HomeMy WebLinkAboutENERGY EFFICIENCY CODEFORM R405-2017 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: THE MANOR 71 t _c, � V a Builder Name: WYNNE BUILDING CORP.SCANNED THE MA Street: THE MANOR 71 Permit Office: ST. LUC E COUNTY City, State, Zip: FT. PIERCE, FL, ['� Permit Number: BY Owner: WYNNE BUILDING CORP.�e\ \ Jurisdiction: St Lucie County Design Location: FL, Fort Pierce County: St. Lucie (Florida Climate Zone 2 ) 1. New construction or existing New (From Plans) 9. Wall Types(1654.2 sqft.) Insulation Area 2. Single family or multiple family Single-family a. Concrete Block - Ext Insul, Exterior R=4.1 1374.20 ft' b, Frame -Wood, Adjacent R=11.0 280.00 ft' 3. Number of units, if multiple family 1 c. N/A R= W 4. Number of Bedrooms 2 d. N/A R= ft' 10. Ceiling Types (1724.0 sqft.) Insulation Area 5. Is this a worst case? Yes a. Under Attic (Vented) R=30.0 1724.00 ft2 6. Conditioned floor area above grade (ft2) 1724 b. N/A R= ft2 Conditioned floor area below grade (ft2) 0 c. N/A R= ft2 11. Ducts R ft2 7. Windows(153.4 sqft.) Description Area a. Sup: Attic, Rat: Attic, AH: Attic 6 200 a. U-Factor: Dbl, U=0.63 113.35 ft2 SHGC: SHGC=0.25 b. U-Factor: Dbl, U=0.65 40.00 ft2 12. Cooling systems kBtu/hr Efficiency SHGC: SHGC=0.21 a. Central Unit 34.8 SEER:15.00 c. U-Factor: N/A ft2 SHGC: 13. Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a. Electric Heat Pump 34.8 HSPF:8.50 SHGC: Area Weighted Average Overhang Depth: 3.010 ft. Area Weighted Average SHGC: 0.240 14. Hot water systems a. Electric Cap: 50 gallons 8. Floor Types (1723.5 sqft.) Insulation Area EF: 0.950 a. Slab -On -Grade Edge Insulation R=0.0 1723.50 ft2 b. Conservation features b. N/A R= ft2 None c. N/A R= ft2 15, Credits Pstat Glass/Floor Area: 0.089 Total Proposed Modified Loads: 54.13 PASS Total Baseline Loads: 53.99 1 hereby certify that the plans and specifications covered by Review of the plans and g1iE ST4T this calculation are in compliance with the Florida Energy specifications covered by this AV a0� Code. calculation indicates compliance with the Florida Energy Code. PREPA Before construction is completed '..- DATE: this building will be inspected for Ce a a110 compliance with Section 553.908 I hereby certify that this building, as designed, is in compliance Florida Statutes. yC with the Florida Energy Code. COD WE'C¢� OWNER/AGENT: BUILDING OFFICIAL: DATE: DATE: - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with 11402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 7,00 ACH50 (R402.4.1.2). FILE COPY DEC 04 2M 8/28/2018 11:47 AM EnergyGauge® USA Section R405.4.1 Compliant Software Page 1 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT PROJECT Title: WYNNE THE MANOR 71 Bedrooms: 2 Address Type: Street Address Building Type: User Conditioned Area: 1724 Lot # Owner Name: WYNNE BUILDING CORP. Total Stories: 1 Block/Subdivision: # of Units: 1 Worst Case: Yes PlatBook: Builder Name: WYNNE BUILDING CORP. Rotate Angle: 225 Street: THE MANOR 71 Permit Office: ST. LUCIE COUNTY Cross Ventilation: No County: St. Lucie Jurisdiction: Whole House Fan: No City, State, Zip: FT. PIERCE, Family Type: Single-family FL, New/Existing: New (From Plans) Comment: CLIMATE / Design Temp Int Design Temp Heating Design Daily Temp V Design Location TMY Site 97.5 % 2.5 % Winter Summer Degree Days Moisture Range FL, Fort Pierce FL_VERO_BEACH_MUNI 39 90 70 75 299 62 Low BLOCKS Number Name Area Volume 1 Entire House 1724 14774.8 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated 1 GREAT ROOM 546 5350.8 No 0 1 Yes Yes Yes 2 MASTER BEDROO 354 2832 No 2 1 1 Yes Yes Yes 3 WIC 77 616 No 0 1 No Yes Yes 4 CLST. 35 280 No 0 1 No Yes Yes 5 M BATH 54 432 No 0 1 Yes Yes Yes 6 KITCHEN 180 1440 Yes 0 1 Yes Yes Yes 7 JUNIOR M. BED 198 1584 No 0 1 1 Yes Yes Yes 8 BATH 50 400 No 0 1 No Yes Yes 9 POWDER 35 280 No 0 1 Yes Yes Yes 10 NOOK 42 336 No 0 1 Yes Yes Yes 11 LAUNDRY 49 392 No 0 1 Yes Yes Yes 12 ENTRY 104 832 No 0 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab -On -Grade Edge Insulatio GREAT ROOM 47 ft 0 546 ft' _--- 0 1 0 2 Slab -On -Grade Edge Insulatio MASTER BEDRO 46 ft 0 354 ft' ---- 0 1 0 3Slab-On-Grade Edge Insulatio WIC 1 ft 0 77 ft' ---- 0 1 0 4 Slab -On -Grade Edge Insulatio CLST. 1 ft 0 35 ft' ---- 0 1 0 5 Slab -On -Grade Edge Insulatio M BATH 9 ft 0 54 ft' ---- 0 1 0 8/28/2018 11:47 AM EnergyGauge® USA Section R405.4.1 Compliant Software Page 2 of 6 rnonn ❑nnr-only IAIPI IT SI IMMARV rwprKI 13T REPORT FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 6SIab-On-Grade Edge Insulatio KITCHEN lift 0 180 ft2 ---- 0 1 0 7 Slab -On -Grade Edge Insulatio JUNIOR M. BED 14 it 0 198 ft2 __-- 0 1 0 8 Slab -On -Grade Edge Insulatio BATH i ft 0 50 ft2 ---- 0 1 0 9SIab-On-Grade Edge Insulatio POWDER 5 It 0 35 ft2 ---- 0 1 0 10SIab-On-Grade Edge Insulatio NOOK E ft 0 42 ft2 ---- 0 1 0 11SIab-On-Grade Edge Insulatio LAUNDRY 17 It 0 49 ft2 ---- 0 1 0 12SIab-On-Grade Edge Insulatio ENTRY 5.9 ft 0 103.5 ft' ---- 0 1 0 ROOF Roof Gable Roof Solar SA Emitt Emitt Deck Pitch # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Hip Metal 1817 ft2 0 ft2 Light 0.6 No 0.9 No 0 18.4 ATTIC / V # Type Ventilation Vent Ratio (1 In) Area RBS IRCC 1 Full attic Vented 300 1724 ft2 N N CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic (Vented) GREAT ROOM 30 Blown 546 ft2 0.1 Wood _ 2 Under Attic (Vented) MASTER BEDRO 30 Blown 354 W 0.1 Wood 3 Under Attic (Vented) WIC 30 Blown 77 ft2 0.1 Wood 4 Under Attic (Vented) CLST. 30 Blown 35 W 0.1 Wood _ 5 Under Attic (Vented) M BATH 30 Blown 54 ft2 0.1 Wood _ 6. Under Attic (Vented) KITCHEN 30 Blown 180 ft2 0.1 Wood 7 Under Attic (Vented) JUNIOR M. BED 30 Blown 198 ft2 0.1 Wood 8 Under Attic (Vented) BATH 30 Blown 50 ft2 0.1 Wood 9 Under Attic (Vented) POWDER 30 Blown 35 ft2 0.1 Wood 10 Under Attic (Vented) NOOK 30 Blown 42 ft2 0.1 Wood 11 Under Attic (Vented) LAUNDRY 30 Blown 49 112 0.1 Wood 12 Under Attic (Vented) ENTRY 30 Blown 104 ft2 0.1 Wood WALLS Adjacent Cavity. Width Height Sheathing Framing Solar Below Space In Pf In Area PA/all e Fraction oh=ng _ 1 SW=>E Exterior Concrete Block- E# InGREAT ROO 4.1 26 0 9 10 255.7 ft2 0 0 0.4 0 _ 2 NW=>S Exterior Concrete Block - Ext InGREAT ROO 4.1 21 0 9 10 206.5 1112 0 0 0.4 0 _ 3 NE=>W Exterior Concrete Block - Ext IndMASTER BE 4.1 25 0 8 0 200.0 ft2 0 0 0.4 0 4 SW=>E Exterior Concrete Block - Ext IndMASTER BE 4.1 8 0 8 0 64.0 ft2 0 0 0.4 0 8/28/2018 11:47 AM EnergyGauge® USA Section R405:6.1 Compliant Software Page 3 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below Space aal -5 NW=>S Exterior Concrete Block - Ext InSAWSTER BE 4.1 13 0 8 0 104.0 ft' 0 0 0.4 0 -6 NE=>W Exterior Concrete Block - Ext Insu1M BATH 4.1 9 0 8 0 72.0 ft' 0 0 0.4 0 -7 SW=>E Exterior Concrete Block - Ext InsuKITCHEN 4.1 11 0 8 0 88.0 ft' 0 0 0.4 0 _ 8 NE=>W Exterior Concrete Block - Ext Ins1WNIOR M. B 4.1 14 0 8 0 112.0 ft' 0 0 0.4 0 -9 SW=>E Exterior Concrete Block - Ext InsuPOWDER 4.1 5 0 8 0 40.0 ft' 0 0 0.4 0 10 SW=>E Exterior Concrete Block - Ext Insul NOOK 4.1 6 0 8 0 48.0 ft' 0 0 0.4 0 _ 11 NE=>W Exterior Concrete Block - Ext InsdIAUNDRY 4.1 3 0 8 0 24.0 ft' 0 0 0.4 0 _ 12 SE=>N Exterior Concrete Block - Ext InsdIAUNDRY 4.1 7 0 8 0 56.0 ft' 0 0 0.4 0 _ 13 SW=>E Exterior Concrete Block - Ext InsaIAUNDRY 4.1 7 0 8 0 56.0 ft' 0 0 0.4 0 _ 14 SE=>N Exterior Concrete Block - Ext Insul ENTRY 4.1 6 0 8 0 48.0 ft' 0 0 0.4 0 15 N=>SW Garage Frame - Wood ENTRY 11 35 8 280.0 ft' 0.23 0.4 0 DOORS # Ornt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 SE=>N Insulated ENTRY None .39 3 6 8 20 ft' WINDOWS Orientation shown is the entered orientation => changed to Worst Case. Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 1 SW=>E 1 Metal Low-E Double Yes 0.63 0.25 Y 46.4 ft' 1 ft 0 in 1 It 4 in None None _ 2 NW=>S 2 Metal Low-E Double Yes 0.65 0.21 Y 40.0 ft' 8 ft 0 in 1 It 4 in None None 3 NW=>S 5 Metal Low-E Double Yes 0.63 0.25 Y 32.4 ft' 1 ft 0 in 1 ft 4 in None None 4 NE=>W 6 Metal Low-E Double Yes 0.63 0.25 Y 6.9 ft' 1 ft 0 in 1 ft 4 in None None _ 5 NE=>W 8 Metal Low-E Double Yes 0.63 0.25 Y 16.2 ft' 1 ft 0 in 1 ft 4 in None None 6 SW=>E 9 Metal Low-E Double Yes 0.63 0.25 Y 6.9 ft' 1 ft 0 in 1 ft 4 in None None 7 SE=>N 12 Metal Low-E Double Yes 0.63 0.25 Y 4.7 ft 7 ft 0 in 1 ft 4 in None None GARAGE # Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation 1 440 ft2 440 ft 35 ft 8 It 11 INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000381 1723.7 94.63 177.97 .282 7 8/28/2018 11:47 AM EnergyGauge® USA Section R405.4.1 Compliant Software Page 4 of 6 R405 2017 INPUT SUMMARY CHECKLIST REPORT HEATING SYSTEM # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump/ None HSPF:8.5 34.8 kBtu/hr 1 sys#1 COOLING SYSTEM # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit/ Split SEER: 15 34.8 kBtu/hr 1044 cfm 0.85 1 sys#1 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric None Garage 0.95 50 qal 60.9 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cent # Company Name System Model # Collector Model # Area Volume FEF None None DUCTS --- Supply --- --- Return --- Air CFM 25 CFM25 HVAC # # Location R-Value Area Location Area Leakage Type Handler TOT OUT ON RLF Heat Cool _ 1 Attic 6 200 ft' Attic 45 ft' Default Leakage Attic (Default) (Default) 1 1 TEMPERATURES Programablee Ceiling Fans: ]Thermosta[[t:jjY Heat ng [X1 Jan [X] Feb [[ ]] [X] Mar [[ ] [ ]Ape [ ] ((jj r ]] Jun [XJ Jul Aug [ ]May [[ ]] EXl Sep ` L.l ] Oct 1 Nov Dee [[X�] Dec Venting [I 11 Jan [[ 1] Feb [[X]] Mar [Xl EX] lXl [ ] 1 Jun [[ 1] Jul I Aug [ l] Sep 111 [ ] Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (WO) PM 80 78 78 78 78 78 78 78 78 78 78 80 Cooling (WEH) PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating (WD) PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating (WEH) PM 68 668 8 68 68 68 68 6 66 668 6 8/28/2018 11:47 AM EnergyGauge® USA Section R405.4.1 Compliant Software Page 5 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT MASS Mass Type Area Thickness Furniture Fraction Space Default(8 Ibs/sq.ft. 0 ft' 0 ft 0.3 GREAT ROOM Default(8 lbs/sq.ft. ft' ft 0.3 MASTER BEDR00 Default(8 lbs/sq.ft, ft' ft 0.3 WIC Default(81bs/sq.ft. ft' ft 0.3 CLST. Default(8 Ibs/sq.ft, ft' ft 0.3 M BATH Default(81bs/sq.ft. ft' ft 0.3 KITCHEN Default(8 Ibs/sq.ft. ft' ft 0.3 JUNIOR M. BED Default(8 lbs/sq.ft. ft' ft 0.3 BATH Default(8 lbs/sq.ft. ft' ft 0.3 POWDER Default(8 lbs/sq.ft. ft' ft 0.3 NOOK Default(8 lbs/sq.ft. ft' ft 0.3 LAUNDRY Default(8 lbs/s .ft. ft' ft 0.3 ENTRY Name: Test Rater Signature: 4ap � Rating Compant: Test Rater Date: 1 0 —( E 8/28/2018 11:47 AM EnergyGauge® USA Section R405:4.1 Compliant Software Page 6 of 6 2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.41.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: WYNNE THE MANOR 71 Builder Name: WYNNE BUILDING CORP. Street: THE MANOR 71 Permit Office: ST. LUCIE COUNTY City, State, Zip: FT. PIERCE, FL, Permit Number: Y U Owner: WYNNE BUILDING CORP. Jurisdiction: w Design Location: FL, Fort Pierce COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in an dropped ed ceiling/soffit Y the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/door jambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spa s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the drywall. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exteriorwalls, or insulation that on installation readily conforms to available space shall Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envalPpe shall be sealed to the sub -floor or drywall. Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufa6tprer. Caulking or other adhesive sealants shall not be used to fill voids a. In addition, inspection of log walls shall be in accordance with the provisions of C-400. 8/28/2018 11:48 AM EnergyGaugeO USA FBC 6th Edition (2017) Compliant Software Page 1 of 1 2017 EPL DISPLAY CARD ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 100 The lower the Energy Performance Index, the more efficient the home 1. New home or, addition 1. New (From Plans) 12. Ducts, location & insulation level a) Supply ducts R 6.0 2. Single-family or multiple -family 2. Single-family b) Return ducts R 6.0 c) AHU location Attic/Attic 3. No. of units (if multiple -family) 3. 1 4. Number of bedrooms 4. 2 13. Cooling system: Capacity 34.8 a) Split system SEER 15.0 5. Is this a worst case? (yes/no) 5. Yes b) Single package SEER c) Ground/water source SEER/COP 6. Conditioned floor area (sq. ft.) 6. 1724 d) Room unit/PTAC EER e) Other 7. Windows, type and area a) U-factor:(weighted average) 7a. 0.635 b) Solar Heat Gain Coefficient (SHGC) 7b. 0.240 14. Heating system: Capacity 34.8 c) Area 7c. 153.4 a) Split system heat pump HSPF b) Single package heat pump HSPF 8. Skylights c) Electric resistance COP a) U-factor:(weighted average) 8a. NA d) Gas furnace, natural gas AFUE b) Solar Heat Gain Coefficient (SHGC) 8b. NA e) Gas furnace, LPG AFUE f) Other 8.50 9. Floor type, insulation level: a) Slab -on -grade (R-value) 9a. 0.0 b) Wood, raised (R-value) 9b. 15. Water heating system c) Concrete, raised (R-value) 9c. a) Electric resistance EF 0.95 b) Gas fired, natural gas EF 10. Wall type and insulation: c) Gas fired, LPG EF A. Exterior: d) Solar system with tank EF 1. Wood frame (Insulation R-value) 10A1. e) Dedicated heat pump with tank EF_ 2. Masonry (Insulation R-value) 10A2. 4.1 f) Heat recovery unit HeatRec% B. Adjacent: g) Other 1. Wood frame (Insulation R-value) 10B1. 11.0 2. Masonry (Insulation R-value) 10B2. 16. HVAC credits claimed (Performance Method) 11. Ceiling type and insulation level a) Ceiling fans a)Under attic 11a. 30.0 b) Cross ventilation No b) Single assembly 11b. c) Whole house fan No c) Knee walls/skylight walls 11c. d) Multizone cooling credit d) Radiant barrier installed 11d. No e) Multizone heating credit f) Programmable thermostat Yes *Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT I certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL display card will be completed based on installed code compliant features. l Builder Signature: Date: Address of New Home: THE MANOR 71 _ City/FL Zip: FT. PIERCE. FL 8/28/2018 11:47:59 AM EnergyGauge® USA 6.0.02 - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 Project Summary Job: Pj -� wrightsoft® � ry By: apros,zo,a Entire House r QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 PhD W: 772-46B-6799 Fax 772-466-6796 Email: QUICKCAl-cr, iAOL.COM Project Information For: WYNNE BUILDING CORP. THE cMANOR 71, FT. PIERCE, FL Notes: Design Information Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outsidedb 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF DesignTD 28 OF DesignTD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 18275 Btuh Structure 16689 Btuh Ducts 6093 Btuh Ducts 7868 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 24368 Btuh Use manufacturers data n Rate/swingg multipplier 0.95 23329 Btuh Infiltration Equipmenisensibleload Method Simplified Latent Cooling Equipment Load Sizing Construction quality Fireplaces Average 0 Structure 2462 Btuh Ducts 2513 Btuh Central vent (0 cfm) 0 Btuh Heatingg Area (ft) 1724 Coolingg 1724 (none) Equipment latent load 4975 Btuh Volume (ft') 14809 Airchanges/bour 0.38 14809 0.20 Equipment Total Load (Sen+Lat) 28304 Btuh EquivAVF (cfm) 94 49 Req. total capacity at 0.70 SHR 2.8 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Trade CARRIERAIR CONDITIONING Make Carrier Trade CARRIERAIR CONDITIONING Model 25HBC536AO030 Cond 25HBC536AO030 AHRI ref 3645945 Coil FX4DNF037 AHRI ref 3645945 Efficiency 8.5 HSPF Efficiency 12.0 EER,15 SEER Heatinglnput Heating output 34600 Btuh @47-F Sensiblecooling Latentcooling 24360 10440 Btuh Btuh Temperature rise 27 Actual airflow 1160 OF cfin Total cooling Actual airflow 34800 1160 Btuh c1m Airflowfactor 0.048 0.08 cfrnBtuh in H2O Air Static flowfactor pressure 0.047 0.08 cfm/Btuh in H2O Static pressure Space thermostat Load sensible heat ratio 0.83 Capacity balance point = 33 OF Backup: Input=7kW, Output= 22529 Btuh, 100 AFUE Calculations approved byACCAto meet all requirements of Manual J 8th Ed. Wrightsof[® 2018-ALC-2812:11.01 mgm-siteOudi rMI201818.0.16RSU08101 DEC"g g 20gal �C'•A ...rds\WdgFAwfl HVAC\WYNNE-THEMANOR-71-1724.np Calc=MJB Fmrd DoorfaceFI L iJL I. Y wrightsoft' Right!® Worksheet Entire House QUICK CALCS, INC. 317 ST. LUCIE LN., Ff. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: OUICKCALCS@AOL.COM Job: Data: Apr 05, 2018 By. 1 Room name Entire House GREAT ROOM 2 Eyosedvall 168.0 It 45.0 ft 3 Room h*hl 8.6 It d 9.8 ft heatlmol 4 5 Room dimensions Room area 1723.5 ft 21.0 x 27.0 ft 567.0 ft Ty Corr*udon U-value Or HTM Area (iP) Load Area (fte) Load number (Bluhfie-T) (BtuW or penmetr M (Bluh) or perimeter (ft) (BNh) Heat Cod Gross NrP/S Heat Cool Gross N/P/S Heat Cool 6 V)J 13A4= 0,143 ne 4.00 2.55 432 410 1640 1042 0 0 0 0 4A5-2om 4A5-2om 0.770 Q770 ne ne 21.56 21.56 36.90 36.90 6 16 0 0 139 346 238 592 0 0 0 0 0 0 0 0 t-(G' 11 G 13A4o 4A5-2om 0.143 0.770 w ne 4.00 21.56 2.55 19.31 104 4 79 4 315 94 200 84 0 0 0 0 0 0 0 0 D 11D0 0.390 se 10.92 11.31 21 21 229 237 0 0 0 0 W 13A-4= 0.143 sv 4.00 2.55 585 532 2131 1355 295 219 876 5S7 4A52om 0.770 sN 21.56 33.76 6 1 139 218 0 0 0 0 4A52om 0770 sv 21.56 35.13 46 5 990 1614 46 5 990 1614 W 13A-4= 0.143 nw 4.00 2.55 310 237 950 604 206 165 661 420 G 4A5-20m 4A5.2omd 0.770 0.770 rw nw 21.56 21.56 36.90 36.90 32 41 0 0 682 880 1167 1505 0 41 0 0 0 880 0 1505 P 12C-Ow 0.091 255 128 258 258 657 331 0 0 0 0 C 16B-30md Q032 - 0.90 1.68 1724 1724 1544 2895 567 567 508 953 F 22A-t11 0.989 27.69 0.00 1724 168 4652 0 567 48 1329 0 6 c)AEDa r9on 1332 1052 Envelopeloss/gain 15389 13415 5243 6100 12 a) Infiltration 2886 814 949 268 b) Roomeentlation 0 0 0 0 13 Internal gains Occupants @ 230 2 460 0 0 Applianceslolher 2000 0 Subhxal(lines6bt13) 18275 16689 6193 6368 Lessexernalload 0 0 0 0 Leslransfer 0 0 0 0 Redisbibution 0 0 0 0 14 Submtal 18275 16689 6193 6368 15 Ductloads 33% 47% 6093 7868 33% 47% 2064 3002 I room load 24368 24557 8257 9370 AT ir required (chn) 1160 1160 393 443 Calculations approved b4ACCA to meet all nuirements of Manual J 8th Ed. -!}F w rl9hfsoT[^ 2018-Arg-2812:11 Al ' RigN-Sule3l Uriverml 201818.0.16 RSU08101 Page 1 ...rOWdghtsoft WAMWYNNE-THEMANOR-71-1724.rnp Calc=MJB Front Doorfaces: N wrightsoft• Right-.l® Worksheet Job* Entire House Dale. Apr06'2016 ey QUICK CALCS, INC. 317 ST. LUCIE UN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCSCAQL.COM 1 Room name MASTER BEDROOM WIC 2 EVosedwall 51.0 ft 0ft 3 Room height 8.0 ft heatbool 8.0 ft heaVocol 4 Roomdimendons 1,0 x 315.0 ft 7.0 x 11.0 It 5 Room area 315.0 IF 77.0 ft Ty Construdon U-value Or HTM Area (" Load Area Load number (BWhtl�°F) (BUNN) or Perimeter (R) (Btuh) or perimeter (to (Btuh) Heat Cod Gross NtP/S Heat Cool Gross N/P(S Heat Cool 6 13A-4= 0.143 re 4.00 2.65 224 224 897 570 0 0 0 0 4A5-20m 0.770 ne 21.56 36.90 0 0 0 0 0 0 0 0 4A5-2om 0.770 ne 21.56 36.90 0 0 0 0 0 0 0 0 13A4= 0.143 w 4.00 2.55 0 0 0 0 0 0 0 0 11 4A5-2om 0.770 sa 21.56 19.31 0 0 0 0 0 0 0 D 11DO 0.390 se 10.92 11.31 0 0 0 0 0 0 0 0 W 13A-4= 0.143 w 4.00 2.55 80 80 320 204 0 0 0 0 LG 4A5-2om 0.770 sN 21.56 33.76 0 0 0 0 0 0 0 0 ff 4A5.2om 0.770 sw 21.56 35.13 0 0 0 0 0 0 0 0 13A-40s 0.143 rw 4.00 255 104 72 290 184 D 0 0 0 4A5-2om 0770 nw 21.56 36.90 32 0 682 1167 0 0 0 0 4A5.2omd 0.770 nw 21.56 36.90 0 0 0 0 0 0 0 0 P 12C.Ow 0.091 2.55 128 0 0 0 0 0 0 0 0 C 16B-30md 0.032 - 0.90 1.68 315 315 282 529 77 77 69 129 F 224,-tpl 0.989 - 27.69 0.00 315 51 1412 0 77 0 0 0 6 C)AEO e=xeion 315 1 -2 EnvelopeloWgain 3884 2970 1 69 127 12 a) hfiWaton 823 212 1 0 0 b) Roomventlafion 0 0 0 0 13 Internal gaits: Omtpants@ 230 2 460 0 0 AApdianoes(lotrer 0 p Subtotal (lines6 to 13) 4707 3662 69 127 Lesse)ftmal bad 0 0 0 0 Lesstansfer 0 0 0 0 Redistributon 0 0 0 0 14 Subtotal 4707 3662 69 127 15 Duriloads 33% 47% 1%9 1726 339% 47% 23 60 Total room load 6276 5388 1 92 187 Airrequired(dm) 299 255 1 4 9 Calculations approved bvACCAto meet all rt�rements of Manual J 8th Ed iFF wrigFrtfsoT[- 2018-AIy-2812:11:01 Right-Sute@Uriwrml201818.0.16RSU08101 Paget ...ntsWnghboi WAC\WYNNE-THE MANOR-71-1724np Cale AJ8 Front Door faces: N + wrightsoft• Right-J® Worksheet Job' Entire House Date: Apr05,2018 By: QUICK CALCS, INC. 317 ST LUCIE LN., FT. PIERCE, FL 34946 Phore:772466-6799 Fax772-466-6796 Email: QUICKCALC,6@AOL.COM 1 Room name CLST. MEATH 2 Eroomdvell 0 It 9.0 It 3 Room height 8.0 ft heaVood 8D It heaV=l 4 Room dimensions 70 x 5.0 ft 6.0 x 9.0 ft 5 Roomarea 35.0 ft54.0 ft' Ty Construction U-value Or HTM Area (ft') Load Area IT) Load number (Btuh&-"F) (StuhM or perimeter (M (Btuh) or perimeter (R) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NrP/S Heat Cool 6 V 13A4= 0.143 ne 4.00 2.55 0 0 0 0 72 66 262 167 4A5-2am 0.770 ne 21.56 36.90 0 0 0 0 6 0 139 238 ��-GG 4A5-2cm 0.770 ne 21.56 36.90 0 0 0 0 0 0 0 0 13A-0ors 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 11 G 4A5-2om 0.770 w 21.56 19.31 0 0 0 0 0 0 0 0 D 11DO 0.390 s 10.92 11.31 0 0 0 0 0 0 0 0 w fi--r: 13A4ors 4A5-2om 0.143 0.770 wu sN 4.00 21.56 2.55 33.76 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 IC 4A5-2om 0.770 sw 21.56 35.13 0 0 0 0 0 0 0 0 w 13A-0acs 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 4A5-20m 0.770 nw 21.56 36.90 0 0 0 0 0 0 0 0 4A5-2omd 0.770 nw 21.56 36.90 0 0 0 0 0 0 0 0 P 12C-0sa 0.091 2.55 1.28 0 0 0 0 0 0 0 0 C 16B30md 0.032 0.90 1.68 35 35 31 59 54 54 48 91 F 22A-tpl 0.989 - 27.69 0.00 35 0 0 0 54 9 249 0 6 c) AED exmreon -1 -10 Envelope lossIgain 31 58 699 486 12 a) Infiltration 0 0 145 41 b) Roomvenfilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Applianw_sbther 0 0 Subtotal (lines 6 to 13) 31 58 945 527 Leasedernalload 0 0 0 0 Lesstransfer 0 0 0 0 14 15 Redistribution Subloal Ductloads 33% 47% 0 31 10 0 58 27 33% 47% 0 845 282 0 527 248 Total room load 42 85 1126 776 Air required (dim) 2 4 54 37 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -OFF- 2018-Atg-2812:11:01 -"'" "'"^`-•-^ Rigtd-Sdte®)Wverml20l8l8.O.l6RSU08101 Page ...nAWrigitsoft HVAC\WVNNE-THE MANOR-71-1724.mp Cab=MJ8 Front Door faces: N wrightsoft Rig ht-J® Worksheet Job: Date: Apr 05, 2018 Entire House By. QUICK CALCS, INC. 317 ST. LUCIE LN.. Fr. PIERCE, FL 34946 Phone:772-46M799 Fax 772-466-6796 Email: QUICKCALC9@AOL.COM 1 Room name KITCHEN JUNIOR MBED 2 EKoosedvall 11.0 ft 14.0 ft 3 Room height 8.0 It heaV000l 8.0 ft heaV000l 4 Roomdimensions 1,0 x 150.0 ft 1.0 x 198.0 ft 5 Room area 180.0 ft- 198.0 ft, Ty Construction U-value Or HTM Area (im Load Area (fl0 Load number (BluhAl--F) or perimeter M (Bluh) or Penmeter (lb (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heal Cool 6 Vt 13A-4= 0.143 ne 4.00 2.55 0 0 0 0 112 96 394 244 4A5-2om 0.770 ne 21.56 36.90 0 0 0 0 0 0 0 0 II--GG 4A5.2om 0.770 ne 21.56. 36.90 0 0 0 0 16 0 346 592 �j M-4= 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 11 I-C 4A5.2om 0.770 se 21.56 19.31 0 0 0 0 0 0 0 0 L�.D 11DO 0.390 se 10.92 11.31 0 0 0 0 0 0 0 0 13A-4os 0.143 sv 4.00 2,55 88 88 352 224 0 0 0 0 G 4A5-2om 0770 su 21.56 33.76 0 0 0 0 0 0 0 0 4A5-2om 0.770 sv 21.56 35.13 0 0 0 0 0 0 0 0 W 13A-4ocs 0,143 nvv 4.00 2.55 0 0 0 0 0 0 0 0 4A5-2om 0.770 m 21.56 35.90 0 0 0 0 0 0 0 0 4A5,20md 0.770 m 21.56 36.90 0 0 0 0 0 0 0 0 P 12C-Ow 0.091 - 2.55 128 0 0 0 0 104 104 265 133 C 16B-30 and 0.032 0.90 1.68 180 180 161 302 198 198 177 333 F 22A-0 0.989 27.69 0.00 180 11 305 0 198 14 388 0 6 c)AED e=lreon -47 -25 Envelope lowigain 818 480 1560 1277 12 a) Infiltration 178 50 226 64 b) Roomventlation 0 0 0 0 13 Internal gains Oovpanls@ 230 0 0 0 0 Applianoadotier 2000 0 Subtotal (lines 6 to 13) 996 2530 1786 1341 Lmexkmal load 0 0 0 0 Lesstransfer 0 0 0 0 0 0 Redistribution 0 996 0 2530 1786 1341 14 15 Subtotal Ductloads 33% 479% 332 1193 33% 47°/ 595 632 Total room load 1328 3722 2381 1973 63 178 113 93 Airrequired(cm) wrightsof[^' AC�P PogFFSule®LHversa1201818.0.16 RSU08101 ...Ms\WngWs ftHVAC\WYNNE-THE MANOR-71-1724.rLp Calc=MJ8 Front Door facas: N 2018-Aug-2812:11:01 Page 4 i + wrightsoft° Rig ht-M Worksheet Entire House QUICK CALCS, INC. 317 ST. LUGE LN., FT. PIERCE, FL 34946 Phow 772-466-6799 Fax 772460-67% Email: QUICKCALCSOAOL.COM Jab: Date: Apr 06, 2018 By. 1 Room name BATH POWDER 2 EVosdvall 0 It 5.0 It 3 Room height 8.0 ft heaVmol 8.0 ft hwV=l 4 5 Room dimensions Room area 5.0 x 10.0 it 50.0 ft' 7.0 x 5.0 it 35.0 fF Ty Conladon U-value Or HTM Area (re)) Load AmiI (M Load number (Btih4M--'F) (BtuhM or perimeter (N (Bluh) or perimeter (ft) (Bluh) Heat Cool Gross N/P/S Heat Cool Gros NP/S Heel Cool 6 V ��(G` 13A4= 0,143 re 4.00 2.55 0 0 0 0 0 - 0 0 0 4A5-20m 0.770 ne 21.56 36.90 0 0 0 0 0 0 0 0 4A5-2om 0.770 re 21.56 36.90 0 0 0 0 0 0 0 0 13A-4= 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 11 G 4A5-2om 0.770 se 21.56 19.31 0 0 0 0 0 0 0 0 D 11D0 0.390 se 10.92 11.31 0 0 0 0 0 0 0 0 U,J IL�_rr-, 13A4= 4AS2om 0.143 0.770 w w21.56 4.00 2.55 33.76 0 0 0 0 0 0 0 0 40 6. 34 1 134 139 85 218 4A5-2om 0.770 w 21.56 35.13 0 0 0 0 0 0 0 0 V)/ 13A-4= 0.143 w 4.00 2.55 0 0 0 0 0 0 0 0 L�-GG 4A5-2om 4A5-2omd 0.-M 0.770 nw nw 21.56 21.56 35.90 36.90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 P 12C-O w 0.091 - 2.55 128 40 40 102 51 0 0 0 0 C 16B30md 0.032 - 0.90 1.68 50 50 45 84 35 35 31 59 F 22A-tpl 0.988 27.69 0.00 50 0 0 0 35 5 138 0 6 c) AEO eAmiacin -2 79 Envelopeloss/gain 147 133 443 441 12 a) Infiltration 0 0 81 23 b) Roomsentlation 0 0 0 0 13 Internal gains: Omlpan6@ 230 0 0 0 0 Appliancealother 0 0 Subtotal (lines6to 13) 147 133 524 464 Lev;eldemal load 0 0 0 0 Lestansfer 0 0 0 0 Redistlibulim 0 0 0 0 14 SubtDbl 147 133 524 484 15 DuCloads 33% 479/6 49 63 339/6 47% 175 219 Total room load 196 196 699 682 Airrequired(1) 9 9 33 32 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -Pl,1- wrwnh d ft- 2018-A1g-2812:11Di """" --"" Riglt.Sdte® Lkiverml 201818.0.16 RSW8101 Pages ...As\WdghlsoftWAC\WYNNE-THEMANOR-71-1724.rip Calc=MJ8 FrontDoorfaces: N wrightsoft` Right-JO Worksheet Entire House QUICK CALCS, INC. 317 ST. LUCIE LN., Fr. PIERCE, FL 34946 Pfwre:772-46&6799 Fax.772-466-6796 EmaiI:QUICKCALI�S@AOL.COM Job: Date: Apr 05, 2018 By: 1 Room name NOOK LAUNDRY 2 Exposedvsll 6.0 it 17.0 It 3 Room height 8.0 It heat/cool 8.0 ft heaUmol 4 5 Room dimensions Room area 7.0 x 6.0 It 42.0 ft' 7.0 x 8.0 It 56.0 IF Ty Construction U-value Or HTM Area (" Load Area (IF) Load number (Btuh4[z°F) (BtuhAF) or perimeter (q (Stuh) or penmen (ft) (Bhah) Heat Cool Gross N/P/S Heat Cool Gross NIP/S Heat Cool 6 UN IL-(G 13A-4ocs 0.143 ne 4.00 2.55 0 0 0 0 16 16 64 41. 4A5-2om 4A5-2cm 0.770 0.770 ne ne 21.56 21.56 36.90 36.90 0 0 0 0 0 '0 0 0 0 0. ' 0 0 0 0 0 0. 13A-4ors 0.143 se 4.00 2.55 0 0 0 0 56 52 207 131 11 G 4A52om 0.770 se 21.56 19.31 0 0 0 0 4 4 94 84 D tj13A-4= 11D0 4A5-2om 0,390 0.143 0.770 se wr sN 10.92 4.00 21.56 11.31 2.55 33.76 0 48 0 0 48 0 0 192 0 0 122 0 0 64 0 0 64 0 0 256 0 0 163 0 ���------CGG 4A5-2om 0.770 sv 21.56 35.13 0 0 0 0 0 0 0 0 W 13A-4ors 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 4A5-2om 0.770 nw 21.56 36.90 0 0 0 0 0 0 0 0 4A5-2cmd 0.770 nw 21.56 36.90 0 0 0 0 0 0 0 0 P 120-O w 0.091 - 255 1.28 0 0 0 0 0 0 0 0 C F 16&30md 22A-tpl 0.032 0.959 - 0.90 27.69 1.68 0.00 42 42 42 6 38 166 71 0 56 56 56 17 50 471 94 0. 6 c)AED excursion -4 -11 Envelope loss/gain 396 189 1142 503 12 a) Infiltration 97 27 274 77 b) Roomventilation 0 0 0 0 13 Internal gains: Ooalpants@ 230 0 0 0 0 ApplianoWother 0 0 Subtotal (lines 6 to 13) 1 493 216 1417 580 LessexlEmal lozd 0 0 0 0 Less6ansfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 493 216 1417 580 15 DuGloads 33% 47% 164 102 339/6 47% 472 274 Total room load 657 318 1 1889 854 Air required (rfin) 31 15 90 40 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -4 - wrfq"+t irt- 201&Ag-2812:11 :01 �/C A "' ""-^ ^•"^ Right-SUteD Uiversal 201818.0.16 RSU08101 Page ...rts\Wrigt#mit WAQWYNNE-THEMANOR-71-1724.np Calc=MJB Frcrt Doorfamv.N wrightsoft• Right-M) Worksheet Job: Date: Apr 05, 2018 Entire House By. QUICK CALCS, INC. 317 ST. LUCIE LN., Fr. PIERCE, FL 34946 Phone:7724656799 Fax.772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name ENTRY 2 EVosed vall 7.0 It 3 Room height 8.0 It he Vcool 4 Room dimensions to x 114.5 ft 5 Room area 114.5 ft Ty Construdion U-value Or HTM Area (ft=) Load Area Load number (Btuh4t;°F) (BIuhAP) or perimeter (Iq (BWh) a perimeter Heat Cool Gross NIPS Heat Cool Gross NIP/S Heat Cool 6 V)J 13A-4= 0.143 ns 4.00 2.55 8 8 32 20 IL-GG 4A5-2am 0.770 ne 21.56 36.90 0 0 0 0 4A5-2om 0,770 ne 21.56 36.90 0 0 0 0 11 W �G 13A-0as 4A5-2om 0.143 0,770 se se 4.00 21.56 2.55 19.31 48 0 27 0 108 0 69 0 D 11DO 0.390 se 10.92 11,31 21 21 229 237 W G 13A-0ocs 0.143 sm 4.00 - 2.55 0 0 0 0 4AS2om 0.770 sN 21.56 33.76 0 0 0 0 ILf21_ 4A5-2om 0.770 sH 21.56 35.13 0 0 0 0 IW 13A-0as 0.143 m 4.00 2.55 0 0 0 0 LZI---t� 4AS2om 0.770 m 21.56 36.90 0 0 0 0 4A5-2omd 0.770 = 21.56 36.90 0 0 0 0 P 12C-0sv 0.091 - Z55 1.28 114 114 290 146 C 16B-30md 0.032 - 0.90 1.68 115 115 103 192 F 22A-to 0.989 - 27.69 0.00 115 7 194 0 6 c) AED excursion -13 Envelope loss/gain 956 652 12 a) Infiltration 113 32 b) Roomeenfilation 0 0 13 Internal gains: Ompanls@ 230 0 0 Appliances/olher 0 Subtotal(lines6 to 13) 1069 684 LessexdBmalload 0 0 Lesstransfer 0 0 Redistributon 0 0 14 Subbtal 1069 684 15 Duct loads 33% 47% 356 323 Total room load 1425 1007 Airrequired(dm) 68 48 Calculations approved byACCAto meet all r quirements of Manual J 8th Ed. �{:- wri9htsoft- 2016-Aug-2812:11 :01 Ri9hl-Sdte®Universrup Ca18.0,16 FrontD o Page7 ...rftWnghtsoft WAC\WYNNE-THE MANOR-71-1724.rrp CaIc=MJB Frord Doorfaces: N - - wrightsofto Duct System Summary Entire House QUICK CALCS, INC. 317ST. LUCIE LN., Fr. PIERCE, FL34946 P1oae:772.466-6799 Fax 772-466-6796 Email: OUICKCALCSQAOL.COM P- For: WYNNE BUILDING CORP. THE MANOR 71, FT. PIERCE, FL External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.08 in H2O 0 in H2O 0.08 in H2O 0.040 / 0.040 in H2O 0.051 in/100ft 1160 drn 156 ft Supply Branch Detail Table Job: Date: Apr05,2018 By. Cooling 0.08 in H2O 0 in H2O 0.08 in H2O 0.040 / 0.040 in H2O 0.051 in/100ft 1160 afm Name Design (Btuh) Htg (cfm) Clg (cfrn) Design FR Diam (in) H x W (in) Duct Mail Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH c 196 9 9 0.074 4,0 OxO VIFx 18.4 90.0 st1 CLST. C 85 2 4 0.071 4.0 Ox0 VIFx 22.5 90.0 st1 ENTRY h 1425 68 48 0.108 5.0 Ox0 VIFx 4.0 70.0 GREATROOM c 4685 197 221 0.054 8.0 Ox0 VIFx 37.3 110.0 st3 GREATROOM-B c 4685 197 221 0.053 8.0 Ox0 VIFx 39.8 110.0 st3 JUNIORM.BED h 2381 113 93 0.070 7.0 Ox0 VIFx 24.7 90.0 st1 KITCHEN c 3722 63 176 0.070 7.0 Ox0 VIFx 24.2 90.0 st1 LAUNDRY h 1889 90 40 0.078 5.0 Ox0 VIFx 13.1 90.0 st2 M BATH h 1126 54 37 0.067 6.0 Ox 0 VIFx 29.6 90.0 st1 MASTER BEDROOM h 3138 149 127 0.054 6.0 Ox0 VIFx 39.3 110.0 st3 MASTERBEDROOAMA h 3138 149 127 0.051 6.0 Ox0 VIFx 45.9 110.0 st3 NOOK h 657 31 15 0.082 5.0 Ox0 VIFx 7.8 90.0 st2 POWDER h 699 33 32 0.082 5.0 OxO VIFx 7.2 90.0 st2 WIC c 187 4 9 0.056 4.0 Ox0 VIFx 33.8 110.0 st3 Supply Trunk Detail Table I Trunk Htg Clg Design Veloc Clam H x W Duct Name Type (dim) (cfm) FR (fpm) (in) (in) Material Trunk st3 PeakAVF 696 706 0.051 899 12.0 0 x 0 VInIFIX st1 SO PeakAVF 938 1025 0.051 959 14.0 0 x 0 VInIFIX s12 PeakAVF 154 88 0.078 350 9.0 0 x 0 VinlFlx _ * wrightrsof - 201E-Aig-2812:11.02 za .,..,.•, .......=m.,.. Rigft-SoRe®Urdvarsal 201818.0.16 RSU08101 Pa e 1 g ...rls0rigfdsoft HVAC\WYNNE-THE MANOR-71-1724.rW Calc=MJ8 Frort Door faces: N Return Branch Detail Table Name Grille Size (in) Htg (Cfm) Clg (Cfm) TEL M Design FR Veloc (fpm) Diam (in) HxW (in) Stud/Joist Opening (in) Duct Mat] Trunk rb1 Ox0 1160 1160 0 0 0 0 Ox 0 VIFx wrightsoft• 2018-Aip-2812:11:02 i9l+l�P'� ..o.,•� w.--.gym Mglt-SUL4 lMversal 201818.0.18 RSU08101 Paget ...rtslWrigtboftHVAQWYNNE-THE MANOR-71-1724.rnp CaIc=MJ8 FrortDoorfacas: N