HomeMy WebLinkAboutPROJECT SUMMARYwrightsoft° Project Summary Job: Entire House 9y B: QUICK CALCS, INC. 317 ST. LUCIE LDL, FT. PIERCE, FL 34946Phone: 77246M799 Fax 772-46M796 Email: OUICKCALCS@AOL.COM Project• • For: THE GRAND CARLTON WYNNNE DEVELOPMENT, FT. PIERCE, FL A' Notes:ey,V�� /O 004p Nk Design. • Weather. Fort Pierce, FL, US Winter Design Conditions Outside db Inside db Design TD Summer Design Conditions 42 OF Outside db 70 OF Inside db 28 OF Design TD Daily range Relative humidity Moisture difference Heating Summary Structure 17848 Btuh Ducts 5654 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 23503 Btuh Infiltration Method Construction quality Fireplaces Simplified Average 0 Heatingg cool* Area (ft2) 1446 1446 Volume (W) 12511 12511 Air changeslhour 0.45 0.23 Equiv. AVF (cfm) 94 48 Heating Equipment Summary Make Carrier Trade CARRIER AIR CONDITIONING Model 25HBC536A'030 AHRI ref 7914585 Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat Capacity balance point = 32 OF Backup: 8.5 HSPF 34600 Btuh @ 47-F 1160 cfm 0.049 cfm/Btuh 0.50 in H2O Input = 7 kW, Output = 23009 Btuh, 100 AFUE 90 OF 75 OF 15 OF 50 % 61 gr/Ib Sensible Cooling Equipment Load Sizing Structure 17520 Btuh Ducts 8536 Btuh Central vent, (0 cfm) 0 , Btuh . (none) Blower 0 Btuh Use manufacturers data n Ratelswingg multipplier Equipmentsensibleload 0.95 24753 Btuh Latent Cooling Equipment Load Sizing Structure 3203 Btuh Ducts 2318 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 6521 Stuh Equipment total load 30274 Btuh Req. total rapacity at 0.70 SHR 2.9 ton Cooling Equipment Summary Make Carder Trade CARRIERAIR CONDITIONING Cond 25HBC536A•030 Coil FX4DN((B,F)037 AHRI ref 7914585 Efficiency 12.0 EER, 15 SEER Sensible cooling 24360. Btuh Latent cooling 10440 Btuh Total cooling 34800 Btuh Actual airflow 1160 cfm Air flow factor 0.045 cfm/Btuh Static pressure 0.50 in H2O Load sensible heat ratio 0.83 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. ' 13 wrightsoft' 2o17-Apr-11 09:29.38 Right- CAR Universal .mp CaIc = MJ8 F 01 ^ ® �� Page 1 ...uick CaIcslDocumenta\THE GRAND CARLTON-1446.rop Catc = MJ3 Front Door fac� T � y',®ILd' DEC 1 04 2018 I I wrightsoft RighW@ Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 7724666799 Fax 772-4666798 Email: QUICKCALCS@IOL.COM 1 Room name Entire House BEDROOM 2 EVosed wall 156.2 It 49.0 ft 3 Room helgM 8.7 It d 8.0 ft heatfcool 4 Room dimensions 1.0 x 297.0 ft 5 Room area 1445.5 ft' 297.0 W Ty Construction U-value Or HTM Area (ft') Load Area (ft� Load number I (Btuwft-F) (Btul fP) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross 14/P/S Heat Cool Gross WP/S Heat Cool 6 W 13A4ccs - 0.143 n 4.00 255 503 465 1862 1184 72 72 288 - 183 . ' L-G '4AS2am 0.770 • n 21.56 19.31 - ' 38 ' 0 816 730 0 C C - 0 13A-0ocs 0.143 a 4.00 255 128 83 333 212 0 0 0 0 1Actom 1.270 a 35.56 87.29 24 2 848 2082 0 0 0 0 11 11DO 0.390 a 10.92 11.31 21 21 229 238 0 0 0 0 W 13A4ccs 0.143 se 4.00 255 34 34 136 66 0 0 -0 0 13A-0ocs 0.143 s 4.00 255 360 353 1414 899 216 216 865 650 1A-clam 1.270 a 35.56 34.77 7 7 247 241 0 0 0 0 W 13A-0acs 0.143 w 4.00 2.55 310 237 949 603 104 72 288 183 iL 1A 1= 1.270 . w 35.56 ` 55.21 32 2 1140 • .1770 32 2 1140 - 1770 4AS2am . 0.770 w 21.56 19.31 41 . 41 880 788 0 0 . 0 '. 0 P 12C-0sw 0.091 - 2.55 1.28 192 192 489 246 0 0 0 0 C', 46A30md 0.1W, - - 0:90 2.32 1446 1446 1295 - 3354 297 297 266 689 F 22A-tpl 0.989 27.69 0.00 1446 156 4325 0 297 49 1357 0 6 c)AFD �lon 918 627 Envelope loss/gain 14961 13349 4204 40(3 12 a) infiltration 2887 791 848 232 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 6 1380 3 6W Appliances/other 2000 0 Subtotal Vines 6 to 13) 17848 17520 5053 4925 Less eldemal load o 0 '0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 17848 17520 5053 4925 15 Duct loads 32% 49% 5654 8536 320% 49% 1601 2400 Total mom load I I 23503 26056 6653 7375 Air required(cfm) 1160 1160 328 326 " " wrightsoft- Right -Suite® Universal 2017 17.0.14 RSU08101 ...uick Celcs\Documents\THE GRAND CARLTON-1446.mp Cale = MJB Front Door faces: 2017-Apr-11 09:29:38 . Page 1 �+wrightsoft, Right-MWorksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772466-6799 F= 77246"796 Email: OUICKCALCS@AOL.COM 1 Room name WIC KfrCHEN 2 .E)yosed wall 0 ft 0 It 3 Room height 8.0 It heat/cool 8.0 ft heat/cool 4 Room dimensions 6.0 x 9.0 ft 1.0 x 172.0 ft 5 Room area 54.0 ft" 1720 ft- Ty Construction U-value Or HTM Area (ft-) Load Area (fN) Load number I (Bluhtft'-F) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross WP/S Heat Cool Gross WP/S Heat Cool 6 1-_G 13A4ccs. 0.143 -- n 4.00 265 0 0 0 0 0 0 0 0 4AS-2cn 0.770 n '21.56 19.31 0 0 0 0 0 0. 0 0 13A-0acs 0.143 a 4.00 2-55 0 0 0 0 0 0 0 0 1A atom 1.270 a 35.56 87.29 0 0 0 0 0 0 0 0 11 r--0 11DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0 W 13A4ocs 0.143 se 4.00 255 0 0 0 0 0 0 0 0 y1 13A4ocs 0.143 s 4.00 255 0 0 0 0 0 0 0 0 t-G 1Aclom 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0 13A-4= 0.143 w 4.00 2.55 0 0 0 0 0 . 0 .0 0 - T 1Aa1om 1.270 w 35.56 55.21 0 0 0 0 0 0 0 .0 4AS-2om - 0.770 w 21.66 19.31 0. 0 0 0 0 0 0 0 P -C 12C-0sw 0.091 - 2.55 1.28 0 0 0 0 64 64 163 82 . _ 46A30md 0.032 - 0.90 - 2.32 54 .. 54 48, 125 , 172 172 154 399 F 22A4pl 0.989 - 27.69 0.00 54 0 0 0 172 0 0 0 6 e)AM excursion -9 ' •170 Envelope loss/gam 48 117 317 311 12 a) Infiltration 0 0 0 0 b) Roomvenlilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 C C Appliances/other 0 C 2000 Subtotal(lines 6to 13) 48 117 317 2311 Less e#emal load 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 48 117 0 317 0 2311 15 Duct loads 32% 10% 15 67 32% 49% 100 1126 Total room lead Air required 64 1784 a18 315 3 8 21 153 wrightsoft• Right-SuiteO Universal 2017 17.0.14 RSU08101 Calcs\Documents\THE GRAND CARLTON-1446.mp Calc = MJ8 Front Door faces: 2017-Apr-11 09:29:38 Page 2 wrightsoftRight-M Worksheet Job: Entire House Date: QUICK CALCS, INC. By- 317 ST. LUCIE LI . FT. PIERCE, FL 34946 Phone: 772�46"799 Fax 772-466-6796 Email: OUICKCALCS@AOL.COM 1 Room name BATH BEDROOM 2 2 =ad wall 5.0 it 34.2 It 3 Room height 8.0 it heavowl 8.0 It heat/cool 4 Room dimensions 9.0 x 5.0 ft 1.0 x 203.5 If 5 Room area 45.0 fl2 203.5 ft2 Ty Construction U-value Or HTM Area (fP) Load Area (ft2) Load number I (Btuh/W"F) (BtutJft2) or perimeter (ft) (Stuh) or perimeter (R) (Btuh) Heat Coal Gross NIP/S Heat Cool Gross NIP/S Heat Cool 6 . - 13A4ccs 0.143 n 4.00 255 40 40 160: 102 - 128 128, 513 : 326 4Ai2am 0.770 n 21.56 19.31 0- 0 0 0 0 0 0 0 VE: 13A-4ocs 0.143 a 4.00 255 0 0 0 0 80 56 225 143 3 1Ac1om 1.270 a 35.56 87.29 0 0 0 0 24 2 848 2092 11 �D 11DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0 w .13A-0ccs 0.143 se 4.00 2.65 0 0 0 0 34 34 - 136 w 13A4ocs 0.143 s 4.00 255 0 0 0 0 32 32 128 .86 81 �C 1Ac1om 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0 13A-4ocs `1A�clam 0.143 w 4.00 255 0' 0 0 0 0 0 0 0 1.270 _ w 35.56 55.21 0 0 0 0 0 0 0 0 ,4A5-2an . ,0.770 w 21.56 - 19.31 0 0 0 0 0 0 0 0 P 12C-0sw 0.097 2.55 1.28 0 0 0 0 0 0 0 . 0 C .16A30md 0.032 - 0.90 2.32 45 45 - 40 104 204 204 ` ' 182 472 F 22A4o1 0.989 - 27.69 0.00 45 5 138 0 204 34 946 0 6 c)AED excursion -16 -85 Envelope loss/gain 339 1901 2978 3106 12 a) infiltration 87 24 593 162 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13) 425 214 3571 3498 Less mdemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 15 Subtotal Duct loads 425 4 31 32% 49% 135 10 104 32Yo 49Yo 113131 13498 704 1704 Total mom load Air required (cfm) 560 318 4 5203 28 14 232 232 32 232 wrightSoR' Right -Suite® Universal 2017 17.0.14 RSU08101 ...uick CalcMDocuments\THE GRAND CARLTON-1446.mp Calc = MJ8 Front Door faces: 2017-Apr-11 09:29:38 Page 3 wrightsoft, Right- J® Worksheet Job: Entire House Date: QUICK CALCS, INC. By- 317 ST. LUCIE LN, FT. PIERCE, FL 34946 Phone; 772-46"799 Fax 772-466-6796 Emil: OUICKCALCS@AOL.COM 1 Room name LAUNDRY GREATIDINING 2 F� ad wall 6.0 ft 47.0 ft 3 Room height 8.0 ft heat/c0ol 9.8 ft heat/cool 4 Room dimensions 7.0 x 6.0 ft 1.0 x 526.0 ft 5 Room area 42.0 fl' 526.0 W Ty Construction U-value Or HTM Area (w) Wad Area (ft.) Load number (Btuhlfti°F) (Btuh/ft') or perimeter (ft) IBM) a perimeter (ft) (Btuh) Heat Cool Gross WP/S Heat Cool Gross WP/S Heat Cool 6 :13A4ocs .-0.143 n 4.00 255 0 0 0 0 255 217 869 552 4AS-20m b:770 - A : 21.56 -- 19.31 0 - 0 - 0 0 38 : 0 815 730 VjI�G 13A-0ocs 0.143 a 4.00 2.55 0 0 0 0 0 0 0 0 1A cl m 1.270 a 35.56 87.29 0 0 0 0 0 0 0 0 11 1-D 11D0 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0 w .13A-4ocs 0:143 se 4.00 255 0 0 0 0 0 0 0 0 l7/ 13A-4xs 0.143 s 4.00 2.55 48 48 192 122 0 0 0 0 -a 1Aaiom 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0 �f1 I-G .13A4ws 0.143 w 4.00 2.55 0 0 0 0 206' 165 661 420 1Aclonn - 1.270 w 35.56 55.21 0 0 0' 0 0 0 0 0 �G -P 4AS-2cm 0.7,70 w 21.56 19.31 0 0 0 0 41 41 880 . 788 12C-0sw 0.091 2.55 1.28 56 56 143 72 0 0 0 0 C .: :16A-30md.. 0.032 - '0.90 2.32 42 42 38 ',. 97 526 526. 1220 F 22A-tpl 0.989 27.69 0.00 42 6 166 0 526 47 ,474 1302 0 I'a .' . 6 c)AED excursion -22 668 Frnelope Ices/gain 539 270 4997 4379 12 a) Nfiltration 104 28 997 273 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 2 460 Appliances/other 0 0 Subtotal (lines 6 to 13) 643 298 5994 5112 Less edema[ load 0 0 0 0 Less transfer 0 0 0 0 Redistdbution 0 0 0 0 14 Subtotal 643 298 5994 5112 15 Duct toads 32% 49% 204 145 32% 49% 1899 2490 Total room load 1 1 846 443 7892 7602 Air required(cfm) 42 20 390 338 -Fp- wrightsoR- Right -Suite® Universal 201717.0.14 RSU08101 ...uick Calcs\Documents\THE GRAND CARLTON-1441i Calc = MJ8 Front Door faces: 2017-Apr-11 09:29:38 Page 4 + wrightsofr Righted® Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772466.6799 Fa�c 772466.6796 Emil: OUICKCALCS@,AOL.COM 1 Room name FOYER M. BATH 2 E)prsed wall 7.0 it 8.0 ft 3 Room height 8.0 It heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 50.0 It 7.0 x 8.0 It 5 Room area 50.0 ft' 56.0 fN TY Construction U-value Or HTM Area ' (it') Load number (Btuf✓ftUF) (Btulvft') or perimeter (it) (B�tauldi) arm perimeter (ft) (Bluh) Heat Cool Gross WP/S Heat Cool Gross WP/S Heat Cool 6 4y 13A-0ocs -_ 0.143- n 4.00 2.55 6 8 '.32 20, 0 0 0 0 • Lr' 4PS2o;n.' 0.770 n 21.56 ' 19.31 0 0 0 0 - 0 0 0 - '0 13A-0acs 0.143 a 4.00 2.55 48 27 108 69 0 0 0 0 1Ac1om 1.270 a 35.56 87.29 0 0 0 0 0 0 0 0 11 11DO 0.390 a 10.92 11.31 21 21 229 238 0 0 0 0 W .13AAces 0.143 se 4.00 2.65 0 0 0 0 0 0 0 0 y/ 13AAocs 0.143 s 4.00 2.55 0 0 0 0 64 57 228 145 -a 1Ac1om 1.270 s 35.56 34.77 0 0 0 0 7 7 247 241 W�--G 13A4ocs 0.143 w 4.00 255 0 0 0 0 0 0 0 0 1Ac1om 1.270 w 35.56. 55.21 0 0 0 0 0 .0' 0. 0 �-G 4AS2an' .0.770 w 21.56 19.31 0 0 0 0 0 0 0 0 P 12C-0sw ',1BA30md 0.091 2.55 1.28 72 72 183 92 0 0 0 0 C - 0.032 - :0.90 232 60 50 45 - - 116 56 56 50 130 F' 22A-t01 0.989 - 27.69 0.00 50 7 194 0 56 8 _ 222 0 6 c)AED excursion 39 38 Envelope loss/gain 792 496 747 478 12 a) Infiltration 121 33 t3 b) Roomverltilation 0 0 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 Appliances/other 0 0 0 Subtotal (fines 6 to 13) 913 529 885 516 Less odemal load 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 15 Subtotal Duct loads 913 529 0 885 0 516 32% 49% 289 2589 32% 49% 2880 251 Total room load Air required (cfm) 1202 787 116658 768 59 35 3434 -M -FV- wrightsoft- 145- Right-Suite® Universal 201717.0.14 RSU08101 ...ulck CalcsWocumentsiTHE GRAND CARLTON-1446.mp Cate = MJ8 Front Door faces: 2017-Apr-11 09:29:38 Page 5 -- wrightsoft® Duct System Summary Date: Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., FT PIERCE, FL 34946 Phone:. 772-466-6799. Fax 772-466-6796 Email: OUICKCALCS@AOL,COM For: THE GRAND CARLTON WYNNE DEVELOPMENT, FT. PIERCE, FL Extemal static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.285 in/f00ft 1160 cfm Cooling 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.285 in/100ft 1160 cfm 176 ft Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Cig (Cfm) Design FIR Diam (In) H x W (in) Duct Mall Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h 560 28 14 0.364 4.0 Ox0 VIFx 22.4 115.0 st1 BEDROOM h 4702 232 232 0.360 7.0 OxO VIFx 23.9 115.0 stl = BEDROOM -A h 3327 164 163 0.300 6.0 OxO VIFx 31.8 135.0 st2 BEDROOM-8 h 3327 164 163 0.285 6.0 OxO VIFx 40.6 135.0 sit FOYER h 1202 59 35 0.505 4.0 Ox0 VIFx 4.0 95.0 GREAT/DINING h 3946 195 169 0.300 7.0 OxO VIFx 31.8 135.0 st2 GREAVDINING-A h 3946 195 169 0.300 7.0 OxO VIFx 31.8 135.0 st2 KITCHEN c 3437 21 153 0.379 6.0 OxO VIFx 17.0 115.0 SO LAUNDRY h 846 42 20 0.361 4.0 OxO VIFx 23.3 115.0 st1 M. BATH -A h 768 58 34 0 0 OxO VIFx 0 0 wlc c 174 3 8 0.309 4.0 Ox0 VIFx 27.0 135.0 st2 Trunk Htg Cig Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (In) Material Trunk st2 Peak AVF 721 . 672 0.285 918 12.0 0 x 0 VinlFlx st1 st1 Peak AVF 1043 1091 0.285 1020 14.0 0 x 0 VinlFlx F#I wrlghtsoft• Right -Suite® Universal2017 17.0.14 RSU08101 AOck ...uick Calcs\Documents\THE GRAND CARLTON-1446.mp Cale = MJB Front Door faces: N 2017-Apr-11 09:29:38 Page 1 Name Grille Size (in) Htg (Cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam I (in) H x W I (in) Stud/Joist I Opening (in) Duct Matl Trunk tb1 Ox0 1 1160 1160 0 1 0 0 0 Ox 0 VIFx 9 wrilhttsoft Right-Suite6l Universal 201717.0.14 RSU08101 2017-Apr-1109.29:38 Page 2 '�...ulck CalcslDocuments\THE GRAND CARLTON-1448.mp Calc=MJ8 Front Door faces: N