HomeMy WebLinkAboutPLANSGeneral Notes A. CONCRETE & FOUNDATION DESIGN: 1. ALL CONCRETE GRADE BEAMS AND FOOTINGS SHALL BE 3000 PSI MINIMUM. 2. ALL CONCRETE FILLED SUPPORTED SLABS SHALL BE 2500 PSI MINIMUM, 3 I/2" NOMINAL THICKNESS. 3. FIBERMESH (3/4" PER CUBIC YARD MIN.) MEETING APPROPRIATE ACI AND ASTM REQUIREMENTS MAY BE USED IN LIEU OF WELDED WIRE MESH 4. ALL SLABS ON GRADE SHALL BE 4" THICK WITH FIBERMESH, 5. ALL REINFORCING SHALL CONFORM TO ASTM A615, BE GRADE 60 (60 KSI MIN.) DEFORMED BARS, #3 BARS MAY BE GRADE 40. 6. ALL OVER POUR CONCRETE FILLED SUPPORTED SLABS SHALL BE 3000 PSI MIN., 2" MINIMUM. THICKNESS. 7. SOIL BEARING PRESSURE SHALL BE A MINIMUM OF 1500 PSF. 8, THE CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING: OPC (PORTLAND CEMENT TYPE 1,-ASTM C 150). AGGREGATES - #6 STONE, ASTM C 33 SIZE NO.67 LESS THAN 3/4". AIR ENTRAINING +/-1%- ASTbI C 260. WATER REDUCING AGENT - ASTM C 494. CLEAN POTABLE WATER OTHER ADMIXTURES SHALL NOT BE PERMITTED. 9. METAL WELDED WIRE SHALL CONFORM TO ASTM A 185. 10. PREPARE & PLACE CONCRETE ACCORDING TO AMERICAN CONCRETE INSTITUTE MANUAL STANDARD PRACTICE, PART 1, 2, & 3 ALONG WITH HOT WEATHER CONDITIONS RECOMMENDATIONS. 11. IF UTILIZING EXISTING CONCRETE FOR FOUNDATION, CONCRETE SHALL BE A MINIMUM OF 4" IN THICKNESS, VISIBLY FREE OF ANY STRUCTURAL EXCESSIVE CRACKING, SPALLING OR OTHER DETERIORATION. B. MASONRY- (.CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR s.ALL MORTAR SHALL BE OF TYPE M OR S. 3. ALL GROUT SHALL BE 2000 PSI MINBNUM AND HAVE MAXIvIUM COARSE AGGREGATE SIZE OF 3/8". 4.PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS Y-0" IN HEIGHT. C. ALUMIlVIIM: 1. ALL STRUCTURAL ALUMINUM SHALL CONFORM TO THE MINIMUM REQUIREMENTS OF 6005-T5 FOR ALLOY WITH A MINIMUM THICKNESS OF 0.040" FOR SUPPORTING MEMBERS. 2. WHERE HICK PLATES ARE USED A MINMIUM THICKNESS OF 0.024" SHALL APPLY. 3. STRUCTURAL ALUMINUM DESIGN CONFORMS TO "PART 1-A - SPECIFICATIONS FOR ALUMINUM STRUCTURES - ALLOWABLE STRESS DESIGN" OR "PART 1-B - SPECIFICATIONS FOR ALUMINUM STRUCTURES - BUILDING LOAD AND RESISTANCE FACTOR DESIGN" OF THE ALUMINUM DESIGN MANUAL PREPARED BY THE ALUMINUM ASSOCIATION, INC.WASHINGTON D.C. THE FLORIDA BUILDING CODE 61h EDITION ( CHAPTER 16 STRUCTURAL DESIGN & CHAPTER 20 ALUMINUM). 4. WHERE ALUMINUM COMES INTO CONTACT WITH STEEL, OR PRESSURE TREATED LUMBER PROVIDE DIELECTRIC SEPARATION. 5. ALUMINUM MEMBERS SHALL BE STITCHED WITH NO LESS THAN 910 SMS 6" FROM THE ENDS AND 12" ON CENTER IF USING #12 SPACING MAY BE 24" ON CENTER. 6. VINYL AND ACRYLIC PANELS SHALL BE REMOVABLE. THEY SHALL BE IDENTIFIED WITH A DECAL ESSENTIALLY STATING "REMOVABLE PANEL SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH" , DECAL SHALL BE PLACED SO IT IS VISIBLE WHEN PANEL IS INSTALLED. 7. I"X2"X0.045" NON-STRUCTURAL MEMBERS SHALL BE ATTACHED TO HOST WITH I/4"0 X I-3/4" EMBEDMENT & 24" O.C. MASONRY SCREW FOR CONCRETE & EQUIVALENT SIZE WOOD SCREW WHEN IN WOOD & #10X 1/2" EMBEDMENT SMS OR TEK SCREWS IN ALUMINUM MEMBERS TYPICAL. D. FASTENERS: 1. ALL LAG BOLTS SHALL CONFORM TO STAINLESS STEEL TYPE 30018-8, WITH STANDARD FLAT WASHER UNLESS MANUFACTURER GALVANIZES BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD. 2. HEX BOLTS HAS TO B� ,.:.:M A 325, PLATED WITH STANDARD ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED - --FLAT-WASHERS-AND-NUTS. HOME. BAWL, 3. ALL CONCRETE SCREWS SHALL BE, STEPSON, APPROVED TAPCON, REDHEAD, DYNABOLT, PORTECT OR APPROVED 2. E ENCLOSURE CONTAINS A SWIMMING BEG POOL OR SPA. THE ENCLOSURE SHALL COMELY WITH RESIDENTIAL S WTMMING [/ / ^�� EQUAL. BARRIER REQUIREMENTS OF THE FLORIDA BUILDING CODE 60, f✓ ell, � I ��GI 4. ALL METAL TIES AND ASSOCIAIBD ACCESSORIES SHALL BE EDITION R 4501.17IN ITS ENTIRETY. �_1 ? HOT DIPPED GALVANIZED. 3. DOOR LOCATIONS MAY BE DETERMINED IN THE FIELD BY ST. LUC1E COUNTY BUILbIND DIV N 5. ALL LAG BOLTS SHALL HAVE A MINIMUM EMBEDMENT OF 8X coNTRACTOR, REVIEWED FOR COMPLIANCE BOLT DIAMETER INTO STRUCTURAL FRAMING(G=.42 MIN.). 4. IF PAVERS ARE UNDER ALUMINUM MEMBERS THEY SHALL REVIE D I 6. LAG BOLTS AND SCREWS INTO WOOD FRAMING SHALL BE HAVE. EPDXY ADHESIVE TO CONCRETE OR IF USING GROUT, DATE PROVIDED WITH PILOT HOLES HAVING A DIAMETER NOT ENSURE BONDING AGENT IS USED FIRST. GREATER THAN 70 PERCENT OF THE THREAD DIAMETER OF 5. SCREENING MATERIAL SHALL BE I8X14X0.0I3 OR PLANS AND PERMIT MUST BE KEPT OB THE BOLT OR SCREW. -ALL LAG BOLTS AND SCREWS SHALL BE INSERTED IN PILOT HOLES BY TURNIN EQUIVALENT DENSITY SCREEN MESH ONLY UNLESS NOTED GS SITE OR NO INSPECTION(S) WILL BE MADE G AND UNDER NO ON DRANIN -2. CIRCUMSTANCES BY DRIVING WITH A HAMMER 6. PLEASE NOTE: 2x2(tyP) DIAGONAL BRACING SHALL BE 7. ALL EXPANSION ANCHORS SHALL BE DESIGNED IN 2"X2"X0.055" MATERIAL, UNLESS OTHERWISE NOTED ON S-2. ACCORDANCE WITH THE SPECIFIC MANUFACTURER'S REQUIREMENTS AND ALLOWABLE LOADS AND SHALL ONLY FILE COPY BE APPLIED IN CONDITIONS ACCEPTABLE TO MANUFACTURER FASTENERS SHALL BE A MINIMUM OF SAE GRADE 95 OR BETTER ZINC PLATED. 8. ALL FASTENERS CONNECTING ALUMINUM COMPONENTS OR PRESSURE TREATED LUMBER ARE STAINLESS STEEL TYPE 300 18-8, UNLESS MANUFACTURER GALVANIZED BOLTS SPECIFIES -DESIGN DATA: FOR USE WITH ACQ PRESSURE TREATED WOOD, OR 1. ULTIMATE DESIGN WIND SPEED Vu11, (3 SECOND GUST): ISO MPH OTHERWISE NOTED ON PLANS. NOMINAL DESIGN WIND SPEED Vmd: 116 MPH 9. ALL FASTENERS SHALL COMPLY WITH ASTM A153. 2. RISK CATEGORY: 1 10. ALL CONNECTORS SHALL COMPLY WITH ASTM A653 3. WIND EXPOSURE; B CLASS G-185. 4. WIND LOADS: 11. FOR SMS, THE MINIMUM CENTER -TO -CENTER SPACING SCREEN ROOF: 9 PSF SHALL BE 3/4" AND MINIMUM CENTER -TO -EDGE SHALL BE 1/2" SCREEN WALLS: 31 PSF UNLESS NOTED OTHER WISE. SOLID ROOF (SCREEN WALL): N/A COMPONENTS AND CLADDING LOAD: N/A E. REFERENCE STANDARDS: ASTME 119 ASTM E 1300 CURRENT ASCE 7 CURRENT ALUMINUM DESIGN MANUAL -AA ASM35, AND SPEC. FOR ALUMINUM PART I -A, & I-B ASTM C94 ASTM C150 ASTM C33 ASTM C260 ASTM C494 ASTM A615 ASTM A185 FLORIDA BUILDING CODE 611, EDITION (CHAPTERS 16,20 & 23). F. ABBREVIATIONS: THE FOLLOWING LIST OF ABBREVIATIONS IS NOT INTENDED TO REPRESENT ALL THOSE USED ON THESE DRAWINGS, BUT TO SUPPLEMENT THE MORE COMMON ABBREVIATIONS. 1. TYP -TYPICAL 2. SIM--SIMILAR 3. UON-UNLESS OTHERWISE NOTED 4. CONT - CONTINUOUS 5. VIF-VERIFY IN FIELD G. RESPONSIBELITY- 1. ALL SITE WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDINANCES, ETC. 2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND DETAILS, NOTIFYING ENGINEER OF ANY DISCREPANCIES BETWEEN DRAWINGS, FABRICATED ITEMS, OR ACTUAL FIELD CONDITIONS, 3. THESE DRAWINGS REPRESENT THE ACCEPTABILITY OF THE 'SUNROOM' ROOM ADDITION ELEMENTS AS PROVIDED BY THE CONTRACTOR. 4. ALL DETAILS ON THESE DRAWINGS ARE ENGINEERED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND MANUFACTURER. 5. ANY DETAILS NOT SHOWN ARE TO BE ENGINEERED BY A LICENSED P.E. IN ACCORDANCE WITH STANDARD ENGINEERING PRACTICES. I-L MISCELLANEOUS: 1. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPARATE 4TH WALL SUPPORT SYSTEM MUST BE ENGINEERED SO THAT NO 5. THIS STRUCTURE COMPLIES WITH FBCE. 1103.2 AND THEREFORE HAS NO ADVERSE AFFECT ON THE EXISTING STRUCTURE. 6. FACTOR APPLIED TO SCREEN WIND LOADS FOR 18X14X0.013 OR EQUIVALENT DENSITY SCREEN MESH: 0.88 7. FACTOR APPLIED TO SCREEN WIND LOADS FOR ALLOWABLE STRESS DESIGN: 0.6 S. LIVE LOAD: 3001b. VERTICAL DOWNLOAD ON PRIMARY SCREEN ENCLOSURE MEMBERS. 2001b. VERTICAL DOWNLOAD ON SCREEN ENCLOSURE PURLINS. 8. EXISTING SLAB AND OR FOOTING MEETS THE REQUIREMENTS TO RESIST THE UPLOADS FOR THE PROPOSED STRUCTURE, 9. SCREEN ROOF TYPE: I2 MANSARD/ TRANSVERSE GABLE 10. SOLIDROOFTYPR- MIA ALUMINUM STRUCTURAL MEMBERS SCANNED BY St Lucie County HOLLOW SECTIONS I THESE PLANS AND ALL PROPOSED WORK 2 x 2: ---------------------------------------2" x 2" x 0.044" ARE SUBJECT TO ANY CORRECTIONS 2 x 3: ---------------------------------------2" x 3" x 0.050" REQUIRED BY FIELD INSPECTORS THAT 2 x 4: ---------------------------------------2" x 4" x 0.050" MAY BE NECESSARY IN ORDER TO 2 x 5: ---------------------------------------2" x S" x 0.050" COMPLY WITH ALL APPLICABLE CODES. 3 x 3: --------------------------------------- 3"x 3" x 0.12S" OPEN BACK SECTIONS 1 x 2:---------------------------------------1"x 2" x 0.040„ 1 x 3:----------- ----1" x 3" x 0.045" SNAP SECTIONS 2 x 2 SMS-----------------------------------2" x 2" x 0.045" 2 x 3 SMS:---------------------------------2" x 3" x 0.072„ 2 x 4 SMS+-------------------------------- V x 4" x 0.045" 3 x 3 SMS:--------------------------------- 3" x 3" x 0.090" SELF MATING (SMB 2 x 4 SMB:---------------------- 2" x 4" x 0.044" x 0.100" 2 x 5 SMB:--------------------- 2" x 5" x 0.050"x 0.118" 2 x 6 SMB:---------------------- 2"x 6" x 0.050" x 0.120" 2 x 7 SMB:------------- --------- 2" x 7" x 0,057" x 0.120" 2 x 8 SMBr--------------------- 2" x B" x 0.072" x 0.224" 2 x 9 SMB:------------- •-------- 2" x 9" x 0.072" x 0.224" 2 x 10 SMB;------------------ 2" x 10" x 0.092"x 0.374" TUBE SECTIONS 2 x 2:-------------------------------------2" x 2" x 0.090„ CONCEALED FASTENERS OR ATTACHMENTS ARE THE RESPONSIBILITY OF THE CONTRACTOR OR RECORD RECEIVED DEC 03 aJi8 ST. LUcle county, PermfEEitiii ENGINEER OF RECORD: David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson P FLORIDA LICENSE: 38654 Mark R. Dunn P.E. FLORIDA LICENSE: 73968 Joel Falardeau P.E. 17LORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineerir Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph# (813)788-5314 Fax# 1-(866)824-7894 E-mail-erb @tbcplans,com W ebsite-W Ww,tbcplans.conn C.O,A: #29054 DATE: 10/29/2018 DRAWN BY: TLK REVISION: DATE: RO 1 RO 2 RO 3 RO 4 Job# 18111344 PROJECT ADDRESS: 0 GRAND OAK AV PIERCE, FL 34981 "ONTRACTOR: K & S INDUSTRIES, INC. 1379 SW SILTMORE ST. PORT ST LUCIE, FL 34983 NOTES S-1 SHALL NOT BE REPRODUCED IN I I I 2X2DJ I I 0 s-a 2X5SMB I 2X2DJCL _ N 2X5SMB I I I I/ 2X5SMB _ y a / I N N / / / 1X2 I 2X8 SMB CB W/ KICK PLATE OVER THIS AREA, `KICK, PLATE TO ATTACH / TO TIE BEAM. i A I S-3 2X2(typ 2X2(typ 2X2(typ) ZX2(typ) 2X2(typ). s-3 N CN d N 2X2(typ) 2X2(typ) 2X2(typ) 2X2(typ) N\X2(typ M � 07 M m N N N 2X2(typ 2X2(typ) I 2X2(typ) � S-3 2X2 i �— -f----- ----7` <----r-----I------ram C3 I In IRL I D] —�\ I D7 Ina D7ICA4 o in In In In In O -I X I N N N X N X LO N S-a X N N O 0 2X2(tyP) 2X tYP) 2X2( p) 2X2(typ) 1X2 11YP) S-4 \LyN/ S-4 I / I 1 I / I I/ I I I 2X5SMB I I I f 2X5SMB I I I I I 04 I j X 2X5SMB \ I \ I \I \I \I 2X5SMB /1X \ N X N -ell`. ® U= 0- ,D� a; c` o m� �T,yTFOF Off/ r cp ••> le/0 DA _' <r ENGINEER OF RECORD: David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson P. FLORIDA LICENSE: 38654 Mark R. Dunn P.E. FLORIDA LICENSE: 73968 Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph# (813)788-5314 Fax# 1-(866)824.7894 E-mail-erb @ fbcplans.com W ebs ite-www. fbcplans.com C.O,A. #29054 DATE: 10/29/2018 DRAWN BY: TLK REVISION: DATE: R01 RO 2 RO 3 RO 4 PROJECT ADDRESS: )0 GRAND OAK AV PIERCE, FL 34981 ;ONTRACTOR: K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 34983 FLOOR PLAN S2 Bn ALUMINUM GUSSET 2"x_PURLINS (SEEA-1 FOR SIZE)ATTACHED TO BEAM W/MIN (4) #10 x 1'/," NA` _ �T Sry a • � � • • • • • •\ f y)� NOTES: 1 "N" NUMBER OF SCREWS IN ANY BEAM "B" "N" "S1" "S2" "ST' "S4" 2X4 12 4 3/4" 1 " 16" 3.75" 2X5 12 4 3/4" 1 " 16" 4.75" 2X6 16 5 1" 14" 19" 5.75" 2X7 20 6 1" 1 22" 6.75" 2X8 24 7 1" 1 " 23" 7.75" 2X9 24 7 1" 1-j" 23" 8.75" 2X10 1 28 1 8 1" 1 1j" 24" 19.75" EAVE DIRECTION. 2. TOTAL NUMBER OF SCREWSPERJOINT EQUALS 4 TIMES "B". 3• PLATE WIDTH SHALL BE DETERMINED FROM ANGLE OF BEAM AND MIN. SPACE REQUIRED. 4. GUSSET PLATES MAY BE INTERNAL OR EXTERNAL. 5. INTERNAL SCREWS FOR PURLIN CONNECTION MAY BE INCLUDED IN TOTAL NUMBER OF SCREWS. 6. GABLE SPLICE WILL HAVE THE SAME PATTERN. D \ BEAM SPLICE GUSSET DETAIL TYPICAL S'3 SCALE:NTS (1) 3/R'O THRU BOLT W/ NYLON LOCKING NUT OR THREAD LOCKING MATERIALAPPLIED 1" x 2" x 0.045" OPEN BACK W/ (2)#IOX 2" THRU SCREW BOSS BEAM 10 FLAT sl.oeeEDeD 0 2"x2"xy"XALUMINUM ANGLEW/ (4)#12X3/4"SMS INTO BEAM EA SIDE OPTIONAL 2"X2"XO.062" RECEIVING CHANNELW/ (2) #IOX3/4" EA SIDE TO COVER EXPOSED BEAM r•1 (2) 3/8" x Z" MIN, EMBEDMENT LAG SCR BEAM & (1) @ 12" O.C, THE HOST STRUCTURE SHALL HAVE AT LEAST A 2"X4" FASCIA AND ROOF TRUSS SYSTEM. CONTRACTOR SHALL VERIFY THIS AND IF SMALLER -CONTRACTOR SHALL BRING STRUCTURE UP TO A 2"X4" FASCIA AND ENSURE LEES THAN A 2'-0' OVERHANG. (� ROOF BEAMS TO FASCIA ATTACHMENT DETAIL S'3 N.T.S. HINGELOCATION (2) #1OX3' SMS CROSS SCREWING BRACE TO BEAM OR 2" x 2" EXTRUSION EAVE MEMBER (.125" BACKING 2" x 2" EXTRUSION PLATE USED) Q U ROOF 2"x'2"x.125" FLAT BAR (typ) HN104KIWAODRI HINGE NOTES: 1. HINGES SHALL BE ATTACHED TO STRUCTURE W/ (3) #10 x 5/8" SMS MINIMUM. 2. DOOR SHALL BE ATTACHED TO ENCLOSURE w/(2) HINGES MINIMUM. 3. HINGES SHALL BE ATTACHED TO DOOR WITH (3)#10 x 5/8" SMS. FASTENA 1" x 2" x 0.044" TO UPRIGHT W/#12 x 1" SMS O 12" O.C. AND WITHIN 3" FROM END OF THE UPRIGHT. •� ROOF BRACING CONNECTION DETAIL S'J SCALE: N,7.S, PICAL SCREEN DOOR CONNECTION DETAIL S' TY3 SCALE: NTS UPRIGHT WEB LAPPED OVER PURLIN W/ (2) #12X3/4" SMS EACH SIDE THRU UPRIGHT& PURLIN 2"X2"MEMBER ATTACHED TO UPRIGHT W/ (3) 01OX3-1/2" SMS INTO SCREW BOSS 1'X2"XO.045"OPEN BACK / \—NOTCH Porn ATTACHED TO PURLIN W/ (2)J AS NEEDED #10XI-1/2" SMS INTO SCREW BOSS 1"X270.045" OPEN BACK ATTACHED TO 2'X2'XD.045' UPRIGHT SAVE RAIL MEMBER 91OXI-1/2" SMS .. C@ 24" O•C C SLOPED OR FLAT PURLIN UPRIGHT LAP DETAIL S'3 SCALE: NTS BEAM SCREWS 2"X4"SMB 6 2"X5"SMB 6 2"X6"SMB 8 2"X7"SMB 8 2"X81SMB 10 2"X9"SMB 10 2"X10"SMB 12 FOR SLOPED BEAMS, MAINTAIN ALL SCREW SPACING FROM EDGE OF BEAM 2"x 2" EAVE RAIL SECTION (UNLESS OTHERWISE SHOWN ON S-2) - ATTACHED TO BEAM w/� (3) SOX 2" SMS INTO SCREW BOSS 1' X 2" OPEN BACK EAVE RAILATTACHED TO , #10xl%"SMSINTO SCREW BOSS \_2" NOTCH OF INSIDE BEAM #10 X 1 Y,," SMS 24" C/ TO SLIDE OVER UPRIGHT 914X 3/4" SCREWS (SEE TABLE ABOVE) • (MIN) UPRIGHT [--A 1� \ UPRIGHT TO BEAMCONNECTION -ALL WIND ZONES S-3 SCALE: NTS 0 FOR UPRIGHT i i Ooil ;;;z 9 oil i ENGINEER OF RECORD: David W. Smith P.E. FLORIDA LICENSE:53608 Thomas L. Hanson P.E FLORIDA LICENSE: 38654 Mark R. Dunn P.E. FLORIDA LICENSE: 73968 Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineerir Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph# (813)788-5314 Fax# 1-(E166)824-7894 E-mall-erb@fbcplans.com W ebs ite-www. fbcplans. corn C.OA. #29054 DATE: 10/29/2018 DRAWN BY: TLK REVISION: DATE: RO 1 R02 RO 3 RO 4 Job# 1$ 1113 44 PROJECT ADDRESS: )0 GRAND OAK AV PIERCE, FL 34981 K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 34983 DETAILS S-3 THIS SHALL NOT BE REPRODUCED IN WHOLE OR IN PARTWTHOUT EXPRESSED WRITTEN PERMISSION OF TRAC DESIGN, 5" OR 7"X 6" WIDTH X 0.250" EXTRUDED GUTTER BRACKET @ EA. BEAM W/ (4) #12 X 3/4" SMS INTO GUTTER LIP 1"x2"x 0.045"OPEN BACK W/ (4)#14X 1-1/2- INTO GUTTER & (1)#14X� 1-1/2" @ 24" O.C. 2" SMS INTO BEAM ON EA SIDE EA LEG 2"X2"XO.062" RECEIVING CHANNEL W/ (2) #lOX 3/4" EA SIDE TO COVER EXPOSED BEAM CARRIER BEAM FLAT OR SLOPPED (SEE SHEET S-2 FOR SIZE) STITCHED TQ GUTTER W/ (2) #12X3/4" SMS @ 24" D.C. OPTIONAL: V12"OPEN BACK ATTACHED TO HOST W/ (1) 1/4"0 CONCRETE SCREW OR LAG WITHIN 6" OF BEAM & @ 24" O.C. MAX p BETWEEN BEAMS F Lam[F-... O N � ti (B) - 1/4" 0 CONCRETE SCREW W/ 1-1/2" EMBEDMENT INTO MASONRY (1.1/2" MIN. SPACING OR (B)-1/4" 0 X 2" LAG SCREWS INTO WOOD (1" MIN SPACING) (TYP 2 LOCATIONS) NOTE: 2X4 SMB BEAM ONLY REQUIRES 4"_ WIDTH GUTTER BRACKET W/ (2) 3/8" LAGS (4) 3/8" LAG SCREWS @ 1.1/2" SPACING @ EA. GUTTER BRACKET & @ 12" O.C. MAX- MIN EMBEDMENT SHALL BE 2" SUPER GUTTER (5" OR 7") (4) #12 x 3/4" SMS -INTO CARRIER BEAM EA SIDE THE HOST STRUCTURE SHALL HAVE AT LEAST A 2"X4" FASCIA AND ROOF TRUSS SYSTEM. CONTRACTOR SHALL VERIFY THIS AND IF SMALLER -CONTRACTOR SHALL BRING STRUCTURE UP TO A 2"X4" FASCIA AND ENSURE LESS THAN A T-O" OVERHANG. (6)- #14 X 3/4"SMS ATTACHING ANGLE TO BEAM EACH SIDE (1" MIN. SPACING) i i i i O � SLOPED OR FLAT ROOF BEAM (SEE SHEET S-2 FOR SIZE) BEAM ,B" NOTES: ��2"X2"X0.125"ANGLE 1. THE MINIMUM EDGE EA. SIDE OF BEAM 2X4 1 DISTANCE IS 3" FOR MASONRY :X:UST;ING HOST STRUCTURE 2x5 2 STRUCTURES. (CONCRETE, GROUT FILLED 2, IPA RECEIVING CHANNEL IS CMUORWOOD) 2X6 2 USED, USE TWICE THE NUMBER "B" ANCHORS INTO THE HOST STRUCTURE. ALL MINIMUM SPACING SHALL BE APPLICABLE. AZ BEAM TO HOST TO CONNECTION DETAIL 2x7 3 2x8 3 2x9 3 2X1D 4 S-4 SCALE:NTS UPRIGHT 4,. E A a SECONDARY ANGLE MIN NA^"°", _ 0.125"THICK (NOT -- -- -� ; - � T016 .- (4) #10 X 3/4" SMS FASTENING SECONDARY REQUIRED FOR 2X3 " %� " C Sj- ANGLETOCOLUMN MEMBER) o -c1 ° "t� "9%-F EACH SIDE) PRIMARY 2"X2" ®tC1 OF 9 cAiD,4 OPTION#1 I (B)- CONCRETE SCREW I X0.125°ANGLE (2]#10X3/4"SMS FASTENING B® tT� ° ° d°� O�,F D x 136" SMS INTO I OPTION #2 ANCHOR INTO SECONDARY ANGLE(TYP EACH SIDE) (SEE I O COLUMN TO PRIMARY ANGLE (TYP EACH SIDE) /I '� ENC ��� SCREW BOSSES TABLE) O I p 1"X2"BASE MEMBER ('IYP EACH SIDE) (/j ANCHORSPA (MIN) (TYP)(SEE TABU) (1) - CONCRETE SCREW (SEE 'd TABLE) ANCHOR INTO PRIMARY PROFESSIONA ENG ER SEAL 2"XZ"OR2"X3"_j I 0,062"ALUMINUM INTERNAL OR MEMBER EXTERNAL RECEIVING CHANNEL I X3/4NTOIN I BEAM OR UPRIGHT, (2) 914X 3/4" EA. LEG INTO GIRT OR PURLIN- (0.062" ANGLE CLIPS w/ (2) #14x3/4" SMS EA LEG) UPRIGHT OR BEAM -SNAP OR SELF MATING OR HOLLOW �,� / 11 PURLIN OR GIRT TO BEAM OR POST DETAIL S-4 SCALE: NTS DOUBLE 4" NOMINAL 318" 0 x 3" MASONRY ANCHOR (MIN 3-3/4" 4" 1-1/2" X 5-1/2" ALUMINUM STRAP W/ (2) 3/8 "0 X 3" MASONRY ANCHOR TOP OP CONCRET Column Size 1/4"& 3/8" 0 Concrete Screw Anchor g Min.Spa q 4- 4 2x - 2 4 WMEW 2 OPTION # 1- A-36 STEEL CLIP MAY BY PLACED ON TOP OR SIDE OF DECK W/ (213/8"X 3" SLEEVE 2500 PSI CONCRETE W/ OPTION 01 `WELDED W (4"SLAe ONLY) FIBERMESH 1.125" STAINLESS STEELCABLE 2500PSICONCRETEW/ TOP of rWELDED WIRE OR Q1. O d ne OPTION #2 WITH FOOTING) ENGINEER OF RECORD. ANGLE AND @ 1/4" 0 CONCRETE 3" (MIN) SCREWANCHOR@ David W. Smith P.E. 24"0.C.BETWEEN COLUMNS FLORIDA LICENSE: 53608 (TYP EACH SIDE) NOTES: Thomas L. Hanson P 1. NUMBER OF ANCHORS "B"ISEACH SIDE INTO THE SECONDARY LICENSE: 38654 ANGLE AND DOES NOT INCLUDE THE ANCHOR INTO THE 1X2. FLORIDA 2.MINIMUM EMBEDMENT OF ANCHORS INTO CONCRETE FOOTING Mark R. Dunn P.E. SHALL BE 2-3/4" AT AT ALL UPRIGHT LOCATIONS. ALL SCREW LENGTHS AT UPRIGHT CONNECTIONS SHALL BE OF SUFFICIENT FLORIDA LICENSE: 73968 LENGTH FOR REQUIRED EMBEDMENT INTO CONCRETE FOOTING 1 T; 1 oel Falardeau P.E. WHEN A PAVER DECK IS PRESENT. 3. CONCRETE SCREW ANCHOR DESIGNS ARE BASED ON THOSE LISTED FLORIDA LICENSE: 70667 FA TENERS, OTHER BRAND& TYPE SHALL BE APPROVED Erik Stuart P.E. BY ENGINE 4.2X3W/1X2 CORNERPOST SHALL REQUIRE SAME BASE FLORIDA LICENSE: 77605 CONNECTIONS AS 2X4 SHOWN IN TABLE. G�2"x3" OR LARGER UPRIGHT TO CONCRETE W/WO PAVERDETAILS S 4 SCALE: NTS NOTE: WHEN USING OPTION #2 CONNECTION CABLE MUST BE L WITHIN 6" OF CORNER OR 7T PRIMARY MEMBER. T1 1"X2"X1/8"ANGLE (4) #12 X 3/4" SMS O O (TYP TOP AND SIDE) o �e DUL STAINLESS CABLE 1L STEEL CABLE 3/8" WELDED STAINLESS STEEL EYE BOLT (8) #14 X 3/4 SMS View 1" 0 (MIN) WASHER BENEATH NUT � S. FBC Plans & Engineerir Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph# (813)788-5314 Fax# 1-(B66)824.7894 E-mail-erb@fbcplans,com W ebs ite-www.fbcplans. com C.O.A.429054 1/8-ALUMINUM PLATE @ 45° DATE: 10/29/2018 ANGLE W/ 1" BREAK @ 90° W DRAWN BY: TLK 5/16° EYE BOLT w/LOCKNUT& REVISION: DATE: WASHER EA SID #14X3/4SM RO1 " O.C. RO 2 RO 3 OPTION #3 RO4 Top View I' 3/8" O ADJUSTABLE EYE II BOLT FOR CABLE TENSION OPTION #2 . 1/8"0 STAINLESS I STEEL CABLE PERIMETER FRAMIN 2"XZ"X 1/8" EXTRUDED ANGLE ON 45°ANGLE Side View OPTION #1 J2 CABLE CONNECTION AT CORNER S_4 SCALE: NTS PROJECT ADDRESS: )0 GRAND OAK AV PIERCE, FL 34981 :ONTRACTOR: K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 34983 DETAILS S-4