Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Oakland' Lake Subdivision Loth y p_
5275 Oakland Lake Circl Permit$12 0022, t. Pierce, St. Lucie County, FL
F-i' a1
1% 211010
SCANNE®
Sr Lucie County
As requested, Universal Engineering Sciences, Inc. (LIES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No. I Date I Type of Report
105835-1 I I 01 /17/20191In-Place Density Test Report w/Activity Record
We hope th
the undersi
Attachments (1)
information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
Sincerely,
Universal
Certificate
Sciences, Inc.
)n No. 00000549
z"AM
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
This item has been electronically signed and seated by
Richard E. Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verified on any electronic
copies.
ICC Email: cbugg@nvrinc.com; rhager@nvrinc.com; sign/seal MAIL to ryan homes at 5369 Oakland Lake, Vero Beach, FL 32966
Revised May 2015
UNIV13RSAL
9LIES Reporto: 105835 1 ARC 011719
ENGINEERING SCIENCES on-SiteTime (hrs):0.50
Consultants In: GeotechnicalEngineering • Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services • Materials Testing's Threshold Inspection Travel Time (hrs): 0.25
!
3
Building Code Administrztion, Compliance Inspection & Plan Review Total Time (hrs):0.75
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Client:
Project:
Date of
Activity Record
Ryan Homes
1450 Centrepark Blvd Suite340
West Palm Beach, FL 33401
Oakland Lake Subdivision Lot 61
5275 Oakland Lake Circle Permit 1812-0022, Ft. Pierce, St. Lucie County, FL
Thursday, 17 January, 2019
Technician: Timothy Hughes
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the house pad.
While on s4Ie, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for house
pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records
UN1VLSAL .
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering +Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Pvenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
UEE sect No: 0310.1700251.0040
U E S No:
UES Report No: 105835-1 DT 011719
In -Place Density Test Report
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 61
5275 Oakland Lake Circle Permit 1812-0022, Ft. Pierce, St. Lucie County, FL
Area Tested: house'pad
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 01/17/2019
Lab: ASTM D1557 Modified Proctor
Technician: Timothy Hughes
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not adcir0sc tha rnnriitinn of the L.+.i...., ♦k- J_-.,_
Test
Field Dry
Field
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Density
(PCF)
Moisture
%
%
Compaction
Comments
1
NW comer
of pad
0 to -1 ft
12.00
21143
110.4
6.2
96
(3)
A
2
SW corner
of pad
0 to -1 ft
12.00
21143
110.2
7.9
96
A
3
SE corner
of pad
0 to -1 ft
12.00
21143
109.1
4.6
95
A
4
NE comer
of pad
. 0 to -1 ft
12.00 1
21143
110.1
6.8
96
A
••r 1%0I. yatuIu. u - iuu uI Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
Density
Content
21143
115.0
12.0
(3) Uomments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This test was performed without deviation from ASTM procedures.
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
UNIVERSAL vP anu 3 PV
ENGINEERING SCIENCES
consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection (� rrr111 rrr���
Building Code Administration, compliance Inspection&Plan Review Q
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978 1 7Vk v /Q
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
LRECEIVED
Client: Ryan Homes
1450 Centrepark Blvd Suite 340 AN $ 12019
West Palm Beach, FL 33401Project: Oakland Lake Subdivision Lot 61e County, Permitting
5275 Oakland Lake Circle Permit 1812-0022, Ft. Pierce, St. Lucie County, FL
As requested, Universal Engineering Sciences, Inc. (UES) representative(s) performed construction materials testing and/or
field inspection services on the above project Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
SCANNED
Scope of Work By
Work Order No. Date Type of Report
r 106835.1 1 ow712o19 In•Place Density Test Report wfActivity Record
We hope this information is sufficient for your immediate needs. if you have any questions, please do not hesitate to contact
the undersigned.
Attachments (1)
Sincerely,
Universal Engineering Sciences, Inc.
Certificate of Authorization No. 00000549
' ^'
Richard E.
�? ErN4, - 0
Hoaglin, P.E.
NO. 48796 =
£ 2019.01.31
11:17:15
srATE of , �v`
RoamP .• ��•
-05'00'
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
This item has been electronicallysigned and sealed by
Richard E Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verified on any electronic
copies.
ICC Email: cbugg@nvrine.com; rhager@nvrinacom: signtseal MAIL to ryan homes at 5369 Cakland Lake, Vero Beach, FL 32006
Revised May 2015
820
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building CodeAdministration, Compliance Inspection & Plan Review
UES Project No: 0310.1700251.0040
UES DOCS No:
UES Report No: 105835-1 ARC 011719
On -Site Time (hrs): 0.50
Lab Time (hrs): 0.00
Travel Time (hrs): 0.26
Total Time (hrs): 0.75
we, Rockledge, FL 32955 - P:'321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes.
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
:et: Oakland Lake Subdivision Lot 61
5275 Oakland Lake Circle Permit 1812-0022, Ft. Pierce, St. Lucie County, FL
of Activity: Thursday, 17'January, 2019
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the house pad.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for house
pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
proj ict compaction requirements of 95% of the maximum dry density perASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
820
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechniral Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
.Building Code Administration, Compliance Inspection Ulan Review
Avenue, Rockledge, FL 32956 • P: 321.638.0808 - F: 321.638.0978
Client:
Project:
Area' Tested:
Type of Test:
Technician:
Requirements:
In -Place Density Test Renort
LIES Project No: 0310.1700251.0040
LIES DOCS No:
LIES Report No: 105835-1 DT 011719
Ryan Homes JAN 31 2019 1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Oakland Lake Subdivision Lot 61 ST• Lucie County, perm
5275 Oakland Lake Circle Permit 1812-0022, Ft. Pierce, St. Lucie County, FL
house pad .
Field: ASTM D-6938 Nuclear Gauge Method
Lab: ASTM D1557 Modified Proctor
Timothy Hughes
Date of Test: 01/17/2019
95% of Proctor maximum dry density. These tests apply to the fill andfor surficial sail conditions
nni., .nA An nM �rirlraec tho ennrlitinn of the nndprIvina soils below the tested deDths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
°%
%
Compaction
Comments
(3)
1
NW corner of pad
0 to -1 ft
12.00
21143
110.4
6.2
96
A
2
SW comer of pad
0 to -1 ft
12.00
21143
110.2
7.9
96
A
3
SE comer of pad
0 to -1 ft
12.00
21143
109.1
4.6
95
A
4
NE corner of pad
0 to -1 ft
12.00
21143
110.1
1 6.8
96
A
(1) , Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21143
115.0
12.0
ts) commems Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This test was performed without deviation from ASTMprocedures.
This report shall not be reproduced, except in full, without the written approval 0f Universal Engineering Sciences.