Loading...
HomeMy WebLinkAbout2021-02-04 Fire Flow DeterminationProject: Self -Storage 4900 Kings Highway, Fort Pierce, FL Calculations performed: January 28, 2021 Prepared by. OAK INCZAING 1209 Edgewater Drive, Suite 100 Orlando, FL 32804 (407) 951.5915 f iz STN s Cc 51 Self -Storage 4900 Kings Highway Fort Pierce, FL Minimum Required Fire Flow Determination The required fire flow for the building has been determined from NFPA 1, table 18.4.5.2.1 as shown below. Building characteristics: 103,200 square feet, type IIB construction Requirement from NFPA 1 table 18.4.5.2.1: 6,750 GPM Reduction of 75% allowed for approved automatic sprinkler protection per NFPA 18.4.5.2.1. 6,750 GPM x 0.75 = 1,688 GPM Final Needed Fire Flow:1,688 GPM COMMON OAK ENGINEERING, LLC 1209 Edgewater Drive Suite 100, Orlando, FL 32804 Tel: (407) 951.5915