HomeMy WebLinkAboutSCREEN PAPERWORKGENERAL NOTES 1. DESIGN CRITERIA: APPLICABLE CODES, REGULATIONS & STANDARDS: -1.THE-2017 FLORIDA-BUILDING CODE, 6TH-EDITION SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CHAPTER 23 WOOD. 2. ASCE 7-10. & SEI7 3. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 4. AC1318 CONCRETE REFRENCE MANUAL. 5. PC[ PRECAST & PRESTRESSED CONCRETE. 6. AA ASM 35 & AA ADM 1 WIND LOADS: 1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE 1604.5: RISK CATEGORY 1. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 150 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: C 3. SCREENED ROOF ENCLOSURE FBC 2017 CH. 20 TABLE 2002.4 CONCRETE & FOUNDATION DESIGN: 1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE APPLICABLE: A. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING COMPONENTS: I. PORTLAND CEMENT TYPE 1 - ASTM C 150 II. AGGREGATES - LARGE AGGREGATE 3/4" MAX. - ASTM C 33 III. AIR ENTRAINING +/-1 %- ASTM C 260 IV. WATER REDUCING AGENT- ASTM C 494 V. CLEAN POTABLE WATER VI. OTHER ADMIXTURES NOT PERMITTED B. METAL ACCESSORIES SHALL CONFORM TO: I. REINFORCING BARS - ASTM A615, GRADE 60 II. WELDED WIRE FABRIC -ASTM A185 C. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3" OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT PERMITTED. D. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3 INCLUDING HOT WHEATHER RECOMMENDATIONS. E. MOIST CURE OR POLYETHYLENE CURING PERMITTED. F. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE ARE FOR TERMITES IN COMPLIANCE WITH THE FBC. G. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR BARRIER. 2. FOOTING SIZE: EXISTING CONCRETE SLAB. NO ADDITIONAL FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE PROPOSED CONSTRUCTION IF A MINIMUM 4" CONCRETE SLAB (3000 PSI) IS PROVIDED IN SOUND CONDITION, FREE FROM STRUCTURAL CRACKING, SPALLING & OTHER DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER CONCRETE SLAB MINIMUM 8"x8" W/ (1) #5 BAR TO BE VERIFIED BY CONTRACTOR. SEE TYPICAL FOOTING DETAILS FOR NEW FOOTING DESIGN MINIMUM REQUIREMENTS. 3. WHEN APPLICABLE FOR ATTACHING NEW FOOTER TO EXISTING, DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1" MIN. HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE (OR EQUAL) TYP. ALL LOCATIONS. 4. WHEN INSTALLING 4" CONCRETE SLAB -ADD ADJACENT TO EXISTING-DOWELL INTO EXISTING CONCRETE 48" O/C W/8" #5 REBARS- DRILL 3/4" HOLE 4" EMBEDMENT- EPDXY W/ NON -SHRINKING "SIMPSON EPDXY TIE" (OR EQUAL). 5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHER WISE NOTED. ALUMINUM SPECIFICATIONS: 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS OTHERWISE SPECIFIED. 2. ALL SELF MATING BEAM SECTIONS ARE70-BE STITCHED WITH #12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. 3. ROOF BRACING SHALL BE A MINIMUM 2 %2"X.050". 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING LLC- FASTNER SPECIFICATIONS: 1. FASTNERS ARE REQUIRED TO BE SAE GRADE 2 OR BETTER ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS OR BETTER, INSTALLED TO MFG.) 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, AND FASTENERS TO MANUFACTURING SPECIFICATIONS. 3. WHERE WOOD DECK IS PRESENT USE 1/4"X3-1/2" GALV. LAG SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE SPECIFIED. 4. 1"X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED 1/4"X2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS B. FOR WOOD APPLICATION USE #14X2-3/4" WOOD SCREW AT 24" O.C. AND 6" FROM ENDS. C. FOR ALUMINUM APPLICATION USE #10X1-1/2" SMS OR TEK SCREW AT 24" O.C. AND 6" FROM ENDS D. WHERE VX2" INSTALLED THROUGHOUT AN "OPEN VIEW" SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS MASONRY SPECIFICATIONS: 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR. 2. ALL MORTAR SHALL BE TYPE M OR S. 3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". 4. PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS 5'-0" IN HEIGHT. MISCELLANEOUS: -- - - - - _ ST.-LUCIE COUPYTY- L- r BUILDING DIVI ..�^, R NVbs FOR COMP IAN REVIEWED BY DATE PLANS AND PE MIT MUST BE KEPT ON.JOB OR NO INSPECTION WILL BE MADE 2. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND INSURE INSTALLATION HAS BEEN ACCOMPLISHED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH THE ATTACHED DETAILS. 3. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND. 1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. 3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN THE FIELD. 4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR SHALL EPDXY TO DECK OR GROUT TO DECK W/3000 PSI GROUT WITH BONDING AGENT. 5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED STRUCTURE. 6. ALL 2X4 & GREATER ARE TO BE SMB UNLESS OTHERWISE INDICATED. RESPONSIBILITIES: 1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. Aw iL LEGEND: (ALL MAY NOT APPLY) SCR = SCREEN KP = KICK PLATE PW = PICTURE WINDOW X = HORIZ. SLIDING WINDOW O = HORIZ. STATIONARY WINDOW DH = DOUBLE HUNG WINDOW SH= SINGLE HUNG WINDOW SIP =SOLID INSULATED PANk# CT CABLE TIE bNCFALED F STENERS OR ATTACHMENTS = SG = SUPER GUTTER CS CLEAR SPAN ,ARE THE ESPONSIBILITYOF THE = KB = KNEE BRACE CONTI ACTOR OFRECOM ALUMINUM MEMBERS DIMENSIONS HOLLOW SECTIONS 2 x 2: 2"xZW.044" 2 x 3: 2"xTW.044" THESE PLAN % AND ALL PROPOSED WORK 2 x 4: 2"x4"x0.044" ARE SUDJ-C TO ANY CORRECTIONS 2 x 5: 2"x5"x0.050" REOUIRm F3 FIELD INSPECTORS -mT OPEN BACK SECTIONS I4Y De 1�EC SSARY IN ORDER TO 1 x 2: 1 "xZW.044" 1x3:1"xTW.044" COLIPLYWITI I ALL APPLICACLECODES, SNAP SECTIONS 2 x 2 SNAP: 2"x2"x0.050" 2 x 3 SNAP: 2"x3"x0.050" 2 x 4 SNAP: 2"x4"x0.045" SELF MATING (SMB) 2 x 4 SMB: 2"x4"x0.044"x0.100" 2 x 5 SMB: 2"x5"x0.050"x0.100" 2 x 6 SMB: 2"x6"x0.050"x0.120" 2 x 7 SMB: 2"x7"x0.057"x0.120" 2 x 8 SMB: 2"x8"x0.072"x0.124" 2 x 9 SMB: 2"x9"x0.082"x0.124" 2 x 10 SMB: 2"x10"x0.092"x0.398" NOTE: AS INDICATED ABOVE ALL MEMBER PROFILES ARE INDICATED IN INCHES. O co O) co co p o U of p U 01m LL Lo 'LU N H m c 0 c 2 U z_ w Lu Z z Q 0 w O LL. NNEO 0 �Q�n�l St. ,e w 0 W W LL w N zw F0a w o Z a � ID 0 0 Occ) 0 0 w LL N LL DESIGN DATE: 72/10/2018 REVISION 1: DATE PAGE: ljy REVISION 2: DATE SCALE: NTS WALL i HEIGHT PER PLANTo p o sp 0 ru `\\ I„ V 01-0.1 _I_ 81-01. J_ Upl lX3 X 2X3 0 o N N w rn X X rn w 0 ' 00 co , 1X3 I I I I f ------------------ 10' O., 24'-0" cn 0 C n G) C m 0 z� 00 iO -i rn 00 f~-1 r20'-0" i -n D m� ------------------T 0i z 0 \ 1X3 G> m z O N \` X X Dm rn \\cn w Cn ow O W 07 N W sp z 2X3 w �o c{ 0 00 1X3 c _81-011—�81-011__.�-41-011���121-6" Az r—Y F.0 �O m m� �z �_ xm 0 -n m = z 30 cNi m m m CONTRACTOR: m < < N PIONEER SCREEN LLC .v� FLORIDA ENGINEERING LLC 0 4456 TAMIAMI TRAIL, UNIT B14 m PORT CHARLOTTE, FLORIDA 33980 0 m o m (941) 391-5980 • — PROJECTADDRESS: www.flengineeringilc.com ti FOUST 2656 CONIFER DR y E. Gunderson, P.E. #60102 N m .. FORT PIERCE, FL . PROJECT NO. 1834408 CA CERT.#30782 DATE: 12/10/20I8 f~ I I I I I I - 3X2 V ' � 2X6SMB `\ I I V' I II 1- w 2X6SMB I I I i V _ I I I I w i 2X6SMB i W N � W W I I • I I 2X6SMB I I I I I V I W - �\ � 2X6SMB \ \\ i i \ i i w \ i 3X2 \�� ; 3'-0" I I I I I I � 3X2 I X ' w X i w I i 2X8SMB 2X8SMB I I i I I I I I I w 2X8SMB I I I I i I i I W _ W N N N W W 2X8SMB i I I 2X7SMB Nil iC i i li I Xw `"' 3X2 '� FLASHING 'HORIZONTAL OR SLOPED N O O I-xr FASTEN TO COL. (INTERNAL) W/(2) #10x1-1/2" SMS, FASTEN TO EAVE RAILS ABOVE W/ #10X1-1/2" SMS TABLE D BEAM QTYEACHSIDUSRE 2x3 4112 2x4 B/10 2x5 8/10 2x6 10/10 2x7 12/10 2x8 8/14 2x9 9/14 2 x 10 9/14 j 0 1 0 MAINTAIN MIN, OF 518" SEPERATION FROM EDGE OF BEAM SMS O.C. DETAIL E - UPRIGHT TO BEAM CONNECTION SCALE:NTS (2) #10x3" SMS INTO SCREW BOSSES FOR EDGE MEMBEF EDGE MEMBER OR PURLIN BEAM PER PLAN (2)#1Ox2" `. NOTCHED TO RECEIVE INTO BEAM COLUMN WITHIN ISMS, (EACH SIDE) BEAM BRACE QTY PER TABLE D INSTALL BRANOTCH PROFILE MAY VARY TO CORNERCE TO PERMIT CORRECT # SMS PURLIN COLUMN PER PLANS TABLE "B" SECONDARY ANGLE SCHEDULE DETAIL "D" - ROOF BRACING CONNECTION DETAIL SCALE: NTS EDGE MEMBER OR PURLIN ALUMINUM INTERNAL OR EXTERNAL RECEIVING CHANNEL w/(4) #10x.75- INTO GIRT OR PURLIN 8 (2) #14x75" INTO BEAM OR UPRIGHT 0.062 ANGLE CLIPS MAYBE USED �. P_URUN I UPRIGHT, BFAM-SNAP, SELF MATING, OR HOLLOW III. 1. MEMBER. < DETAIL "C" -GIRT OR PURLIN TO BEAM OR POST DETAIL SCALE: NTS NOTE: IF PAVERS ARE PRESENT, CONCRETE UPRIGHT QTY. TAPCON/ SCREW 'ALL MEMBERS PER PLAN ANCHORS SHALL 2X3 O 'MEMBERS VARY PER PLAN PENETRATE INTO 3"x2" EDGE BEAM ; FOOTING 2-1/4"MIN. 2X4 1/2 ------ TYP) 2X5 1/2 NOTE: WHEN FASTENING 2Y`6 2/ 4 PORUN TO WOOD USE 1/4" GALV. (2) #10x5" SMS LAG SCREW IN LIEU OF 2X7 2/ 4 lii FASTEN TOP OF HEADER TO INTERSECTING INTO SCREW BOSSES 4 CONC. ANCHORS AND 2XS 316 MEMBERw/(2)#10SMSw/1" p o CONINECTINGEDGE ENSURE PENETRATION a PENETRATION INTO SCREW BOSS OF o 1 a u BEAM TO PURLIN 2"X3"%2"X7/8"ANGLE MIN2-1WINTO 2X9 3/6 MEMBER-TYP. BOTH SIDES FASTENED COLUMN W/(4)#12 X 3/4"EA LEG STRUCTURAL FRAMING 2X10 4/6 w/(2) M BENEATH (TYP.) ^ A SCREWBOSSESFOR SMB SCRE1BOSS"SFOR SM I � II V III I'iiv iil na sMna on, uMM IIt 5032 H-32 ANGLE 2 -#12 SMS INTO COLUMN 1/4" MASONRY ANCHOR EACH 3000 PSI CONIC. SLAB/FTG. 6x&10x1O W WM OR FIBERMESH SELF MATING OR SNAP SECTION TYP. PER PLAN 1"x2" O.B. BASE PLATE-TYP. 01 2-1/4" MIN. CONC. ANCHOR EMBEDMENT 2" MIN. WHEN GREATER THAN 2x4 UPRIGHT IS USED SEETABLE"B"SECONDARY \);: ANGLE SCHEDULE SIDE VIEW 2 - #12 SMS 1/4"TAPCON XL (RED HEAD MFG. OR EQUAL) 2 @ 14 BASE 2 @ SLAB (BEYOND) 1"x2" BASE PLATE ANCHORED TO CONIC w/ 1/4" MASONRY ANCHOR 6" MAX EACH SIDE OF POST AND 24" O.C. MAX 30DO PSI CONC. SLAB/ FTG. I 6x&im FRONTVIEW WWM OR FIBERMESH DETAIL "B" - 2"x4" OR LARGER SELF MATING UPRIGHT TO DECK DETAILS SCALE: N.T.S. PER PLAN FASTEN HEADER INTO SCREW BOI ALTERNATE HEADER CONNECTION WHEN Z-BAR IS USED- FASTEN Z-BAR TO COLMEADER AT EACH CORNER AND 18" O/C ALTERNATE BASE PLATE CONNECTION ATTACH MEMBER TO BASE PLATE (INTERNAL) w/(2) #10x2" SMS ATTACH BASE PLATE TO MEMBER W/(2) #10x3" SMS INTO SCREW BOSS OF BASE PLATE � 1/4" TAPCON (RED HEAD MFG. OR EQUAL) WITHIN 6" OF COLUMN 824" O.C. MAX. 1-114" PENETRATION INTO UNDERLYING FOOTING DETAIL "F' - DOOR JAMB & HEADER CONNECTION SCALE: NTS NOTCH COLUMN AS REQ'D. COLUMN PER PLAN DETAIL "G" -SLOPED PURLIN CONNECTION SCALE:NTS J W rn Fw- 12 \ SY O Uy J r DO N o J m rn # M of Z_ Z 0 O LL p (3 WJOoo0) W LL LO .L �- r (''� V `M'` Z 0 c W Q00 0 o O LL Nt LL. 00 O Z U LI O Q. 1-1/2"x 1/16" PLATE (12)#12XV SMS (TOP OR BOTTOM) @ V SPACING \ \\\\1 J 3"X2" EDGE BEAM J 3RW.W01 W J 0 0 LL' (2) #10x5" SMS INTO SCREW BOSSES O.' ll.l CONNECTING EDGE LU U BEAM TO PURLIN 1"b" FASTENED TO COLUMN W lL Of W/(2)#10x1-1/2"SMS INTO Of N Z w W SCREW BOSSES FOR SMB W 0 OR SNAP COLUMN W of (n H p O F :D V Q UL LL NOTCH COLUMN AS REDD. Q- W 04 LL COLUMN PER PLAN z n ALTERNATE DET"G" SLOPED PURLIN CONNECTIOAILN SCALE: NTS DESIGN DATE: 12/10/2018 REVISION 1: DATE PAGE: REVISION 2: DATE SCALE: NITS GIRT FASTENED INTERNALLY AT EACH END w/ #10xl.5' EACH SCREW GROOVE. FASTEN TO BEAM w/ 2x2xl25 ANGLE (2) #12 EMS INTO BEAM & (2) #10x1-1/2" THRU ANGLE INTO GUTTER WHERE NO GIRT IS PRESENT, ATTACH ANGLE DIRECTLY TO GUTTER _ 25Q"AIW ANGLE BEAM o CLOSE BOTTOM OF BEAM WHEN TRIMMED .044 RECEIVING CHAW FASTEN w/(2) #12 SMS EACH SIDE OF BEAM/ OF 2x2xl/8" ANGLE EA SIDE OF BEAM w/(2) #12 SMS EACH LEG EACH S FOR BEAMS ABOVE 2x8 INSTALL GUTTER BRACE AT MIDPOINT BETWEEN BEAMS & INCLUDE 2" GUTTER BRACE AT EACH BEAM LOCATION 18"O.C. FOR BEAM OVER 2x5 .044 RECEIVING CHANNEL FASTEN TO STRUCTURAL GUTTER IN ERNALLYw/(2)#12 SMS ALTERNATELY 2x2xl/8" ANGLE BELOW GIRT, (2) #14 SMS INTO BEAM & (2) #12 SMS INTO STRUCTURAL GUTTER SIDE VIEW TOP VIEW DETAIL"H" SCALE: NTS FASTEN GUTTER TO FASCIAw/#14x2" WOOD SCREW TW O.C. (2) #12 SMS (2)#14x2' WOOD SCREW FASCIA (25B" MIN. EXISTING) STRUCTURAL GUTTER "ALTERNATELY SEE PAGE 5 0 oTo of JI F of i o of` `F 0 -L o I \ \o �\ o F yo F NOTE INSTALL FASTENERS ALONG PERIMETER OF GUSSET -BEAM JOINT 318" MIN, FROM EDGE. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 FASTENER PATTERN MAY APPEAR DIFFERENT FROM ILLUSTRATION. MAINTAIN 1/2" SEPARATION BETWEEN FASTENERS. MAINTAIN 3/8' MIN, FASTENER SEPARATION FROM BEAM JOINT OR EDGE OF BEAM LAP FASTENERS MAY BE EVENLY SPACED AROUND EDGE OF GUSSET WITHIN 3/8" OF BEAM JOINT. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 3116"-5052-H32 GUSSET INTERNAL OR EXTERNAL (2X10SMB ILLUSTRATED) TABLE B-1 8E M COL TO BEAM OTYSM� SIOEOFCOL. BEAMTO BE Owsm FACESICE 2 x 4 (5) #12 (9) #12 2 x 5 (5) #12 (9) #12 2 x 6 (7) #12 (9) #12 2x7 (10)912 (10)#12 2x8 (12)#12 (14)#12 2x9 (14)#14 (14)#14 2 x 10 (16) #14 (15) #14 DETAIL "K" GUSSET CONNECTION SCALE:NTS .050" GUTTER STIFFNER FASTEMTOFASIAw(2)— #12x2" WOOD SCREW FASTEN TO GUTTER w(2) #12 SMS l WHEN BEAM & PURLIN HIT ON CORNER - FASTEN OUTSIDE OF BEAM & PURLIN w/ 1/8"x250 ANGLE & (4) #12 SMS EACH LEG FASTEN INSIDE CORNER (BEAM TO PURLIN) w/ 1/Wx25Q" ANGLE w/(2) #12 SMS INTO EA. MEMBER "ALTERNATELY SEE PAGE 5 T (BEAM & PURLIN) DETAIL "M" BEAM &PURLIN TOGUTTER CONNECTION SCALE: NTS 2x2xl/8" ANGLE w/(2) #12 SMS EA LEG, (2) #12 SMS SMB L GIRT 1/8"x2'h4" STRAP (2) #12 SMS INTO BEAM STRUCTURAL GUTTER (2) #12 SMS INTO GUTTER SIDE VIEW n�"o".� FASCIA 118"x2"x4" STRAP GIRT (2) #12 SMS INTO BEAM (2) #12 SMS INTO GUTTER GIRT FASCIA (2) GUTTER BRACES SMS ENTACH GUTTER IO GUTTER 8 (2) # \ WOOD SCREWS INTO 2x2x1/8"ANGLE w/(2) #12 SMS E& LEG (2) #12 SMS SMB 1HW"x4" STRAP (2)#12SMS INTO BEAM GIRT (2) #12 SMS NTO GUTTER STRUCTURAL GUTTER TOP VIEW DETAIL "L" CORNER CONNECTION SCALE: NTS (9) #10x2" SN IB" PLATE ON 45' ANGLE OR M"x2")T ANGLE 4(4) #12 SMS INTO EACH INTERSECTING MEMBER PERIMETE FRAMING YEBOLT FOR ABLETENSION 1/8" STAINLESS STEEL BRAIDED CABLE DETAIL "I-2" CABLE CONNECTION AT CORNER SCALE: NTS 40" MIN. 60' MAX. 4" MIN. SLAE w/FOOTING 40' MIN. 60' MAX. 1W STAINLESS STEEL BRAIDED CABLE 1 3/8" DIA x3" EMBED CONIC. SCREW ANCHOR (TAPCON OR EQUAL) 3WO PSI CONIC. 6x6-10A0 W WM OR FIBERMESH 1 n 4" MIN. SLAB/ 1.5"x5.5"ALUM. STRAP w/FOOTING WI(2) 1/4" DIA x 2-1W MASONRYANCHOR (TAPCON OR EQUAL) DETAIL "I-1" CABLE CONNECTION AT FOUNDATION SCALE: NTS 3000 PSI CONC. 6x6-10x10 W WM OR FIBERMESH J QD J rn (D Im� r c. Z Z O LL p U Lu 0 05 —, W < LL Ln "c Z —F-LLMa) r (D Z O�c' W Q .J N j OLo LL DO O 'IT M 00 T O Z U W O IL 0 J J Z J W W LL K w LU LL U) LL N Of W o Z LU F d ~ Z O Q ~i (0 OtOO 0 w IL N LL DATE: 12/10/2018 N1: DATE PAGE: N 2: DATE NTS 1 1/4" 3/16" 5052-H32 GUSSET 2" X PURLINS ATTACH TO H MIN (4) #10 X 1 1/2" SMS WASHER-UNDERSCREW IN GUSSET CORNER 2"X2"X7/8" ANGLE X 4" LONG PROVIDE #14 X 1" INTO EACH MEMBER AS INDICATED BELOW PROVIDE INTERIOR ANGLE ABOVE AND BELOW CHAIRRAIL EXTERIOR CORNER POST x2x #14 SMS @ 1 1/4" O.C. a y iye�5�m 2 NOTES: 1. GUSSET DIMENSION ARE MINIMUM REQ'D (1) EA SIDE OF BEAM - MAYBE INTERNAL OR EXTERNAL 2. AS BEAM SIZE CHANGES, ADD OR SUBTRACT SCREWS TO MAINTAIN 1-1/4" C/C SPACING 3. GUSSET LENGTHS REMAIN CONSTANT WIDTHS CHANGE TO MATCH BEAM SIZE. RAIL Vx2"O.B. PATIO SECTION 3" x 3" x 0.050" MIN., 6063-T6 ALLOY PLATE DR STRONGER (ONE SIDE) WITH (3)-#12 x 3/4" S.M.S. EACH SIDE AS 10WN (3/8" MIN. PLATE EDGE DISTANCE & C-C FASTENER SPACING) LATERAL "W'-BRACING CONNECTION DETAILS K-BRACE GUSSET PLATE PER E-SERIES 3" x 2" x 0.050" MIN., 6063-T6 ALLOY PLATE DR STRONGER (ONE SIDE) (3) - #12 x 3/4" S.M.S., EACH SIDE AS SHOWN (1/2" MIN. PLATE EDGE DISTANCE 8 C-C FASTENER SPACING) V X 2" O.B. FASTENED TO CORNER "ANGLE POST W/ 912 X 1 112" SMS AT 6" FROM TOP 8 BOTTOM RAILS TYPICALLY @ 24" O.C. 11" INTO EACH - _ 1/8"DICATED.BELOW___ X X 2" EXTRUDE ANGLE 5052 _ _ _ _ _ 14 H-32 ALLOY EA CORNERW!(2)#14 X2" H-3 L CORNER POST I�I SMS INTO POST 8 (1) 3/8" DIA CONCRETE SCREWANCHOR INTO 6" CONCRETE DETAIL #2 M (2) #1O X 1 1/2" THRU SCREW BO: SLAB/FOOTING NOTES: SEE PLAN 1. CONNECTION DETAIL AT EAVE RAIL SIMILAR SELF MATING BEAM CONTRACTOR TO INSTALL (2) #14 X 2" SMS THRU BRACE INTO BEAM THRU GUSSET PLATE CORNERPOST Tx 2 x 0.093 BRACE (TXF 3/8" 0 CONCRETE ANCHOR (2 PLATES) FOUNDATION IN LIEU OF TYP. 1/4" 0 CONCRETE SCREWS FOR CORNER COLUMN LATERAL "K"-BRACING CONNECTION DETAILS SIDE VIEW CORNER K-BRACE DETAIL SCALE: N.T.S. (4)#14 X3. INTI 1" X 2" BASE PLATE ANCHORED TO CONC W/ 1/4" CONCRETE SCREW ANCHOR (MIN. 1 1/4" EMBED) 6" MAX EACH SIDE OF POST AND 24" O.C. MAX 'OST W/ 1"X 2" @ 3TH AS REQUIRED EMBED CONCRETE CHOR INTO FRONT VIEW CP-1 CORNER POST TO CONCRETE DETAIL AFL SCALE: NTS 6" x 5" x 0.050" COLUMN 6063-T6 ALLOY PLATE ���\\\ (ONE SIDE)OR STRONGER \ 2x2x0.093 \ BRACE (fYP.) K-BRACE ----� 2 x 3 x 0.070 CHAIR RAIL p `. I p O \ O O O GIRT (CHAIR RAIL) K-BRACE O 2x2xO.093 BRACE(TYP.) (11 TOTAL)-#12 x 314" S.M.S. AS SHOWN (1/2" MIN. PLATE EDGE DISTANCE & LATERAL "W'-BRACING C-C FASTENER SPACING) CONNECTION DETAILS N O O Bl a 00 0 N - N O a 'H N 0. .y m LU LU J m Coo J M Ur co ZZo 0 U n/ LL D� p U W J OCo W < LL Lo .0 Z w m a> Z O W< —j F q'r J O_ LL U J J 2 W W W' U w W W z O 91 DESIGN DATE: REVISION 1: REVISION 2: O Z F- U w O atf IL � J 0 LL w WLu U LL of 2W F Od U �,od O(o0 LL N LL 12/10/2018 DATELPAgGE:DATE NTS