HomeMy WebLinkAboutENERGY EFFICIENCY CODEu
prl 03 - ON 1 %
Florida Energy Efficiency Code For' Building Construction
Florida Departmenf-of ComrnunityAffairs.•
FLA/COM 2004 v2.5 —Form 400A-2004-
Method A: Whole Building Performance Method for. Commercial'Buildings
Short Desc: PATCHES
Owner:
Addressl: MIDWAY ROAD
Address2:
PROJECT SUMMARY
BY
at Lucie County
Description: PATCHES PEDIATRIC
City: PORT ST. LUCIE
State: FLORIDA
Zip: 0
Type: Healthcare -Clinic Class: New Finished building
Jurisdiction: PORT ST LUCIE, ST LUCIE COUNTY, FL (661200)
Cond Area: 4150 SF Cond & UnCond Area: 4150 SF
No of Storeys: I Area entered from Plans 0 SF
Permit No: 0 Max Tonnage 10
If different, write in:
3/22/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLA/COM 2004 v2.5 1
Compliance Summary
Component Design Criteria Result
Gross Energy Use 1,341.2 1,769.1 PASSES
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
PASSES
PASSES
PASSES
PASSES
PASSES
PASSES
Yes/No/NA
RTANT NOTE: An input report of this design building must be submitted
with this Compliance Report.
3/22/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLA/COM 2004 v2.5 2
CERTIFICATIONS
I hereby certify that the plans and a ifications covered by this calculation are in compliance with the
Florida Energy Code
PreparePa
Building Official:
rfh _'2Co Date:
I certify that this building is in compliance with the FLorida Energy Efficiency Code
Date_, c3.,,7 7: D'J
If Required by Florida law, I hereby certify (') that the system design is in compliance with the FLorida
Energy Efficiency Code
Architect: Reg No:
Electrical Designer: Reg No:
Lighting Designer: Reg No:
Mechanical Designer: Reg No:
Plumbing Designer: Reg No:
(") Signature is required where Florida Law requires design to be performed by registered design
professionals. Typed names and registration numbers may be used where all relevant information is
contained on signed/sealed plans.
'3/22/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLA/COM 2004 v2.5
Project: PATCHES
Title: PATCHES PEDIATRIC NURSING CENTER
Type: Healthcare -Clinic
(WEA File: DAYTONABEACH.TMY)
External Lighting Compliance
Description Category
Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
Ext Light 2 Main entries
30.00 10.0 300 50
Design: 300 (W)
PASSES
'Allowance: 300 (W)
Project: PATCHES
Title: PATCHES PEDIATRIC NURSING CENTER
Type: Healthcare -Clinic
(WEA File: DAYTONABEACH.TMY)
Lighting Controls Compliance
Acronym Ashrae Description
Area No. of Design Min Compli-
ID
(sq.ft) Tasks CP CP ance
ProzoISp1 17 Office - Enclosed
4,150 1 2 2 PASSES
PASSES
3/22/2007 EnergyGauge Summit v3.10 incorporating Florida,Energy Code Version - FLA/COM 2004 v2.5
i
Project: PATCHES
Title: PATCHES PEDIATRIC NURSING CENTER
Type: Healthcare -Clinic
(WEA File: DAYTONABEACH.TMY)
Lighting Controls Compliance
Acronym Ashrae Description
I
Area No. of Design Min Compli-
ID I
(sq.ft) .Tasks CP CP ance
PrOZoISp1 17 Office - Enclosed
4,150 1 2 2 PASSES
PASSES
Project: PATCHES
Title: PATCHES PEDIATRIC NURSING CENTER
Type: Healthcare -Clinic
(WEA File: DAYTONABEACH.TMY)
System Report Compliance
PrOSyl System 1
Constant Volume Air Cooled No. of Units
Split System < 65000 Btu/hr 1
Component Category Capacity
Design Eff Design IPLV Comp-
Eff Criteria IPLV Criteria liance
Cooling System Air Cooled <65000 Btu/h
13.00 13.00 8.00 PASSES
Cooling Capacity
.4ir Handling Air Handler (Supply) -
0.80 0.90 PASSES
System -Supply Constant Volume
PrOSy2 System 2
Constant Volume Air Cooled No. of Units
Split System < 65000.Btu/hr 1
Component Category Capacity
Design Eff Design IPLV Comp-
Eff Criteria IPLV Criteria liance
Cooling System Air Cooled < 65000 Btu/h
13.00 13.00 8.00 PASSES
Cooling Capacity
Air Handling Air Handler (Supply) -
0.80 0.90 PASSES
System -Supply Constant Volume
PASSES
3/122/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLNCOM 2004 v2.5
Plant Compliance
Description Installed Size
No
Design Min Design Min
Eff Eff IPLV IPLV
Category Comp
liance
Open centrifugal, chiller 1 10
5.4, 5.0 5.4 5.3
Water Chilling Packages PASSES
(Elec)„ Water Cooled
(centrifugal), 0 to 150 tons
PASSES
Project: PATCHES
Title: PATCHES PEDIATRIC NURSING CENTER
Type: Healthcare -Clinic
(WEA File: DAYTONABEACH.TMY)
Water Heater Compliance
Description Type
Design
Category Eff
Min Design Max Comp
Eff Loss Loss liance
Water Heater 1 Electric water heater
<= 12 [kW] 0.97
0.86 PASSES
PASSES
Project: PATCHES
Title: PATCHES PEDIATRIC NURSING CENTER
Type: Healthcare -Clinic
(WEA File: DAYTONABEACH.TMY)
Piping System Compliance
Category Pipe Din Is Operating Ins Cond Ins Req Ins
[inches] Runout? Temp [Btu-in/hr 'Thick [in] Thick [in]
[F] SF.F]
Heating System (Steam, St
Condensate, & Hot Water)
0.00 0.00 P
3/22/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLA/COM 2004 v2.5 6
A: PATCHES
PATCHES PEDIATRIC NURSING CENTER
Healthcare -Clinic
L File: DAYTONABEACH.TMY)
Other Required Compliance
Category
Section
Requirement (write N/A in box if not applicable)
Check
Infiltration
406.1
Infiltration Criteria have been met
System
407.1
HVAC Load sizing has been performed
Ventilation
409.1
Ventilation criteria have been met
ADS
410.1
Duct sizing and Design have been performed
T & B
410.1
Testing and Balancing will be performed
Motors
414.1
Motor efficiency criteria have been met
Lighting
415.1
Lighting criteria have been met
O & M
102.1
Operation/maintenance manual will be provided to owner
Roof/Ceil
404.1
R-19 for Roof Deck with supply plenums beneath it
El
Report
101
Input Report Print -Out from EnergyGauge FlaCom attached?
El
3/22/2007 EnergyGauge Summit v3.10 incorporating Florida Energy Code Version - FLA/COM 2004 v2.5 7
SIN RNW21609
RIGHT-N ZONE SUMMARY
Units:
For:
By:
Job #:
U.S. customary (I—P)
PATCHES
COOLING LOAD
Zone:
1 & 2
1.
DESIGN CONDITIONS at 3PM
Peak load at 3PM
Inside: 75 OF Outside: 90 OF
TD:
15 OF
RH: 50 % Moisture: 61 gr/lb
Mult:
1.0 Ins.wb
63 OF
Sensible
Latent
2.
SOLAR RADIATION THROUGH GLASS
4956
3..
TRANSMISSION GAINS Sensible
9867
Walls: 1559
Glass: 677
Doors: 454
-
-
Partitions: 196
Floors: 0
Roofs/Ceilings: 5692
Return Air Ceiling: 1290
4.
INTERNAL HEAT GAIN Sensible
Latent
23834
5940
Occupants: 22500
5940
-
-
Lights: 54
0
-
-
Motors: 0
0
-
-
Appliances &Other: 1280
0
-
-
5.
INFILTRATION: Outside air cfm:
24
396
1003
6.
SUBTOTAL: Spaceload
39053
6943
7.
SUPPLY DUCT
1953
-
8.
SUBTOTAL: Bldg comp's and supply duct
41006
Actual cfm: 1866 at Supply TD:
20
-
-
9.
VENTILATION: Make—up air cfm:
201
3313
8397
10.
RETURN AIR LOAD: Lighting & roof (net)
588
-
11.
RETURN DUCT
1172
-
J2.
TOTAL LOADS ONEQUIPMENT
46078
15339
HEATING LOAD
13.
DESIGN CONDITIONS
Mult:
1.0
Inside: 70 OF Outside: 42 OF
TD:
28 OF
14.
TRANSMISSION LOSSES
12503
Walls: 3085
Glass: 1336
-
Doors: 847
-
Partitions: 365
-,'
Floors: 3583
-
Roofs/Ceilings: 2446
-
Return Air Roof: 840
-
15.
INFILTRATION; Outside air cfm:
231
7098
16.
SUBTOTAL: Building components
19601
17.
SUPPLY DUCT:
980
18.
VENTILATION: Make—up air cfm:
201
6185
19.
HUMIDIFICATION
5223
20.
RETURN DUCT
588
21.
TOTAL HEATING LOAD ON EQUIPMENT
32577
Manual N: 4th Edition
Right-N: Ver.3.0.07
Certified by ACCA to meet all requirements of Manual Form N
EnergyGauge Summit v3.10
INPUT DATA REPORT
Proiect Information
Project Name: PATCHES Orientation: North
Project Title: PATCHES PEDIATRIC NURSING CENTER Building Type: Healthcare -Clinic
Address: MIDWAY ROAD Building Classification: New Finished building
State: FLORIDA
Zip: 0
Owner:
No.of Storeys: 1
GrossArea: 4150 SF
Zones
No Acronym Description Type
Area
[sfl
Multiplier
Total Area
[sfl
1 PrOZol Zone 1 CONDITIONED
4150.3
1
4150.3 ❑
Spaces
No Acronym Description Type Depth
[ftl
Width Height Multi
[ftl [ftl plier
Total Area
[sfl
Total Volume
[cfl
3/22/2007
EnergyGauge Summit v3.10
I
In Zone: PrOZol
I PrOZ01Sp1
ZOOSpl Office - Enclosed
99.29 41.80
9.00
1 4150.3 —
3735791:1
Lighting
No
Type Category
No. of Watts per
Luminaires Luminaire
Power
[W]
Control Type
No.of
Ctrl pis
In Zone: Pr0Zo1
In Space: Pr0Zo1Sp1
I Recessed Fluorescent - General Lighting
19 50
950
Manual On/Off
1 ❑
2
No vent
Recessed Fluorescent - General Lighting
27 50
1350
Manual On/Off
1 ❑
No vent
Walls
No Description
Type Width H (Effec) Multi Area DirectionConductance Heat
[ft] [ft] plier [sf] [Btu/hr. sf. F] Capacity
Dens. R-Value
[lb/cf] [h.sf.FBtu]
[Btu/sf.F]
In Zone: PrOZol
1 PrOZo 1 Wal 5/8" stucco 41.80
99.29 1 4150.3
North
0.2067 5.731
34.65 4.8 ❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
Gyp
Windows
No
Description Type Shaded U SHGC Vis.Tra
W
H (Effec) Multi
Total Area
[Btu/hr sf F]
[ft]
[ft] plier
[Sf]
In Zone: PrOZol
In Wall: PrOZolWal
I PIOZolWalWil User Defined No
2 PrOZolWalWi2 User Defined No
3 PrOZolWalWi3 UserDefined No
1.2500 0.70 0.58
1.2500 0.70 0.58
1.2500 0.70 0.58
2.00
2.00
3.00
6.00 6
5.00 4
5.00 2
72.0 El
40.0 El
30.0 El
3/22/2007
EnergyGauge Summit v3.10
-
Doors
-
-
No Description Type
Shaded? Width H (Effec) Multi
Area
Cond.
Dens. Heat Cap.
R-Value
[ft] Ift]
plier
[sf]
[Btu/hr. sE F] [lb/cf] [Btu/sf. F1
[h.sEF/Btu]
In Zane: PrOZol
In Wall: PrOZolWal
1 PrOZolWalDrl Aluminum door,
No 3.00 7.00
3
21.0
0.1919
43.67
0.53
5.21
❑
1.25 in.
polystyrene
2 PrOZolWalDr2 Aluminum door,
No 6.00 7.00
3
42.0
0.1919
43.67
0.53
5.21
❑
1.25 in.
polystyrene
Roofs
No Description Type
Width H (Effec) Multi
Area
Tilt
Cond.
Heat Cap
Dens.
R-Value
[ft] IN plier
[sf1
[deg]
[Btu/hr. SE F]
[Btu/sE F1
[lb/cf]
[h.sf.F/Btu]
In Zone: Pr
1 PrOZOlRfl Shnglll/2"WD
41.80 99.29 1
4150.3
45.00
0.0320
1.50
8.22
31.2
❑
Deck/WD Truss/9"
Batt/Gyp Brd
Skylights
No Description Type
U SHGC Vis.Trans
W
H (Effec) Multiplier
Area
Total Area
[Btu/hr sf F]
IN
IN
[Sf]
[Sf]
In Zone:
In Roof:
3/22/2007
EnergyGauge Summit v3.10
7�__-
Floors -
No Description Type Width
[ft]
H (Effec) Multi Area Cond. Heat Cap. Dens. R-Value
[ft] plier [sf] [Btu/hr. sf. F] [Btu/sL F] [lb/cf] [h.sf.FBtu]
In Zone: PrOZol
1 Pr0ZOlFl1 Concrete floor, 41.80
carpet and rubber
pad
99.29 1 4150.3 0.5987 9.33 140.00 1.67
❑
Systems
PrOSyl System 1
Constant Volume Air Cooled Split No. Of Units 1
System < 65000 Btu/hr
Component Category
Capacity Efficiency IPLV
1 Cooling System (Air Cooled < 65000 Bluth Cooling
Capacity)
2 Air Handling System -Supply (Air Handler (Supply) -
Constant Volume)
61.50 13.00 8.00
1500.00 0.80
❑
❑
PrOSy2 System 2
Constant Volume Air Cooled Split No. Of Units 1
System < 65000 Btu/hr
Component Category
Capacity Efficiency IPLV
1 Cooling System (Air Cooled < 65000 Btu/h Cooling
Capacity)
2 Air Handling System -Supply (Air Handler (Supply) -
Constant Volume)
61.50 13.00 8.00
1500.00 0.80
❑
❑
Plant
Equipment Category
Size Inst.No Eft. IPLV
1 Open centrifugal, chiller Cooling Equipment
10.0 [Tons] 1 5.40 [COP] 5.40
3/22/2007
EnergyGauge Summit v3.10
N
Water Heaters
W-Heater Description CapacitlCap.Unit UP Rt. Efficiency Loss
1 Electric water heater 50 [Gal] [M] 0.9700 [Ef] [Btu/h] ❑
Ext-Lighting
Description Category
No. of Watts per Area/Len/No. of units
Luminaires Luminaire [sf/ft/No]
Control Type
Wattage
[W]
Piping
No Type
Operating Insulation
Temperature Conductivity
[F] [ Btu-in/h.sEF]
Nomonal pipe
Diameter
[in]
Insulation
Thickness
[in]
Is Runout?
I Heating System (Steam, Steam Condensate, &
Hot Water)
105.00 0.28
0.25
0.00
Yes ❑
Fenestration Used
Name Glass Type No. of Glass SHGC VLT
Panes Conductance
[Btu/h.sf.F]
ASHULTntAl1Fr User Defined 1 1.2500 0.7000 0.5800 ❑
In
3/22/2007
EnergyGauge Summit v3.10
5
- -
- Materials Used
-
Only R-Value
RValue Thickness
Conductivity
Density
SpecificHeat
Mat No
Acronym
Description
Used
[h.sf.FBtul
[ft]
[Btu/h.ft.F]
[lb/cf]
[Btu/Ib.F]
264
Mat1264
ALUMINUM, 1/16IN
No
0.0002
0.0050
26.0000
480.00
0.1000
❑
214
Mat1214
POLYSTYRENE, EXP.,
No
5.2100
0.1042
0.0200
1.80
0.2900
El
1-1/41N,
187
MatI187
GYP OR PLAS
No
0.4533
0.0417
0.0920
50.00
0.2000
❑
BOARD,1/2IN
151
Matl151
CONC HW, DRD, 140LB,
No
0.4403
0.3333
0.7570
140.00
0.2000
❑
4IN
178
Mat1178
CARPET W/RUBBER PAD
Yes
1.2300
❑
268
Mat1268
0.625" stucco
No
0.1302
0.0521
0.4000
16.00
0.20o0
❑
42
Mat142
8 in. Lightweight concrete
No
2.0212
0.6670
0.3300 -
38.00
0.2000
❑
block
269
Matl269
.75" ISO BTWN24" oc
No
2.2321
0.0625
0.0280
4.19
0.3000
❑
12
Matll2
3 in. Insulation
No
10.0000
0.2500
0.0250
2.00
0.2000
❑
23
Mat123
6 in. Insulation
No
20.0000
0.5000
0.0250
5.70
0.2000
❑
81
Matl81
ASPHALT -ROOFING,
Yes
0.1500
❑
ROLL
244
Mat1244
PLYWOOD, 1/21N
No
0.6318
0.0417
0.0660
34.00
0.2900
❑
Constructs Used
Simple
Massless Conductance Heat Capacity
Density
RValue
No
Name
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.FBtu]
1002
Aluminum door, 1.25 in. polystyrene
No
No
0.19
0.53
43.67
5.2
❑
Layer
Material Material
Thickness
Framing
No.
[ft]
Factor
1
264 ALUMINUM, 1/16IN
0.0050
0.000
❑
2
214 POLYSTYRENE, EXP., 1-1/41N,
0.1042
0.000
❑
3
264 ALUMINUM, 1116 IN
0.0050
0.000
❑
3/22/2007 EnergyGauge Summit v3.10
- --Simple-
- Massless--
- Conductance - - Heat Capacity
—Density�Value__
No
Name
Construct
Construct
[Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sCFBtu]
1004
Concrete floor, carpet and rubber pad No
No
0.60
9.33
140.00
1.7
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
151
CONC HW, DRD, 140LB, 41N
0.3333
0.000
❑
2
178
CARPET W/RUBBER PAD
0.000
❑
Simple
Massless
Conductance Heat Capacity
Density
RValue
No
Name
Construct
Construct
[Btu/h.sf.F]
[Btu/sEF]
[lb/cf]
[h.sf.F/Btu]
loll
5/8" stucco /8"CMU/3/4"IS0 No
No
0.21
5.73
34.65
4.8
❑
BTWN24"oc/.5"
Gyp
Layer
Material
Material
Thickness
Framing
No.
[it]
Factor
1
268
0.625" stucco
0.0521
0.000
❑
2
42
8 in. Lightweight concrete block
0.6670
0.000
❑
3
269
.75" ISO BTWN24" oc
0.0625
0.000
❑
4
187
GYP OR PLAS BOARD,1/21N
0.0417
0.000
❑
Simple
Massless
Conductance Heat Capacity
Density
RValue
No
Name
Construct
Construct
[Btu/k.sf.F]
[Btu/sf.F1
[lb/cf]
[h.sf.FBtu]
1038
Shngf/l/2"WD Deck/WD Truss/9" Batt/Gyp No
No
0.03
1.50
8.22
31.2
❑
Brd
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
I
81
ASPHALT -ROOFING, ROLL
0.000
❑
2
244
PLYWOOD, 1/21N
0.0417
0.000
❑
3
12
3 in. Insulation
0.2500
0.000
❑
4
23
6 in. Insulation
0.5000
0.000
❑
5
187
GYP OR PLAS BOARD,1/2IN
0.0417
0.000
❑
3/22/2007 EnergyGauge Summit v3.10