Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutENERGY EFFICIENCY CODEFlorida Energy Efficiency Code For Building Construction
EnergyGauge Summit® Fla/Com-201 % Effective Date: March 1'5.2012 — Form 506-201 T
Total Building Performance Method "for Commercial Buildings
BY
PROJECT SUMMARY
Short Desc:
OFFICE
Description:
DRAWDY BROS
Owner:
DRAWDY BROS
Addressl:
ST. LUCIE CO
City:
FT. PIERCE
Address2:
FLORIDA
State:
FLORIDA
Zip:
0
Type:
Office
Class:
New Finished building
Jurisdiction:
ST LUCIE COUNTY,
ST LUCIE COUNTY, FL (661000)
Conditioned Area:
3600 SF
Conditioned & UnConditioned Area:
3600 SF
No of Stories:
1
Area entered from Plans
0 SF
Permit No:
0
Max Tonnage
3.5
If different, write in:
REVIEWED FOR COMP E
SUBJECT TO'FIEL PECTIONS
E ATTAC REVISION SHEET
REVI
FILE Copy
EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
2/5/2013 Page 1 of 7
Component Design Criteria Result
Gross Energy Cost (in $) 2,465.0 2,504.0 PASSED
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
PASSES
None Entered
PASSES
None Entered
None Entered
None Entered
Yes/No/NA
IMPORTANT MESSAGE
Info 5009 -- -- -- An input report of this design building must be submitted along with this
EnergyGauge Summit® Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
2/5/2013 Page 2 of 7
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the
Florida Energy Code
Prepared By: PAUL WELCH INC. Building Official:
r
Date: FIB 0 O 2013 Date:
I certify that this building is in compliance with the FLorida Energy Efficiency Code
Owner Agent: DRAWDYBROS
Date:
If Required by Florida law, I hereby certify (") that the system design is in compliance with the Florida
Energy Efficiency Code
Electrical Designer: - Reg No:
Lighting Designer: Reg No:
Mechanical Designer: PAUL WELCH INC. Reg No:, 29945
Plumbing Designer: Reg No: .
(') Signature is required where Florida Law requires design to be performed by registered design
professionals.
EnergyGauge Summit© RaXom-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
5/2013 Page 3 of 7
Project: OFFICE
Title: DRAWDY BROS
Type: Office
(WEAFile: FL ST LUCIE CO INTL.tm3)
Building End Uses
1) Proposed
2) Baseline
Total
158.20
200.40
$2,465
$3,130
ELECTRICITY(MBtulkWhf$)
158.20
200.40
46334
58724
$2,465
$3,130
AREA LIGHTS
26.80
41.40
7839
12128
$417
$646
MISC EQUIPMT
54.00
54.00
15823
15823
$842
$843
PUMPS & MISC
0.10
0.10
21
23
$1
$1
SPACE COOL
41.20
46.90
12061
13753
$642
$733
SPACE HEAT
2.20
6.30
649
1846
$35
$98
VENT FANS
33.90
51.70
9941
15151
$529
$808
Credits Applied: None
PASSES
Passing Criteria = 2504
Design (including any credits) = 2465
Passing requires Proposed Building cost to be at most 80% of
Baseline cost. This Proposed Building is at 78.8%
EnergyGauge Summi* FlalCom-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
/5/2013 Page 4 of 7
I
External Lighting Compliance
Description Category Tradable? Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
None
Project: OFFICE
Title: DRAWDY BROS
Type: Office
(WEAFile: FL ST LUCIE CO INTL.tm3)
Lighting Controls Compliance
Acronym Ashrae Description
Area Design Min Compli-
ED
(sq.ft) CP CP once
OFFICE 17 Office -Enclosed
3,600 20 2 PASSES
PASSES
Project: OFFICE
Title: DRAWDY BROS
Type: Office
(WEAFile: FL ST LUCIE CO INTL.tm3)
System Report Compliance
OFFICE System I
Constant Volume Air Cooled No. of Units
Single Package System < 3
65000 Btu/hr
i
Component Category
Capacity Design EfI Design IPLV Comp-
i
Eff Criteria IYLV Criteria liance
j Cooling System Air Conditioners Air Cooled
13.00 12.23 1.00 PASSES
Single Pkg < 65000 Btu/h
Cooling Capacity
Heating System Electric Furnace
1.00 1.00 PASSES
Air Handling System Air Handler (Supply) -
0.80 0.82 PASSES
-Supply Constant Volume
Air Distribution ADS System
6.00 6.00 PASSES
System (Sup)
Air Distribution ADS System (Ret)
6.00 4.20 PASSES
System (Ret)
PASSES
EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
i2/5/2013 Page 5 of 7
Plant Compliance
Description Installed Size Design Min Design Min Category Comp
No Eff Eff IPLV IPLV Hance
None
Water Heater Compliance
DDesign Min Design Max Comp
Description Type Category
Eff Eff Loss Loss Hance
None
Piping System Compliance
Category Pipe Din Is Operating Ins Cond Ins Req Ins Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] SF.F]
NoneTj
1
12/5/2013
I
EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
Page 6 of 7
:t: OFFICE
DRAW DY BROS
Office
k File: FL_ST_LUC1E_CO_INTL.tm3)
Other Required Compliance
Category Section
Requirement (write N/A in box if not applicable)
Check
Report 506.4.2
Input Report Print -Out from EnergyGauge FlaCom attached
Operations Manual 303.3.1,
Operations manual provided to owner
503.2.9.3,
505.7.4.2
Windows & Doors 502.3.2
Glazed swinging entrance & revolving doors: max. 1.0 cfin/ft2; all
other products: 0.3 cfm/ft'
Joints/Cracks 502.3.3
To be caulked, gasketed, weather-stripped or otherwise sealed
Dropped Ceiling Cavity 502.3
Vented: seal & insulated ceiling. Unvented seal & insulate roof &
side walls
HVAC Efficiency 503.2.3
Minimum efficiencies: Tables 503.2.3(1)-(8)
El
HVAC Controls 503.2.4
Zone controls prevent reheat (exceptions); separate thermostatic
El
control per zone;
Ventilation 503.2.5
Outdoor air supply & exhaust ducts shall have dampers that
El
automatically shut when systems or spaces served are not in use.
Exhaust air energy recovery required for cooling systems
(Exceptions).
ADS 503.2.7.5
Duct sizing and Design have been performed
❑
HVAC Ducts 503.2.7
Air ducts, fittings, mechanical equipment & plenum chambers shall
be mechanically attached, sealed, insulated & installed per Table
503.2.7.2. Fan power limitations.
Balancing 503.2.9.1
HVAC distribution system(s) tested & balanced. Report in
❑
construction documents.
Piping Insulation 503.2.8
HAC and service hot water. In accordance with Table 503.2.8.
Water Heaters 504
Performance requirements in accordance with Table 504.2. Heat
trap required.
Swimming Pools 504.7
Vapor -retardant or liquid cover or other means proven to reduce
El
heat loss on heated pools; Time switch (exceptions); readily
accessible on/off switch.
Motors 505.7.5
Motor efficiency criteria have been met
❑
Lighting Controls 505.2, 502.3
Automatic control required for interior lighting in buildings >5,000
s.f; Space control; Exterior photo sensor; Tandom wiring with 1 or
3 linear fluorescent lamps>30W
EnergyGauge Summi* Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
I2/5/2013 Page 7 of 7
Project Name: OFFICE
Project Title: DRAWDY BROS
Address: ST. LUCIE CO
FLORIDA
State: FLORIDA
Zip: 0
Owner: DRAWDY BROS
EnergyGauge Summit® A.10
INPUT DATA R.EPOR
Proiect Information
Orientation: North
Building 1'ype: Office
Building Classification: New Finished building
No.of Stories: 1
GrossArea: 3600 SF
Zones
No Acronym Description Type
Area
[so
Multiplier
Total Area
[sf]
1 OFFICE Zone 1 CONDITIONED
3600.0
1
3600.0 ❑
Spaces
No Acronym Description Type Depth
IN
Width Height Multi
[ft] [ft] plier
Total Area
[st]
Total Volume
lei]
2/5/2013 EuergyGauge Summit® v4.10 1
In Zone: OFFICE
1 OFFICE DRAWDYBROS Office - Enclosed
40.00
90.00
10.00
1 3600.0
36000.0
Lighting
No Type
Category
No. of
Watts per
Power
Control Type
No.of
Luminaires
Luminaire
[W]
Ctrl pts
In Zone: OFFICE
In Space: OFFICE
1 Recessed
Fluorescent - General Lighting
40
64
2560
Manual On/Off
20
No vent
Walls
No Description
Type Width H (Effec) Multi
Area DirectionConductance
Heat
Dens. R-Value
[ft]
[ft] plier
[sf]
[Btu/hr. sf. F]
Capacity
[Ib/ci] [h.sf.F/Btu]
[Btu/sf.F]
In Zone: OFFICE
1 DRAWDYBROS
8"CMU/3/4"ISO 90.00
10.00 1
900.0
North
0.2642
9.696
62.72 3.8
❑
BTWN24"oc/5/8
2 DRAWDYBROS
8 CMU/3/4"ISO 90.00
10.00 1
900.0
North
0.2642
9.696
62.72 3.8
❑
BTWN24"oc/5/8
GYP
3 DRAWDYBROS
8"CMU/3/4"ISO 40.00
10.00 1
400.0
North
0.2642
9.696
62.72 3.8
❑
BTWN24"oc/5/8
GYP
4 DRAWDYBROS
8"CMU/3/4"ISO 40.00
10.00 1
400.0
North
0.2642
9.696
62.72 3.8
❑
BTWN24"oc/5/8
GYP
Windows
No Description Type Shaded U SHGC Vis.11a
W
H(Effec)
Multi
Total Area
[Btu/hr sf F]
[ft]
[ft]
plier
[sf]
2/5/2013 EnergyGauge Summit® v4.10
I—InZone: OFFICE
In Wall: S WALL
1 DRAWDYBROS User Defined
No 1.2500 0.82 0.76
66.00 4.00 1
264.0
Doors
No Description Type
Shaded? Width H (Effec) Multi
IN [ft] plier
Area
[sf]
Cond. Dens. Heat Cap. R-Value
[Btu/hr. sL F] Ub/cf] [Btu/sL F] [h.sEFBtal
In Zone:
In Wall:
Roofs
No Description Type
Width H (Effec) Multi Area
IN [ft] plier [sf]
Tilt
[deg]
Cond. Heat Cap
[Btu/hr. SE F] [Btu/sf.F]
Dens. R-Value
[lb/cf] [h.sEFBtu]
In Zone: OFFICE
1 DRAWDY BROS Mtl Bldg Roof/R-19
Batt
90.00 40.00 1 3600.0
0.00
0.0492 1.34
9.49 20.3
❑
Skylights
No Description Type
U SHGC Vis.TYans
[Btu/hr sf F]
W
[ft]
H(Effec)Multivlier
[ft]
Area Total Area
[St] [Sf]
In Zone:
EIn Roof:
Floors
No Description Type
Width H (Effec) Multi Area
[ft] [ft] plier [sf]
Cond. Heat Cap. Dens.
[Btu/hr. sE F] [Btu/sE F] Rb/cf]
R-Value
[h.sEFBtu]
2/5/2013 EnergyGauge Summit® v4.10 3
InZone• OFFICE
I DRAWDY BROS 1 ft. soil, concrete
floor, carpet and
rubber pad
90.00 40.00 1
3600.0 0.2681 34.00 113.33 3.73
❑
Systems
OFFICE System 1
Constant Volume Air Cooled Single No. Of Units 3
Package System < 65000 Btu/hr
Component Category
Capacity
Efficiency IPLV
1 Cooling System
2 Heating System
3 Air Handling System -Supply
4 Air Distribution System (Sup)
5 Air Distribution System (Ret)
42000.00
44000.00
1400.00
13.00 1.00
1.00
0.80
6.00
6.00
❑
❑
❑
❑
❑
Plant
Equipment Category
Size
Inst.No Elf. fPLV
Lj
Water Heaters
W-Heater Description Capacit7Cap.Unit 1/PRt.
Efficiency Loss
Fact -Lighting
Description Category No. of Watts per Area/Len/No. of units Control Type Wattage
Luminaires Luminaire [sf/ft/No] [W]
2/5/2013 EnergyGauge Summit® A.10
Piping
No Type Operating Insulation Nomonal pipe Insulation Is Runout?
11 Temperature Conductivity Diameter Thickness
[F] [ Btu-in/h.sCF] [in] [in]
Fenestration Used
Name Glass Type No. of Glass SHGC VLT
Panes Conductance
[Btu/h.s£F]
ASHULSg1C1rA11 User Defined 1 1.2500 0.8200 0.7600 ❑
Frm
Materials Used
Mat No
Acronym
Description
Only R-Value
RValue Thickness
Conductivity
Density
SpecificHeat
Used
[h.sGF/Btu]
[it]
[Btu/h.ft.F]
[Ib/ct]
[Bt"b.F]
o
.2000
BOARD,1/2IN
178
Mat1178
CARPET W/RUBBER PAD
Yes
1.2300
❑
265
Mat1265
Soil, 1 8
No
2.0000
1.0000
0.5000
100.00
0.2000
❑
48
Mat148
6 in. Heavyweight concrete
No
0.5000
0.5000
1.0000
140.00
0.2000
❑
105
Mat1I05
CONC BLK HW, 8IN,
No
1.1002
0.6667
0.6060
69.00
0.2000
❑
HOLLOW
269
Mat1269
.75" ISO BTWN24" oc
No
2.2321
0.0625
0.0280
4.19
0.3000
❑
23
Mat123
6 in. Insulation
No
- 20.0000
0.5000
0.0250
5.70
0.2000
❑
94
Mat194
BUILT-UP ROOFING, 3/8IN
No
0.3366
0.0313
0.0930
70.00
0.3500
❑
2/5/2013 EnergyGauge Summit® v4.10 5
Constructs Used
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sEF]
[Btu/sEF]
Vb/cf]
[h.sEFBtu]
1014
8"CMU/3/4"ISO BTWN24"oc/5/8 Gyp No
No 0.26
9.70
62.72
3.8
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
105
CONC BLK HW, 8IN, HOLLOW
0.6667
0.000
❑
2
269
.75" ISO BTWN24" oc
0.0625
0.000
❑
3
187
GYP OR PLAS BOARD,1/21N
0.0417
0.000
❑
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sEF]
[Btu/sf.F]
Vb/cf]
[h.sEF/Btu]
1056
Mtl Bldg Roof/R-19 Batt
No
No 0.05
1.34
9.49
20.3
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
94
BUILT-UP ROOFING, 3/8IN
0.0313
0.000
❑
2
23
6 in. Insulation
0,5000
0.000
❑
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sEF]
[Btu/sEF]
[Ib/cf]
[h.sEF/Btu]
1057
1 ft. soil, concrete floor, carpet and rubber pad No
No 0.27
34.00
113.33
3.7
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
265
Soil, 1 ft
1.0000
0.000
❑
2
48
6 in. Heavyweight concrete
0.5000
0.000
❑
3
178
CARPET W/RUBBER PAD
0.000
❑
2/5/2013 EnergyGauge Summit® v4.10