Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
=RECEIVEDClient: Ryan Homes
1450 Centrepark Blvd Suite 340West Palm Beach, FL 33401 Project: Oakland Lake Subdivision Lot 63
5283 Oakland Lake Circle Permit 1812-0025, Ft. Pierce, St. Lucie County, FL
As requested, Universal Engineering Sciences, Inc. (UES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
SCANNED
QV
Work Order No.
Date
Type of Report
105836.1
01/17/2019
In -Place Density Test Report w/Activity Record
106056-1
1 01/23/2019
In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
Sincerely,
Universal Engineering Sciences, Inc.
Certificate of Authorization No. 00000549
Z
Richard E.
E... c''��
Hoaglin, P.E.
No.
2019.01.31
48796 =_
16:04:01
STATE OF=
-05'00'
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
This item has been electronically signed and sealed by
Richard E. Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verified on any electronic
copies.
ICC Email: cbugg@nvrinc.mm; rhager@nvrinc.com; signrseal MAIL to ryan homes at 5369 Oakland Lake, Vero Beach, FL 32966
041
UNIVERSAL UUESES R pCo NNo: 106056-01 ARC0
012319
ENGINEERING SCIENCES On -Site Time (hrs):1.00
Consultants In: GeotechnialEngineering 9Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services , Materials Testing • Threshold Inspection Travel Time (hrs): 1.00
Building Code Administration, Compliance lnspection&Plan Review Total Time (hrs): 2.00
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 63
5283 Oakland Lake Circle Permit 1812-0025, Ft. Pierce, St. Lucie County, FL
Date of Activity: Wednesday, 23 January, 2019
Technician: Cliff Chermav
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the House pad.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
UNIVERSAL
ENGINEERING SCIENCES
Consultants in: Geotedmical Engineering • Environmental sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building CodeAdministrauon, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
UES Project No: 0310.1700251.0041
UES DOCS No:
UES Report No: 106056-1 DT 012319
In -Place Density Test Report
Client: Ryan Homes JAN 31 2019
1450 Centrepark Blvd Suite 340 sr. Lucie county, perm
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 63
5283 Oakland Lake Circle Permit 1812-0025, Ft. Pierce, St. Lucie County, FL
Area Tested: House pad
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 01/23/2019
Lab: ASTM D1557 Modified Proctor
Technician: Cliff Cherrnay
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the rnnditinn of the underivino soils below the tested deoths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1
NM Test
0-1 ft
12.00
21143
110.2
11.4
96
A
2
WE Test
0-1 ft
12.00
21143
109.6
11.7
95
A
3
S/E Test
0-1 ft
12.00
21143
110.0
11.0
96
A
4
S/W Test
0-1 ft
12.00
21143
111.8
11.0
97
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21143
116.0
12.0
7his test was performed without deviation from ASTM procedures.
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min.. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
/b 1 4 — wtb
U N 1. V r R S A L Date dd: No.: Joan ary31z 200941
ENGINEERING S.CIENC.ES
Consultants In: Geotechnical Engineering • Environmental Sciences FILE ECel� P
.GeophysicabServicesl•'MaterialsTesting • Threshold Inspection93 FEB 2
Building Code Administration, Compliancelnspe Lion & Plan Review 12018
820 Brevard Avenue, Rockledge, FL 32965 - P: 321.638.0808 - F: 321.638.0978 Permitting
Client:
Project:
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
SCANNED
BY
St. Lucie County
Oakland Lake Subdivision Lot•6.3 , -��
5283 Oakland Lake Circle ;eimit 1812_OQ25) t. Pierce, St. Lucie County, FL
As requested, Universal Engineering Sciences, Inc. (UES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No.
Date
I Type of Report
105836-1
01/17/2019
In -Place Density Test Report w/Activity Record
106056-1
1 01/23/2019
In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
Sincerely,
Universal Engineering Sciences, Inc.
Certificate of Authorization No'
, . 00000549
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
This item has been electronically signed and sealed by
Richard E Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verified on any electronic
copies.
ICC Email: cbugg@nvrinc.com; rhager@nvrinc.cem; sign/seal MAIL to ryan homes at 5369 Oakland Lake, Vero Beach, FL 32966
R S A L UES Pr t No: 0310.1700251.0041
UES DC4No:
U N I V ncc oe...,.r u..• ansuza_i ear n-i47aa
ENGINEERING SCIENCES On -Site Time (hrs):0.50
Consultants In: Geotechnical Engineering , Environmental5dences Lab Time (hrs): 0.00
Geophysical Services a Materials Testing-i Thiesholddnspection Travel Time (hrs): 0.25
Building Code Administration, Compliance lnspecUon&Plan Review Total Time (hrs): 0.75
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 63
5283 Oakland Lake Circle Permit 1812-0025, Ft. Pierce, St. Lucie County, FL
Date of Activity: Thursday, 17 January, 2019
Technician: Timothy Hughes
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the house pad.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for house
pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method. 1 test(s) were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557. 3 test(s) were found to not meet the
project compaction requirement of 95% of the maximum dry density per ASTM D-1557 and these areas require recompaction
and retesting.
The Contractor was notified of the test results or a copy was left for their records.
UNIVrRSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering -Environmental Sciences,
Geophysical Services • Materials?esting • ThresholdInspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
In -Place Density Test Report
t1E: ject No: 0310.1700251.0041
LIES, .'CS No:
UES Report No: 105836-1 DT 011719
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 63
5283 Oakland Lake Circle Permit 1812-0025, Ft. Pierce, St. Lucie County, FL
Area Tested: house pad
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 01/17/2019
Lab: ASTM D1557 Modified Proctor
Technician: Timothy Hughes
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underlying soils below the tested depths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1
SE corner of pad
0 to -1 ft
12.00
21143
106.1
6.9
92
B,D
2
SW corner of pad
0 to -1 ft
12.00
21143
108.4
7.1
94
B,D
3
NW corner of pad
0 to -1 ft
12.00
21143
108.6
9.4
94
B,D
4
NE corner of pad
0 to -1 ft
12.00
21143
110.9
6.4
96
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture '
#
Density
Content
21143
115.0
12.0
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This test was performed without deviation from ASTM procedures.
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
'
1
I
N'
v r
t rt �A
UES Report No : 106056-1 ARC 012319
ENGINEERING SCIENCES On -Site Time (hrs):1.00
Consultants In: Geotechnical Engineering • Environmental Sciences Lab Time (hrs): 0.00
Geophysical5ervices • MaterialsTesting'i Thiesholddrispection Travel Time (hrs): 1.00
Building CodeAdministration, Compliance Inspection&PlanReyiew Total Time (hrs): 2.00
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 F: 321.638.0978
Activity Record
Client:
Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project:
Oakland Lake Subdivision Lot 63
5283 Oakland Lake Circle Permit 1812-0025, Ft. Pierce, St. Lucie County, FL
Date of Activity:
Wednesday, 23 January, 2019
Technician:
Cliff Chermay
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the House pad.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
WW ! `� I I � .' S � am US ICS No: 0310.1700251.0041
ENGINEERING SCIENCES "Co ReportNo: 106056-1DT012319
Consultants In: Geotechnical Engineering •Environmental Sciences.
Geophysical Services • Materials Testing'. Threshold'Inspection
Building. Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
In -Place Density Test Report
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 63
5283 Oakland Lake Circle Permit 1812-0025, Ft. Pierce, St. Lucie County, FL
Area Tested: House pad
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 01/23/2019
Lab: ASTM D1557 Modified Proctor
Technician: Cliff Cherrnay
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underlying soils below the tested depths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1
N/W Test
0-1 it
12.00
21143
110.2
11.4
96
A
2
N/E Test
0-1 it
12.00
21143
109.6
11.7
95
A
3
S/E Test
0-1 ft
12.00
21143
110.0
11.0
96
A
4
S/W Test
0-1 ft
12.00
21143
111.8
11.0
97
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21143
115.0
12.0
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This test was performed without deviation from ASTM procedures.