INSPECTION CARD
Permit#: SLC- 0703-0417 ConfM 683
Type: Commercial Renovation
Issued 05/24/2007 Status: FIN
Double Fee: No
Job Location 2959-2963 W MIDWAY RD BUILDING 2
Jurisdiction: St. Lucie County
City, FORT PIERCE
Lot: Block: �CgA,A,�
Parcel: 3405-421-0001-000/2 Subdiv:
Aft- QC Q
Flood: Elev: Flood Map:
.8)e
op
Job Description: INTERIOR BUILD -OUT OF A COMPLETE
BUILDING, FOR PEDIATRIC NURSING
(BUILDING II) MASTER PERMIT FOR BUILDING
#0504-0017, ONLY DAY CARE SERVICE NO
OVERNIGHT STAYS ALLOWED.
Setbacks Left: Right
Front Rear:
Inspection Notes: CHANGE OF PLUMBING CONTRACTOR TO BE DONE BEFORE ANY FURTHER INSPECTIONS
PER GREG S. TO PLUMBING CONCEPTS.
FIRE FINAL 12/03/2007
Contractor DRAWDY TROY W
DRAWDY BROTHERS CONSTRUCTIC (772) 464-8160
2945 W MIDWAY RD
FT PIERCE, FL 34981
Property Owner TROY DRAWDY
(772) 464-8160
2945 W MIDWAY RD
FORT PIERCE, FL 34981
Property Owner PHILLIP DRAWDY
(772) 464-8160
2945 W MIDWAY RD
FORT PIERCE, FL 34981
SUB -PERMITS
Permit #
Status PT Cart #
DBA Owner / Builder
Job Description
0703-0417-01
FIN EP 18881
NEW LIGHT ELECTRIC INC
0703-0417-02
FIN PP 21297
PLUMBING CONCEPTS INC
chg from #18628 to #21297
0703-0417-03
FIN ME 17334
DELAPORTE'S HEATING & C(
INSPECTIONS - For Requests, Call: (772) 462.1261
Pem # Code Description
Priori Date School. Res Description
Inspector Date Insp.
0703-0417 425
Sewer Connect
0 90 Approved
Greg Smyth 06/13/2007
null
Resulted: Wed
Jun 13 13:29:50 EDT 2007
0703-0417 104
Compaction Test
1 06/19/2007 92 Accepted As Noted
Barbara Counsello 06/19/2007
0417 420 Plumbing Rough 1 06/13/2007 81 Disapproved Greg Smyth 06/13/2007
CHANGE PLUMBING CONTRACTOR ON PERMIT TO PLUMBING CONCEPTS BEFORE ANY MORE INSPECTIONS. SERVICE
NOT ROUGHED IN PLUMBER DIDN'T HAVE IT ON HIS SET OF PLANS.
eduled: Tue Jun 12 15:00:39 EDT 2007 with value: Wed Jun 13 00:00:00 EDT 2007
ulted: Wed Jun 13 13:30:10 EDT 2007
0417 420 Plumbing Rough 1 06/15/2007 - 90 Approved Greg Smyth 06/15/2007
nspection 1
eduled: Thu Jun 14 10:55:59 EDT 2007 with value: Fri Jun 15 00:00:00 EDT 2007
ulted: Fri Jun 15 13:30:23 EDT 2007
0417 115 Slab 2 06/20/2007 90 Approved Steve Breads 06/20/2007
: Tue Jun 19 13:15:05 EDT 2007 with value: null
121 Termite Spray 2 06/20/2007 90 Approved
0703-0417 140 Construction Rough Frami 3 06/29/2007 90 Approved
Steve Brasda 06/20/2007
Gary Gerstemeier 06/2912007
Permit Nun 0703-0417
.null ,
Scheduled: Thu Jun 28 07:41:37 EDT ku'ur with value: Fri Jun 29 00:00:00 EDT 2007
0703-0417 238 Electric Rough 3 07/24/2007 90 Approved Gary Gerstemeier 07/24/2007
null
Scheduled: Mon Jul 23 10:12:00 EDT 2007 with value: Tue Jul 24 00:00:00 EDT 2007
0703-0417 351 Mechanical Rough-In(ducl 3 07/24/2007 90 Approved Gary Scheigner 07/2412007
null
Scheduled: Mon Jul 23 10:12:29 EDT 2007 with value: Tue Jul 24 00:00:00 EDT 2007
0703-0417 423 Plumbing Top Out 3 07/18/2007 81 Disapproved Greg Smyth 07/18/2007
null WATER CLOSET IN ADA REST ROOM TO FAR FROM SIDE WALL. ALL HOSE BIBBS TO HAVE SEPERATE SHUTT OFF VALVES
Scheduled: Tue Jul 17 15:13:42 EDT 2007 with value: Wed Jul 18 00:00:00 EDT 2007
Resulted: Wed Jul 18 11:54:26 EDT 2007
0703-0417 423 Plumbing Top Out 3 07/31/2007 90 Approved
Greg Smyth 07/31/2007
Re -inspection 1
Scheduled: Mon Jul 30 09:55:27 EDT 2007 with value: Tue Jul 31 00:00:00 EDT 2007
Resulted: Tue Jul 31,13:52:24 EDT 2007
0703-0417 141 Insulation 4 08/08/2007 90 Approved
Greg Smyth 08/08/2007
Rey -inspection 1
Scheduled: Tue Aug 7 15:31:28 EDT 2007 with value: Wed Aug 8 00:00:00 EDT 2007
Resulted: Wed Aug 8 14:38:55 EDT 2007
0703-0417 141 Insulation 4 08/06/2007 75 Cancelled by Custome
Barbara Counsello 08/06/2007
816107 incall contr canceled.. bac
null
Scheduled: Fri Aug 3 09:40:38 EDT 2007 with value: Mon Aug 6 00:00:00 EDT 2007
0703-0417 165 Handicap Restrooms 5 12/03/2007 81 Disapproved
Gary Gerstemeier 12/03/2007
Did not have handicap restroom sign.
null
Scheduled: Fri Nov 30 11:46:37 EST 2007 with value: Mon Dec 3 00:00:00 EST 2007
0703-0417 165 Handicap Restrooms 5 12/18/2007 90 Approved Gary Gerslemeier 12/1812007
Re -inspection 1
Scheduled: Mon Dec 17 14:31:28 EST 2007 with value: Tue Dec 18 00:00:00 EST 2007
0703-0417 280 Electric Final 5 11/30/2007 90 Approved GaryGerslemeier 11/30/2007
Re -inspection 3
Scheduled: Wed Nov 28 08:06:43 EST 2007 with value: null
Scheduled: Wed Nov 28 11:08:00 EST 2007 with value: null
Scheduled: Wed Nov 28 12:14:23 EST 2007 with value: null
Scheduled: Thu Nov 29 07:01:40 EST 2007 with value: null
Scheduled: Thu Nov 29 13:42:00 EST 2007 with value: null
Scheduled: Thu Nov 29 15:47:35 EST 2007 with value: null
Scheduled: Thu Nov 29 16:49:36 EST 2007 with value: Fri Nov 30 00:00:00 EST 2007
0703-0417 280 Electric Final 5 09/28/2007 82 Disapproved-Reinspec GaryGerstemeier 09/28/2007
3-way switch in hallway not wired correctly. Generator not tied into building. FPL meter location and adjacent panel locations not
accordingto plans. Tankless water electric changed to water heater tank without revision. Revisions needed for changes in electric panel
locations. Need transfer switch included in drawings for generator. Fee req'd. $50.00
Re -inspection 1
Scheduled: Thu Sep 27 13:42:11 EDT 2007 with value: Fri Sep 28 00:00:00 EDT 2007
0703-0417 280 Electric Final 5 11/19/2007 81 Disapproved
Van Whitaker
11/19/2007
Re -inspection 2
Scheduled: Fri Nov 16 11:16:10 EST 2007 with value: Mon Nov 19 00:00:00 EST 2007
Resulted: Mon Nov 19 11:12:08 EST 2007
0703-0417 280 Electric Final 5 09/25/2007 81 Disapproved
GaryGerstemeier
09/25/2007
Power not turned on to weer half of the building. Water heater not terminated.
null
Scheduled: Mon Sep 24 10:21:22 EDT 2007 with value: Tue Sep 25 00:00:00 EDT 2007
280--need disc for hwh in laundry room
0703-0417 380 Mechanical Final 5 11/21/2007 90 Approved
Gary Scheigner
11/21/2007
nut
Sc eduled: Tue Nov 20 09:20:57 EST 2007 with value: Wed Nov 21 00:00:00 EST 2007
070 -0417 480 Plumbing Final 5 11/21/2007 81 Disapproved
Gary Scheigner
11/21/2007
nul
Sc eduled: Tue Nov 20 09:21:33 EST 2007 with value: Wed Nov 21 00:00:00 EST 2007 NEED HAMMER ARRESTERS ON KITCHEN
SINK AND ICEMAKER PERMIT BOX FULL OF WASPS
0703-0417 480 Plumbing Final 5 11/27/2007 90 Approved
Gary Scheigner
11/27/2007
Red -inspection 1
0703-0417 700 Fire Department Final 5 01/30/2008 90 Approved
Debbie Knupp
01/30/2008
Rel inspection 1
0703-0417 700 Fire Department Final 5 '11/30/2007 81 Disapproved
Rob Pedreira
11103/2007
12/7/07 spoke to linda- fire dept: inspection was disapproved.bac
null
Scheduled: Thu Nov 29 16:52:01 EST 2007 with value: Fri Nov 30 00:00:00 EST 2007
Permit Nun 0703-0417
0703-0417 823 Test & Balance Repori 5 12/13/2007 92 Accepted As Note< Ken Arnold 12/13/2007
0703-0417 900 Plan Revision 5 92 Accepted As Noted Van Whitaker 10/30/2007
CHANGE PANEL AND METER LOCATION ALSO CHANGE FROM TANKLESS TO WATER HEATER WITH TANK
0703-0417 999 Final Inspection 5 01131/2008 99 Final Approval Greg Smyth 01131/2008
: Wed Jan 30 11:37:28 EST 2008 with value: Thu Jan 31 00:00:00 EST 2008
Thu Jan 31 08:16:35 EST 2008
Permit Nun 0703-0417