndous 0.300 _ne :8.70'. 16.34 . ` 0 0 .._ 0 --0 0 0 0 0 W� ' 13A150cs 0.125 a 3.63 226 ..•- 0 _ _ 0 0 0 42 - 25 - _ 92 58 11 NN Windows 13A 5oks 10A C W Windows 0.300 0.125 0.300 0.300 _ _-e se se se - - 8.70 3.63 8.70 8.70 20.77 226 11.74 15.68 -0 94 48 0 -0 46 ' 4 0 _ 165 418 0 -- 103 563 0 17 80 0 18 _ 0 62 0 2 - --__ _ 148 225 0 157 _ 353 140 0 282 - G W W Mclaws 0.300 se 8.70 8.93 0 0 0 0 0 0 0 0 11N0.- -0.350 -se 0.00 -,. • 0.00 -0 . 0 0. , _ 0. r . -. 0 - 0 _ .. .0 ... 0 W� � 13A-5ors M/ Windows - - --- 13A-5ocs 0.125 0.300 0.125 s . s ...-.-- 9N 3.63 --- 3.63 226 -- 8.93 226 0 0 0 0 - -- - - - -0 0 0 0 0 0 0 0 46 . .17 90 29 .. . _ 17 90 105 .. _ 148 326 66 152 204 `-�G- Vdl !L-G� My Windows • 0.300 sw 8.70 13.97 0 D 0 0 0 0 0 0 MyWindaws - 13A-5o s 0.300 0.125 sw nw 8.70 3.63 15.68 226 0.• 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W M-c 0.300 rner 8.70 8.17 0 0 0 0 0 0 0 0 MVWlndows My Windows 0.300 0.300 nw nw 8.70 8.70 10.81 16.34 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 WWindows A300 8.70 16.34 0 0 0 0. 0 P _.. _ 12B-Osw .. 0.097 _nw --_ .2.81 _ 1.60 0' __O ... .... ... _ ------_ _ 0 _. 0. 0 0 C 16X19-Oml OAO_8 - 1.64 127 134 134 219 1.69 274 .. 274 450 348 F 22A-tpL. 0.989 „ - 28.68 - . ,. 0.00 111 ,, . - 9 244. D ,. 221 . -,. 39 1128 0 6 c) AED w ursion 170 -18 Envelope loss/gain 1046 1006 3269 1890 12 a) Infiltration 208 55 877 233 b) Room ventilation 0 0 0 0 13 Internal gains Occupants@ 230 0 0 1 230 1 Appliances(other 0 0 Subtotal (lines 6 to 13) 1254 1061 4146 2353 Less e)6malload Lesstransfer 0 0 0 0 0 0 0 0 14 15 Redishibution Subotal Ductloads 29% 74% 0 1254 367 0 1061 784 29% 741/6 0 4146 1213 0 2353 1739 Total room load Air required (cfm) 1621 73 1846 90 5359 242 4092 198 _ Calculations approved bvACCAto meetall requirements of Manual J 8th Ed. wrightsoft� 2018-Nov-2012:56:04 "�cA MgttSuite@Uriversal201818.0.31 RSU27054 Page 1u10ocunerts\WdgWoftWACIMiseResidenue.nip Calc=MJ8 Front Door faces: NW Air Calcs, LLC Right-JO Worksheet Job: 527 (Rest of House) Date: Nov19, 2018 Air Calks, LLC By. Vicki Lynne Barenterg 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vtddlynre@aircalcs.com 1 Room name Bed 3 WIC Bath 3 2 Exposed well 6.5 ft 0 ft 3 Room height 12.3 ft heat/eool 12.3 ft heaUcool 4 5 Room dimensions Room area 5.0 x 6.5 ft 325 tF 9.0 x 6.5 ft 58.5 f' Ty Construction U-value Or HTM Area ft� t�Load number (BtuhlfF-°q (B>lihlfl� or perimefer (f0 (Btuh) or penmefer (fQ (B h) Heat Cod Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 1N - 13A 5ocs 0.125 ne 3.6& 226 65 - 65 236 - .. 147 .- - 0 _ .. 0 b 0 L� NyWlndows 0.300 ne 8.70, 16.34 0 0._ 0 - 0 0 0 .. 0 0- W 13A-5ocs NHWlndova 0.125 a e 3.63 226 2077 b 0 _ 0 0 0 _ 0 0 0 0 0 0 0 1N 11 _ - _ A .ri 13ocs 1 OA-c NtyWindows . .0.300 0.125 0.300 0.300 _ se se se -_8.70 3.63 8.70 8.70 -_ _ 226 11.74 15.68 _ - _ -, 0 0 0 0- 0 t) 0 0' 0 0 0 0 0 0 0 -- 0 0 0 0 0 0 0 0 NyWindows 0.300 se 8.70 8.93 0 0 0 0 0 0 0 0 11N0 .,. 0.WO se. .. -0.00 -0.00 - 0 _ .0-, 'A", _ 0 -0 0 - 0, _ 0 WI - �j 13M= NN Windows_ .. 13A5ocs 0.125 _. 0.300 0.125 s . s - Sw: 3.63 .... 8.70 3.63 226 ._ .. 8.93 226 0 , _ 0 0 0 - 0 0 0 - - __0 0 0 - - -- 0 0 0 0 0 0 - - -0 0 0 0 0 01 0 -0 0 �-G Windows 2Windows 0.300 9N 8.70 13.97 0 0 0 0 0 0 0 0 _ 0.300 sw _ 8.70 15.68 - - 0 0 0 0, 0 0 0 0 W 13A$ocs 0.125 nw 3.63 226 , 0 _ 0 0 0 0 0 0 0 0.300 nw 8.70 8.17 0 0 0 0 0 0 0 0 IW Windows 0.300 nw 8.70 10.81 0 0 0 0 0 0 0 0 P4 Windows 0.300 nw 8.70 16.34 0 0 0 0 0 0 0 0 *Windom - 12B-Osw 0.300 0.097 - nw .'c -8.70 _ , . ..2.81. _ _..16.34 - -1:60 0- - 0 0 0 - ;_ '... 0 0 0 0 .. 0 - 0 .. . ,. , 0 ._ -0 0 p410A-c F j C 16X19-Oml OA08 - 1.64 127 40 40 66 51 73 - 7.3 F 22A-tpl . - 6.989 - 28.68 0.00 33 ., 7 - 186 0 59 _ . .. . 0 _119 0 _92 0 6 c) AED excursion -15 -6 Envelopelosslgain 488 184 119 86 12 a) Infiltration 145 38 0 0 b) Room ventilation 0 0 01 0 13 In" gains Oocupants@ 230 0 0 0 0 i Applianoeslother 0 0 Subtotal (lines 6 to 13) 633 222 119 86 14 Less eidemalload Less transfer Redistribution Subtotal 0 0 0 633 0 0 0 222 0 0 0 119 0 0 0 86 15 DUdloadS 129%1 740 185 164 299/0 74% 35 64 Total room load 818 386 154 150 Air required(dm) 37 19 7 7 Calculations aaaroved bvACCA to meet all reauirements of Manual J 8th Ed. { wr Ggtitsoft ^ RigHSu2018-Nov-2012:56:04te®Uriversa1201818.031 RSU27054 Page JulDokunerdslWdghtsoftHVACWuseResdence.rkp Calc=MJ8 Front Door faoes:NW Air Calcs, u_c Right-JO Worksheet (Rest of House) Air Calm, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone:772.800.8413 Email: vfddlyme@aircalcs.com Job: 527 Date: Nov19, 2018 By. Vicki Lynne Barenberg 1 Room name tGtten Dining 2 ExiSosed Hsll 20.0 ft 35.0 ft 3 4 5 Room height Room dimensions Room area 12.3 ft heat/000l 14.0 x 20.0 ft 280.0 82 12.3 ft heat/000l 14.0 x 13.0 ft 182.0 ft= Ty, Construction U-value Or HTM Area ( Load Area fft��Load number (Btuh/fP-°F) (BbrhM or perimeter (fl) (Btuh) or perimeter (iq (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 j . L--, G 13A-5ocs My Windows 13AZocs 0.125 0.300 0.125 ne ,_ne a 3.6-3 8.70 3.63 - - '226 , 16.34 226 : 2-00 ._ 0 0 , 200 -,0 0 -725 - 0 0 463 ... 0 0 130 36 0 94 _.. 0-, 0 341 313 0 213 588 0 W L- G 11 My Windows _ i aA-5ocs _ 0.300 0.125 _ e, - se - 8.70 3.63 _ _ 20.77 226 _ 0 0 - _ 0 0 . __ _ _ _ 0 0 _ 0 6 0, 0 0 0 W 10A-c WyWindows 0.300 0.300 se se 8.70 8.7Q 11.74 15.68 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 } W Wlndows 0.300 se 8.70, 8.03 0 0 0 0 0 0, 0 0 11NO _ 0.350 se _, .0.00 _ . 0.00 " . . _,0 . - 0 0 . . 0 ,. .. 0 0 0 0. IW� r 13A-5ocs WNWlndows 0.125 0.300 s 3.63 8.70 226 . 0 0 0 0 0 0 0 0 0 0 0 0 0 0 !-(i V,V G 13A Sots WWindows _.. 0.125 0.300 __s sw sw 3.63 8.70 - --8.93 . 226 13.97 ... -,.. 0 0_ 0 0 _ . ..0 0 0 - - .- .- - 0 0 .-- - - .0 80 0 _. 60 0 _ ...... .. 290 0 181 0 I;-GG Nty Windows_ .- 0.300 sv 6.70 15.68 0 0 0 0 0 0 0 0 W 13A-5ocs 0.125 nw 3.63 226 _ 0 0 0 0 140 104 377 235 10A-c 0.300 nw 8.70 8.17 0 0 0 0 0 0 0 0 NyWindows Wy Wlndows 0.300 0.300 nw nw 8.70 8.70 10.81 16.34 0 0 0 0 0 0 0 0 0 36 0 0 0 313 0 588 NNWlndowwws - - . _ . 0.300 _rw 8.70 .. 16.34 0 0 0 0 o 0 0.. 0 P .... 12B-0sw 0.097 , '= 281 - 1.60 _....._---.- 0 ... --- •-- 0 ... - 0 - 0 -- - - ---... 0 ._. - _. 0 _ 0 _ 0 C 16X19-0ml 0A08 - 1.64 127 347 347 - 570 440 226 _ _ 226 370 _ _ 286 F ± 22Artpf _ 0.989 , - _ _ 28.68 ` 0.00 286 _ - - 20 , , . 574 _ 0 182 _ 36 „ 1004 0 6 c) AED excursion -155 -108 Envelope losstgain 1868 738 30081 1983 12 a) Infiltration 446 118 780 207 b) Room ventilation 0 0 0 0 13 Intemalgains: OGmpants@ 230 0 0 0 0 Appiianceslother 1500 0 Subtotal (lines 6 in 13) 2314 2356 3788 2190 14 15 Less extemalload Lesstrfansfer Redislibution Subtotal Ductloads 29% 74a 0 0 0 2314 677 0 0 0 2356 1742 29% 74% 0 0 0 3788 1109 0 0 0 2190 1619 Total rgom load Air required (cim) 2991 135 4098 199 4897 2211 3808 185 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed. wrGgfftsoft^ 2018-Nov-2012:56:04 AC� " ""' "" ^ RigltSute®Universal 201818.0.31 RSU27054 Page 10 _.la'00 erts\WriglisoftWACWhseResidence.rLQ Calc=MJ8 Front Door faces: NW Air Calcs, LLC Right-M Worksheet (Rest of House) Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Plane: 772.800.8413 Email: viddlyme@aircalcs.com Job: 527 Date: Nov19, 2018 By: Vicki Lynne Barenberg 1 Room name GreatRoom 2 Exposed vall 20A ft 3 Room height 13.8 ft heat/aool 4 Room dimensions 1.0 x 468.5 It 5 Room area 468.5 tt2 Ty Construclion U-value Or HTM Area (tt� Load Area Load number (BtuhA� °F) (BtuhAn or perime r (ff) (Btuh) or perimeter Heat Cool Gross NIPIS Heat Cool Gross NIPIS Heat Cool 6 ` 13A-5ocs 0:125 ne 3.63 -226 0 0 �-G .NV Windows .. 13A-5ors NH Windows 0.300 0.125 0.300 : ne a e.. 8.70 3.63 16.34 226 20.77 .. -0 0 • ... 0 0 0 0 0 0 0 . 0 W ' W 11 .. 13A-5as 10A-c Ny Windows - 0.125 0.300 0.300 se se se " . _ .8.70 3.63 8.70 8.70 .... 226 11.74 15.68 _ .. ..0 0 0 0 _ 0 0 0 -_ _- - - -0 0 0 0 .._ ..- -- 0 0 0 W Windows 0.300 se 8.70 8.93 0 0 0 0 11NO _ .... 0.350 . se. 0.00 ..._.0.00 :::.0 . ..: 0 .. :0 , 0-- IW L-G 13A-5o s WWIndam 0.125 s s------- 3.63 8.70 226 _8.93 0 0 0 0 0 - 0 W, _ - 13Ar5oM _0.300 0:125 -- sw 3.63 226 -- _..0 0 _ _0 0 0 0 *Windows 0.300 sw 8.70 13.97 0 0 0 0 I�_rG *Wlndam . 13A5ocs 0.300 0.125 , sw, nw 8.70 3.63 15.68 226 ." - 0 236 - 0 156 - - .. 0 565 0 352 W 10A-c 0.300 nw 8.70 8.17 48 0 418 392 W Wlndovis 0.300 rtw 8.70 10.81 32 0 278 346 NyWlndows 0.300 rrw 8.70 16.34 0 0 0 0 MVWlndows... ._-8.70•.-- 16.34 . 0 - 0 .....0 ... 0 - - 15 . -_.... 12B-Ow - _ _..0.300 0.097 _nw_ , _ - 2.81 1.60 0 - 0 0 _ _ _ _ 0 C , _ 16X19-0ml 0A08 - 1.64 127 565 565 928 717 F i 22A-tpl. 6.989 - _ 28.68 - 0.00 _ 469 _ 20 , - _ 586 0 6 c) AED excursion 278 Envelopeloss/gain 2774 2085 12 a) Infiltration 525 139 b) Room ventilation 0 0 13 Internal gains: Omipants@ 230 0 0 Applianoes(other 900 Sub" (lines 6 to 13) 3299 3124 Less exfemalload Lesstransfer 0 0 0 0 Redisbibubon 16 12 14 Subtotal 3316 3136 15 DUdloads 29% 749/6 970 2318 Total room load 4286 5454 Air required (cfm) 193 264 Calculafions approved WACCA to meet all reauirements of Manual J 8th Ed. wri FrtsoR'^ �- 9 2018-Nov-2012:56:04 .4C& Rigid Sute®Uriversal201818.0.31 RSU27054 Page 11 ki ...lDoamerds\WdghtsoftWACIMcseResiderae.nQ Calc=MJ8 Front Door faces: NW Air Calm LLC RighW@ Worksheet Job: 527 (Unconditioned) Date: Nov19, 2018 By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicidlyme@aircalcs.com 1 Room name (Unconditioned) Garage 2 EJVosed %all 66.0 ft 66.0 It 3 Room height 12.3 ft 12.3 ft unoondit 4 5 Room dimensions Room area 510.0 fl= 20.0 x 25.5 ft 510.0 ft2 Ty Construction number U-value (BfuhM2 T) Or HTM (BkMn Area (ft� or perimeter (ft) Load (Bfuh) Area (T) or perimeter (ft) Load (Bilih) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W, i 131r ' W Windows 13A-5o s ows WWlnd_ _ 13A5ocs 0.-125' 0.300 0.125 0,300 0.125 ne _ ne a _e se 0.00 0.00 0.00 _ 0.00 D.00 0.00 0.00 0.00 - - 0.00 0.00 205 0 0 _ 0 200 -205 0 0 _- _ --_0 72 0 0 0 -0 0 0 _, 0 0 .0 0 "205 0 0 _ 0 200 205 0_ 0 .0-- 72 " 0 0 0 - 0 0 0 0 0 0 0. ,,G W W I 10A-c *Windows WWindows 0.300 0.300 0.300 se se se, 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0, 0 0 0 0 0 0 0 . 1I -- 11 N0 13A5ots 0.350 0.125 se. s ... . 0.00' 0.00 0.00 0.00 _- ... ; , 128 0 128 0 0 0 .. _ 0 0 -.128 0 . - .128 0 . _ 0 0 0 0 NN Windows ...._ ... 13A-5oks .My Windows 0.300 0.125 0.300 ., s.. sw sN 0.00 0.00 0.00 ... _ 0.00 0.00 0.00 -- 0 255 ; 0 . 0 255 0 . - 0 0 0 .0 0 0 .. - -. 0 255 0 _ -_ ..... 0 255 0 .. - 0 0 0 0 0 0 WI fG' W Windows 13X5ocs 0.300 0.125 _sw, nw, _ 0.00 0.00 0.00 0.00 _ 0 0 0 0 0 0 _ 0 0 0 0 0 0 0 0 0 0 10A-c MRr Windows W Windows 0.300 0.300 0.300 nw, nw nw 0.00 0.00 0.00 0.00 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 MWIndows_. ._... - 1213.0sw - _ _ 0.300 aw _nw. - -0.00 0.00 - 0.00, . 0.00 _..0 0 0.. 0. .-..-0 0 -. ....-. .0 _ 0 0 0 .. - 0 _ 0 0 Q 0 . _. 0 P I' C 16X19.0ml OA08 - 0.00 0.00 601 601 0 0 601 601 0 0 F i 22A-tpl _ 0.989 _- . 0.00 . ;0.00 510; a" 66 -, 0 - 0 . , ,510' _ 66 0 A 6 q) AED excursion 0 0 Envelope loss/gain 0 0 0 0 12 a) 141Uaton 0 0 0 0 b) Roomventlaton 0 0 0 0 13 Internal gains: Oocupants@ 230 0 0 0 0 Appliancestother 0 0 Subtotal (lines6 to 13) 0 0 0 0 14 15 Lesseidemalload Lessi ansfer Redis6ibuton Subtotal Ductloods 0% 0%1 0 0 0 0 0 0 0 0 0 0 0% 0%1 0 0 0 0 0 0 0 0 0 0 Total room load Air recibired(dm) 0 0 0 0 0 0 0 0 Calculations aaaroved bvACCAto meet all reauirements of Manual J 8th Ed. -FN&- wri-gt�tsoTe- 2018-Nov2012:56:04 ^ '""" "" R ighl-Sute®Uriversal201818.0.31 RSU27054 Page 12 wlDocunerds\WrigtboftWACWseResidenoe.np Calc=MJB Front Door faces: NW Air Calcs, LLC Duct System Summary (Rest of House) Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.600.8413 Email: vicidlyme(daircalcs.com Project• • For. Muse Residence 5821 Mustange Circle, Port St Lucie, FL 34953 External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest fiction rate Actual airflow Total effective length (TEL) Heating 0.60 in H2O 0 in H2O 0.60 in H2O 0.347 / 0.253 in H2O 0.213 in/100ft 1567 cfm 282 ft Job: 527 Date: Nov 19, 2018 By: Vicki Lynne Barenberg Cooling 0.60 in H2O 0 in H2O 0.60 in H2O 0.347 / 0253 in H2O 0.213 in/100ft 1567 cfm Name Design (Btuh) Htg (crm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Bath c 154 9 9 0.322 6.0 Ox0 VIFx 32.8 75.0 st2 Bath C 150 8 9 0.281 6.0 Ox0 VIFx 28.5 95.0 st7 Bed 2 h 2880 156 147 0.361 7.0 Ox 0 VIFx 11.3 85.0 sty Bed 3 WICI h 386 44 22 0 0 Ox 0 VIFx 0 0 Bed 3-A h 2680 145 119 0.281 7.0 OX 0 VIFx 28.4 95.0 st7 Bed 3-B h 2680 145 119 0.264 7.0 OX 0 VIFx 36.4 95.0 st7 Den/Study h 1963 106 75 0.213 6.0 Ox 0 VIFx 28.4 135.0 st7 Dining h 4897 265 222 0.291 8.0 Ox 0 VIFx 44.5 75.0 st4 Foyer c 1846 88 107 0.221 6.0 Ox 0 VIFx 22.3 135.0 st7 Great Room c 2727 116 159 0.312 7.0 Ox0 VIFX 36.2 75.0 st4 GreatRoon A c 2727 116 159 0.305 7.0 Ox0 VIFX 39.0 75.0 st4 Ivtden c 2049 81 119 0.260 6.0 Ox 0 VIFx 38.7 95.0 SO Kirrne�A c 2049 81 119 0.258 6.0 Ox 0 ViFx 39.8 95.0 SO Laundry c 1113 20 65 0.392 6.0 Ox 0 VIFx 8.6 80.0 st5 Master Bath h 1098 87 64 0 0 Ox 0 VI Fx 0 0 Master suite h 3433 186 168 0.291 7.0 Ox 0 VIFx 44.5 75.0 st2 Master Suite -A h 3433 186 168 0.295 7.0 Ox 0 VIFx 42.8 75.0 St2 WIC c 280 16 16 0.334 6.0 Ox 0 VIFx 29.0 75.0 st2 V TR GST h 456 25 13 0.321 6.0 Ox 0 VIFX 33.4 75.0 st2 _ Ad- wrightsoft- 2018-Nov-2012:56:06 ,ccnurk.ra rni..x.w.a�mrov Right-8uita®Universal 201818.0.31 RSU27054 Pagel Ia-, cmerts%WNgttsoftHVACIMiseResidenoe.nQ Calc=MJ8 Front Door faces: NW Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (ch) Design I FR Veloc Opm) Diam (in) H x W (in) Duct Material Trunk st5 PeakAVF 176 212 0.361 793 7.0 0 x 0 VnIFIX st1 st1 PeakAVF 176 212 0.361 793 7.0 0 x 0 VinIFIX st2 PeakAVF 421 375 0.291 771 10.0 0 x 0 VinlFlx st3 PeakAVF 493 429. 0.213 627 12.0 0 x 0 VInIFIX st7 PeakAVF 493 429 0.213 627 12.0 0 x 0 VnIFIX st3 st4 PeakAVF 659 777 0.258 727 14.0 0 x 0 VinlFlx st9 PeakAVF 162 1 238 0.258 683 8.0 0 x 0 VnIFIX st4 Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name i Size (in) (cfm) (cfm) 00 FR (fpm) (in) (in) Opening (in) Mat Trunk rb2 Ox 0 475 417 118.9 0.213 444 14.0 Ox 0 VIFx rt1 rb3 Ox 0 156 147 99.5 0.254 584 7.0 Ox 0 VIFx rt1 rsb3 Ox 0 335 261 0 0 0 0 Ox 0 VIFx rsb2 Ox 0 809 980 88.2 0.286 555 18.0 Ox 0 VIFx rt1 rb5 Ox 0 106 75 0 0 0 0 Ox 0 VIFx Name Trunk Type Htg (cfm) Clg (dim) Design FR Veloc 00m) Diam (in) H x W (in) Duct Material Trunk rt1 PeakAVF 1439 1544 0.213 585 22.0 0 x 0 VnIFIX WCight30ft- 2018-Nov-2012:56:06 ..,•�• �� mow, . �m RigWSUte®Uriversal201818.0.31 RSU27054 Page wlDoamerWWrigtdsoftHVACWIiseResidence.nip Calc=MJ8 Frort Door faces: NW Air Calcs, LLC Duct System Summary (Unconditioned) Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: viddlynrie@aircaics.com INToject intormation For. Muse Residence 5821 Mustange Circle, Port St Lucie, FL 34953 Bdemal static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0 in H2O 0 in H2O 0 in H2O 0.000 / 0.000 in H2O 0 in/100ft 0 crm 0 ft Job: 527 Date: Nov 19, 2018 By: Vicki Lynne Barenberg Cooling 0 in H2O 0 in H2O 0 in H2O 0.000 / 0.000 in H2O 0 in/100ft 0 cfm _ -Fk wrightsoft® 2018-Nov-2012:56:06 Right-SuteOUriversal201818.0.31 RSU27054 Page 3 ACCK _JdlDoamerts\WdghlsoftHVACIMise,Residence.nQ CaIc=MJB Frort Door faces: NW Level, PACE 2000 :. DB*V {p IAA RCw } 7- t WTR CST C:f7LCYE^1 I^"14C • -5 �9aA2.: + 9can - aa 158z12 DY rc p, 79adm F%a 1 C ,.l '7 14- Bvl13 OHJSW/ 8.8 1� 6x0 I 1 (")V?.1 CT 5 159can Bx0 ')-\y, Ti -9can g• •. R H V.A 1pBctrn � y'� A4kh "8, `„ `Axe A N F41 Allp l 2 AIJ. iLEGI;.'C44 BMW 3 F[ 13iBCEn l g G.M w y 1p ttr. .'-C-,7pxia k 1a5 WT�, �145 Qm 1' �.7 j INC i n n c nc._ ...�......_.,. 7 a 4 : > } g Job #: 527 Performed by -Vicki Lynne Barenberg-for: Muse Residence 5821 Mustange Circle Port St Lucie, FL 34953 Air_ Calcs, _ LLC__ 7550 Hidden Hammock Ln Vero Beach, FL 32966 Phone: 772.800.8413 %Ackilynne@aircaics.com _ Scale: 1 : 194 Page 1 Right -Suite® Universal 2018 18.0.31 RSU27054 2018-Nov-2012:57:27 ightsoft HVACWIuse Residence.rup