Loading...
HomeMy WebLinkAboutELEVATOR PAPERWORKJ SI®ENTIAL LEVAT®RS Minimum Requirements Feb Luxury Lift Traction Elevators°�PLUCi13 °Unfy 1. 52" x 57" clear inside hoistway dimensions when using an accordion style solid gate. 2. 8" minimum pit built to withstand a 5,100 lb. load. 3. 102" clear hoistway overhead for Std. cab. 114" clear hoistway overhead for 8'-0" cab.. 4. 12" minimum return on rail side wall. If this cannot be obtained, contact office for approval. 5. If masonry construction, rail wall needs to be poured 6. Rail side blocking for wood frame hoistways must be two 2 x 12's sandwiched together, running vertically the entire length of the hoistway 12" on center of either side of the rail wall centerline. (Please see rail wall structural drawing.) 7. Legal machinery space with access doors. (Please see access door drawing.) 2DResident1al;'D`r,;=Crawfordville, FL 32327 Toll,Free (860) 8k-2004 Fax (850) 926-5319 WWW.ResidentialElevators. ccm r-�— . I IM RXMRU�L L C I AAF=3379 ARM11105 APPROVED ra. --"Bmrr APPROVED AS CORRECTED This review is 00), Mi' C'X;'i C - project document-.. GoirrEcl,: S 'r M.T1.1-11PIL r this rzvlcvr do no! fC'W:.' iratud-approval of an assembly Of tractor is responsible for Diffrel-S." 10 F.'-- job ge; Iffantgoon filat pertains S01,31Y tc lnh ir means, methoas,technicivas, sequencasand ton: coordination of the work of ali other trades: and f3f P in a safe and satisfactory MaUff. DAME 12 1 vFJ 14 a,.. pM (r RAILS SEE HOR AD 06 RH RAIL ACCESSDOOR OPPOSITE HALL DOOR Elevating your standard of living LH RAIL ACCESS DOOR OPPOSITE HALL DOOR SEE HOR AD 04 RAILS HALL DOOR cm.) Qt RECOMMENDED CLEARANCE FOR ACCESS TO MOTOR/ GEARBOX WITH ACCESS DOOR IN REAR OF SHAFT. 2Q RECOMMENDED MIN. SHAFT DEPTH FOR ACCESS DOOR IN REAR OF SHAFT. LUXURY LIFT LLT TRACTION SEE HOR AD 05 REAR RAIL ACCESS DOOR RIGHT ADJACENT WALL SEE HOR AD 08 REAR RAIL ACCESS DOOR LEFTADJACENT WALL ACCESS DOOR BY GENERAL CONTRACTOR FINISHED 52" — SHAFT (48.10 MIN.) MA70MUM JO PLATFORM 3C" MK) 5" - NOW — L LLLt� 'ice( ffI i�i L a' 5m—mi� N / c STATiONQV 4" 36 12" CONSULT FACTORY IF LARGER G.P. 6719N0 ADDLLTDESIMTION fiR F.P. Qa081t1 CHANGE M9L SKAFT GP. M.C. 04M11M ADD20-WK==ONCLE4RANCE G.P. 1WMM9 RMUCEWaoM 10 NOTES: O IF PLATFORM SIZE IS REDUCED. THEN THE BLOCIaNG IS TO BE 5 12" POSITIONED SUCH THAT IT IS CENTERED ONTHE PLATFORM. (PLATFORM DEPTH 12) +2" = CENTERLINE OF RAIL BLOCIONG OFF OF INSIDE FRONT WALL (MIN. 28" DIMENSION) NJ _2i124 L 'L. N`cC N N *�344! _2x12bb N P R STANDARD HOBSTWAY PLAN STALE- yr=1• NOTE ALL DIMENSIONS ARE APPROXIMATE LUXURY LIFT- TMENfORiAATWNWMAQEDXEiE1NI550Lp.Y04MED RYRESIOENML a ATORS, NCA REPROLLCTIONN LLT TRACTION PAREORASAWH EWR =WidTTal PERMSSIDNR RESRENR E"ATORS.WC MSIRI YPROMBR O CARTO WALL(C11N) DIMENSION IS 340 MN. O3 HOISiWAYDOORS AND FRAMES TOBEINSTALLED INA2'xe WALL CONSTRUCTION OR RECESSED INTO A DEEPER WALL CONSTRUCTCN TO EQUATE TOA2'x4" WALL. THIS IS REQUIRED TO COMPLY WITH 3' x S RULE. ® HOISTWAYDOORSTOBESOLm CORE(BYOTHERSj O CLEAR CAB DIMENSIONS BASED ON A 3W FLAT WALL CABDESIGN. PICTURE FRAMEAND FRAME /PANEL CABS - REDUCE CLEAR INSIDE WIDTH BY 1-10 AND CLEAR INSIDE DEPTH BY 317. © MIN- CLEARANCE TO ALLOW FOR MOTOR/ BRAICFJ GEARBOX Muafing your standard ofliDing 950#, RH RAIL, IN -LINE OPENING, ACCORDION GATE. 12 SO. FT. 20 RESIDENTIAL DRIVE CRAWFORDVILLE, FL 32327 Resdential8evatDrs c= 1-800-832-2004 HOR HP9 A 12 LxurtilxTugeAxo MACHINERY ACCESS DOOR uDe/r swrttx lsro.c.l A x 4 ELECIRi 11( ( 24' x 24' MAX. (BY G.C.) FOR 2<D VAC 1� (GC/O'MlFA PROADED) \�Iy � r0H 120 VAC (GC/ONNERPRP0W) OR 110 V.ftELEPTALIE (gYO.C.) ® O \\ - - ELEVATOR CONTROLLER TEIEPRONE COMIECIlONTO BE 1ER6111UTFD PI EIEVAIOq COtrtftOLlEq (gYpC.) OVERHEAD CLEARANCE GEARBOX AND MOTOR ASSEMBLY 102` MIN. FOR STD. CAB HEIGHT 114' MIN. FOR V-0' CAB HEIGHT ALTERNATE ACCESS DOOR (IF LESS THAN 10Y IS 24' MAX. x 18' (BY G.C.) AVAILABLE, CONSULT P F 1.) Cl O LINE ELEVATOR SHAFT WALLS WITH PLYWOOD (PREFERRED) OR DRYWALL LANDING DOORS CHECK LOCAL CODE REQUIREMENTS FOR THICKNESS 2'-8` OR V-0' W BY V-8' OR S'-W H SOLID CORE TGPaooR RECOMMENDED ugorao (BY G.C.) DOOR INTERLOCK ELEVATOR RAILS & BRACKETS BY R.E.I. (TYP.) BY R.E.I. AND INSTALLED BY R.F 1. 0 4'I 0 COUNTERWEIGHT ASSEMBLY L- HALL PUSH BUTTON STATION BY R.F 1. (TYP.) ELEVATOR PIT MINIMUM 4' THICK Donou REINFORCED CONCRETE SLAB iL00q PIT DEPTH uxowo °e e' WMIN. A o°o ego' TYPICAL ELEVATION RESIDENTIAL ELEVATORS(REI) CONTROLSYSTEM CONTAINS THE 240VAGAND 120VAC DISCONNECTS, TYPICAL2 STOP HOISTWAY LAYOUT HOWEVER; GC/ OWNER MUST PROVIDE DEDICATED NOTES: CIRCUIT AND WIRE 704' x 4` BOX (1 FOR 24D VAC & 1 FOR 120 VAC) IN MACHINE SPACE PER DRAWING. 1. RAIL IS CONCRETE ANCHORED WITH 11T REDHEAD OR SEE REI ELECTRICALREOUIREMENTS BROCHURE CONCRETE SLEEVE BOLTS GR.5 - V2' x 4' ANCHORS FORfURTHER DETAILS. LAG D W 1/2' 4' HEX EAD lEE 11fORVATONCOMAh401RRENG50lilYMl'tSD0YPE59F1Rt+LF1EVATORS. NS A!ITRFPAOWCTgY P! PARTOq ASA1YYOlE1YDHOVINAR1ER ifJtV39GRIRW AEEDERN1FlEVAi0R5.w0.G51WLRYPgOH'EgEO. Elevating your standard of living 2. RAIL RRACKETS ARE GE ITH x H LAG SCREWS 3. FOR EACH T HOISTWAY IS REDUCED IN WIDTH OR DEPTH CAR SIZE IS REDUCED BY 1' IN WIDTH OR DEPTH LUXURYLIFT LLTTRACTION Home Elevator e Pre Installation Checklist Each item listed below is required to be fully complete prior to Residential Elevators, Inc. scheduling an installation crew. Please see WORK DONE BY OTHERS for specific requirements. Job REI # Completed Item Y / N Date Notes 1 Pit Depth (8" min/35" max), plumb & square with hoistway/shaft. Confirm loads per Work By Others. 2 Hoistway measurements per specs. Legal Hoistway that is clean, dry, clear, square & plumb 3 Legal machine room (hydraulic only) 4 Access door per spec's (traction only) 5 Dedicated 240VAC/ 30A circuit 10-3 wire to machine room (hydro) or top of shaft traction in 4x4 junction box with 6" pigtail 6 Dedicated 120VAC/ 20A circuit 12-2 wire to machine room (hydro) or top of shaft a traction in 4x4 junction box with 6" pigtail 7 Phone line w/ 10' pigtail to machine room h dro / equipment location traction 8 Rail side blocking complete per spec (whole wall to be solid concrete, poured block, or (2) 2"x12" wood blocking sandwiched with 2 2"x4" perframin detail 9 Rail side door returns per specs 10 Door entry comply w/ 3"x5" rule 11 Hydro only: Confirm minimum 3" clear knockout through all penetrations between machine room and hoistwa 12 Overhead measurement (from top landing to underside of holstway cellinper s ec's 13 Hoistway and Machine Room (hydraulic) covered by sheet rock including 240VAC / 120 VAC / Phone line 14 Doorjamb installed & compliant w/ 3"x5" code a 15 Solid core door installed maximum 3" from edge of floor / threshold 16 Maximum 1/4" thick hoistway door casing / trim on holstway side of jamb 17 GFI Light & Switch in machinery space 18 Door hardware installed u01i 19 Temp. power to machine room a20 Permanent power on home I have reviewed the job site conditions as outlined above and confirmed that all work required in the "Work Done By Others", is complete and jobsite is ready for elevator installation. General Contractor/ Job Superintendent Date Residential Elevators, Inc. November 2011 Home elevator 311x 579 Rule Residential Elevators manufactures and installs a fully code compliant elevator per the ASMEANSI Al7.1 National Safety Code for Elevators- Section 5.3 Private Residence Elevators. Rule 5.3.1.4.2 (aka 3"x 5" Rule) of the above referenced code states: Clearance Between Hoistway Door(s) or Gate(s) and Landing Sill(s) and Car Door(s) or Gate(s). The clearance between the hoistway doors or gates and the hoistway edge of the landing sill shall not exceed 3 inches (76 mm). The distance between the hoistway face of the landing dooror gate and the car door orgate shall not exceed 5 inches (127 mm). Note: Concrete block It masonry shafts and some commercial metal door frames can often create 311X 5'r Rule violations. -�•. �. "•- *aF LANDING DOOR ��� Landing Door 1J/4'THICK -,--' 1-314' Thick BY G.C. i — HOISTWAY I FACE OF 3" Max. LANDING DOOR Finished — HOISTWAYWALL Edge of 5" Max. Gate Flooring W-1-1/4" * 114" —trim ELEVATOR should not Running Maximum CAB GATE exceed 3' Clearance - or no trim at from back of MWMax. all (preferred) doctor Cab b" MAXIMUM extend Top View FINISHED 3" MAXIMUM EDGE OF FLOORING * 1/4" trim (or no trim at all.) Do not Install conventional House Side door casfng. Elevator Plallorm or Elevator ** 1-3/4" thick door In lieu of a — -- standard 1-1/2" door is required. /J7 i— RUNNING CLEARANCE) Note: An out of plumb shaft will greatly 112" TO 1.114" THE INFORMATION CONTAINED HEREIN IS SOLELY OWNED BY affect running clearances and (Rule 6.3.1.4.2) Side View RESIDENTIAL ELEVATORS, INC. ANY REPRODUCTION IN PART ORASA WHOLE WITHOUT WRITTEN exacerbate the 3" x 5" Code Compliance Issues. PEWAISSION FROM RESIDENTIAL ELEVATORS, INC. IS STRICTLY PROHIBITED. The 3"x 5" Rule is a code requirement. Residential Elevators takes pride in ensuring safety in the use of their equipment and as a policy wants to make sure all Builders, Architects, Developers, Owners It Users are aware of and adhere to this National Code. This is a safety issue. Authorized Signature Date April 2012 Electrical Requirements for Elevator Machinery Space (by G.C./Owner/Other) Land Based Light GFI House Phone Line Fixture _' Outlet pigtail (10 Ft. min.) With wall Switch -- Elevator Controller (l1,th irnegral AC disconnects) Elevator Cab Traveling Cable to Elevator Cab Light Power -120 VAC 20 Amp Circuit r (See Note 2) Main Power - 240 VAC 30 Amp Circuit (See Note 1) S e d R E - 4" x 4" Junction Boxes Mounted to Machine Room wall By General Contractor / Owner Each home elevator requires five (5) items from your Electrician and Telecommunications Contractor(s). They are as follows: THE INFORMATION CONTAINED 1. Main Power -10/3 with Ground (min. 6") Pigtail connected to house 30 Amp dedicated circuit HEREIN IS SOLELY OWNED BY 2. Cab Light Power- 12r2 with Ground (min. 6") Pigtail connected to house 20 Amp dedicated circuit RESIDENTIAL IN PART OR ASA 3. One (1) GFI Outlet. PERMISSWITHOUTWRITTEN ION FROM RESIDENTIAL 4. One (1) Light Fixture (with protective cover over bulb) with wall switch. ELEVATORS. INC. IS STRICTLY 5. One (1) Live Land Based Phone Line with pigtail (I V-0" Min.) per code. PROHIBITED. PLEASE BEADVISED THAT POWER ON THE 240 VAC LINE MUST BE A 103 WIRE WITH A GROUND AND INSURE THERE IS A DEDICATED NEUTRAL TO THE UNIT. Explanation: The 240 VAC feed should have a black, red, white and ground wire coming to the machine room. All electrical contractors will have full knowledge of this requirement Simply insure they are aware of the requirement. Slack and red are powered with 120 VAC, each totaling 240 VAC. White is neutral. Ground to ground standard. Also, standard telephone line should be pulled to machine room with approximately ten feet extra length inside machine room. If further explanation or cladreation is needed, please contact your local sales representative. Residential Elevators, LLC Toll Free 1-800-832-2004 May 2013 Elevator Electrical Requirements Hydraulic Application Elevator Hoistway Controller Machine Room ulic Power Unit Controller GFI Outlet Main Power (4" x 4" Box) Cab Light Power (4" x 4" Box) Room Light and Switch Cab Light Power (4" x 4" Box) Room Light and Switch Main Power (4" x 4" Box) GFI Outlet Traction Application Toll Free 1-800-832-2004 Residential Elevators, LLC contact: sales@ResidentialElevators.com Res id a nti a l E l evators. co m THE NFOF.M rMCWTA FOWN GSO.ELYOY.NEOBYR6410E MMATORS,NC.MTREPRORJCTIOM M PARFCRASAWHO MH=VMffikNPEAMG.90MFMMR610ENfW. ATOIS.MGGSit MYPR�. 4 z4 B.ECrRICAL BOXES 11n14T 720 y4p ® o REI 1AC VAC OO CONTROLLER ELEVATION ' VIEW'A' PLAN VIEW Elevating your standard of living ACCESS DOOR ------ V4" THICK WOOD TRIM (MAX.) HALL DOOR I] 1 ELEVATION VIEW'S' R.EI. VARIABLE SPEEDId _—___ DRIVE --_— l ELEVATION VIEW'D' NOTE LIGHT FIXTURE LIGHTSWITCH, RECEPTACLE AND ELEC. BOXES CANNOT BE. MOUNTED LOWER THAN 1S LINE FROM CEILING. NOTE: THESEARE MINIMUM OVERHEAD CLEARANCES. HIGHER CEILINGS WILL ALLOW MORE ROOM FOR DEVICE MOUNTING. ALL DIMENSIONS ARE BASED ON 102" OVERHEAD FOR STD. CABS AND 114' OVERHEAD FOR 9-0" CABS LUXURY LIFT LLT TRACTION UGHTSW. (BY OTHERS) 120 VAC -GFCI u c RECEPTACLE OTHERS) PLACE ALL EQUIPMENT ABOVE THIS LINE (SEE NOTE) ELEVATION VIEW'C' 24" ACCESS °v DOOR HALL DOOR ELEVATION - VIEW'E'