HomeMy WebLinkAboutEVALUATION REPORTSFILE COPY EXTERIOR RESEARCH th DESIGN, LLC. Certificate of Authorization N9503 353 CHRISTIAN STREET, UNIT #13 TRINITY pERD OXFORD, CT 06478 RECEIVED (203) 262-9245 EVALUATION REPORT Boral Roofing DEC I ' G Evaluation Report M35710.12.10-R9 FL14317-RS 7575 Irvine Center Drive, Suite 100 permitting Irvine, CA. 92618 Lucie County, Date of Issuance:12/21/2010 Revision 9:10/14/2017 (602)269-2288 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 61h Edition (2017) Florida Building Code SCANNED sections noted herein. BY DESCRIPTION: Boral Roof Underlayments St. Lucie County LABELING: labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. Trinityl ERD requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words 'Trinity I ERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 7. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCA ANE7983 The facsimile seal appearing was authorized by Robert Nieminen, P.E. on 1011412017. This does notser"e as an elecu4nitally signed document. CERTIFICATION OF INDEPENDENCE: 1. Trinity ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. Trinity ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest In any other entity involved in the approval process of the product. 5. This is a building code evaluation. Neither Trinity ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was use'permitting or design unless retained specifically for that purpose. t f U (51 ( A) ` RIND ERD ROOFING COMPONENT EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: Boral Roof Underlayments, as marketed by Boral Roofing, have demonstrated compliance with the following sections of the 6N Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Prove rty Standard Year 1504.3.1 Wind Uplift UL1897 2012 1507.1.1, T1507.1.1, 1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSA/TRI April 2012 (04-12) 2012 3. REFERENCES: gntitt Examination Reference Date ERD (TST 6049) Physical Properties M36790.07.11 09/30/2011 ERD (TST 6049) Physical Properties B40380.08.12 08/28/2012 ERD (TST 6049) Tensile Adhesion / LTA C41420.09.12-2 09/11/2012 ERD (TST 6049) Adhesion B41940.09.12 09/13/2012 ERD (TST 6049) Tensile Adhesion / LTA B47390.07.14-1 07/31/2014 ERD (TST 6049) Tensile Adhesion / LTA B47390.09.14 09/04/2014 PRI(TST5878) ASTM D1970 NEI-031-02-02:REV 10/27/2010 PRI (TST 5878) ASTM D1970 NEI-029-02-01:REV 12/03/2010 PRI (TST 5878) Tensile Adhesion / LTA NEI-046-02-01REV 12/17/2010 PRI (TST 5878) FRSA/TRI April 2012 NEI-076-02-01 02/14/2011 PRI (TST 5878) ASTM D1970 NEI-034.02-02 01/29/2013 PRI (TST 5878) Wind Uplift BORR-001-02-01 03/17/2015 PRI (TST 5878) Wind Uplift BORR-COS-02-01 06/24/2015 UL, LLC. (QUA 9625) Quality Assurance Service Confirmation Exp.06/21/2020 4. PRODUCT DESCRIPTION: 4.1 Self -Adhering Underlavments: 4.1.1 Boral TileSealO 50Rr is a nominal50-mil thick, polyester -surfaced, self -adhering SBS modified bitumen roof underlayment; meets ASTM D1970. 4.1.2 Boral rile5eal® w is a nominal 60-mil thick, polyester -surfaced, self -adhering SBS modified bitumen roof underlayment; meets ASTM D1970 and FRSA/TRI 04-12. 4.1.3 GatorSealO is a nominal 55-mil thick, granular -surfaced, fiberglass reinforced, self -adhering SBS modified bitumen roof underlayment; meets ASTM D1970. 4.1.4 Citadel° Plus is a nominal 48-mil thick, fabric -surfaced, fiberglass reinforced, self -adhering SBS modified bitumen roofing underlayment for use as a base -layer in two-ply underlayment systems; meets ASTM D1970. S. LIMITATIONS: 5.1 This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically forthat purpose. 5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions. Exterior Research and Design, LLC. Evaluation Report M35710.1210-R9 Cedii7cote of Authorkadan#9503 6n'EDITION(20171 FBC NON-HVHZ EVALUATION FL14317-RS Boras Roof Underlavments; (602) 269-2288 Revision 9:10/1412027 Page 2 of 7 I N I TY =Ru 5.3 Fire Classification is not part of this Laboratory Report refer to current Approved Roofing Materials Directory for fire ratings of this product 5.4 Soral Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within FBc approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. 5.5 Allowable Roof Covers: Table 1 pertains to use of each listed underlayment by4tself beneath the Stated _ .�..:....-.n.,.;.... ;.,�r�, �,+lnne and Table 2 for two-alv underlayment options. 5.5.1 FOUr cuve;s. nav w����o.+............. TABLE 1: ROOF COVER OPTIONS Underlayment Asphalt Nail -On Tile Adhesive -set Tile Metal Wood Shakes &Shingles Slate Shingles Boral TileSeal 50"r Yes No No Yes Yes Yes Boral TiieSeal"r Yes Yes Yes (See 5.5.1) Yes Yes Yes GatorSeal Yes No - No No . Yes yes .AAt,_.:...._ee. T.1 ��;e11.it>,it�.mp of fnllnwine AODfOVedtile adhesives/ underlayment combinations. ,,.,,,eslve—..1.. is., ...... __----------- .. 1 TABLE IA-ALLOWABLETI EADHESIVE/ UNDERLAYMENTCOMBINATIONS Adhesive Florida Product Approval Underlayments uch'n Seal StormBond Roof Tile Adhesive FU4506 Boral TileSeal"r rDowTILEND -Roof Tile Adhesive FL22525 BoralTileSeal"rs Poiyset° AH-160 FL6332 Bo21 TileSeal"rs Polyset° RTA-1 FL6276 Boral TileSeal"r 5.6 Allowable Substrates: 5.6.1 Direct -Bond to Deck: Citadel Plus, Boral TileSeal 50', Boral TileSealw or GatorSeal: > Plywood (unprimed or primed with ASTM D41 primer). Boral TileSeal"r: O5B primed with ASTM D41 primer. Note: Refer to Section 5.6.4 for uplift limitations associated with direct -deck underlayment installations where the overlying roof cover is adhesive -set file roofing 5.6.2 Bond to Base Laver Underlavment: Citadel Plus, Boral TileSeal 50"t, Baral TileSeal"' or GatorSeal: > ASTM D226, Type II felt; Citadel Plus. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under adhesive -set tile systems, base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in accordance with FBC 1504.3.1. I' Refer to rile Manufacturers or Adhesive Manufacturer's Florida Product APPmvolfor Overturning Moment Resistance performance Exterior Research and Oeslgn, LLG Evaluation Report M35710.12.10-R9 Ceruffmte GfAuthvmcdan V9503 O'EDMON(Z017)FBC NON-HVHZ EVALUATION FL14317-RS Boral Roof Underlayments; (602) 269-2288 Revision 9:1011412017 Page 3 of 7 1 RNMI ERD 5.6.3 Bond to Other Substrate Tvoes: Citadel Plus, Boral Tlle5e2150"n, Boral TileSealm or GatorSeal: 9 ASTM D41 primed metal (e.g., flashing metal, valley metal, etc). Boral TileSeal .. Huber Zip Deck (unprimed or primed with ASTM D41 primer); Dens Deck Prime. Note: For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. 5.6.4 Wind Resistance for Underlavment Systems in Adhesive -set Tile Applications- FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath adhesive -set tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not addressed in FRSA/TRI April 203.2 (04-12) and are used in adhesive -set tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-12), Appendix A, Table 1A or FBC 1609 for determination of design wind loads #1 Maximum Design Pressure = -105 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Ply: (Optional) Citadel Plus, self -adhered Underlayment: Boral TileSealn self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x 1%" ring shank nails through 32ga.,1-5/8" diameter tin caps spaced 12-inch o.c. 92 Maximum Design Pressure=-120.0 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: ASTM D41 to the plywood deck Base Ply: Citadel Plus, self -adhered Cap Sheet: Boral TileSealn self -adhered, and back -nailed within the selvedge -edge side laps using 12 ga. x 1%" ring shank nails through 32 ga,1-5/8" diameter tin caps spaced 12-inch o.c. #3 Maximum Design Pressure=-202.5 Dsf Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: ASTM D41 to the plywood deck Base Ply: None Cap Sheet: Boral TileSealm, self -adhered, and back -nailed within the selvedge -edge side laps using 12 ga. x 1Y" ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c. #4 Maximum Design Pressure = -120.0 Bsf: Deck: Min. 2,500 psi structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: ASTM D41 to the concrete deck Base Ply: (Optional) Citadel Plus, self -adhered Cap Sheet: Boral TileSealn self -adhered 5.6.4.1 Note: For adhesive -set tile systems, if there is a base ply or mid -ply of Citadel Plus in the system, the project design pressure requirements may not exceed -120 psf. Exteriar Research and Design, U.C. Evaluation Report M35710.12.30-119 Certlfimteafaut6arimdm 99503 6" EDITION (2017) FBC NON-HVRZ EVALUATION FL34317-118 floral Roof Underlayments, (602) 269-2288 Reuislon 9: 10/14/2017 Page 4 of 7 5.7 Ettposuie, Li�itatio°sc GatorSeal shall not be left exposed for longer than 30-days after installation, prior to placement of final roof cover. "r BoraileSealn shall not he left exposed for longer than 180•days after Boral TileSeal 50and l T installation, prior to placement of final roof cover.underla ment system, shall not be left exposed for longer Citadel Pius, for use as a base -layer in a two-ply Y . than 180-days after Installation, prior to placement of subsequent underlayment layer. 5_8 Tile Sliapa¢e Limitations [FRSA/TRI April 2012 (04-1211: When loading roof tiles on the underlayment in oirect-deek rile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. - — - Tile Profile �Wb="'� --- - 6:12 Underlayment I Max ck Flat � �� I 612 Boral TileSeaF ;; L..ed I Max. 20t0e scat 6. INSTALLATION: published installation 6.1 Barai Roof Underlayments shall be installed in accordance n and the Boral thespecifics noted below. Roofing p instructions subject to the Limitations set forth in Section 5 herein a 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). 6.3 Install self -adhering underlayment when ambient and surface temperatures are minimum 40`F and rising. 6.4 Citadel Plus: 6.4.1 Citadel plus is limited to use as a base or mid -layer in multi -ply underlayment systems beneath Bora TileSeal 50"r, Boral TileSeal xr or GatorSeal. 6.4.2 Slope limitations arethoseassociated withthetop-layerunderlayment. 6.4.3 Direct to Deck: (call 10 to 12 ft. Align the membrane parallel to the roof Cut the membrane into manageable lengths, typically ge onto itself, Remove the release sedge, eing over by Y.4rich. Fold the membrane away from the heet. PI ce the membrane with the exposed rubberized asphalt onto the the deck, pressing firmly into place. Rail into place with a weighted roller. Boral recommends fastening of the top edge of the sheet to the Beckwith roofing nails, nails i tin -tags or 1-inch diameter plastic or steel cap nails spaced 24-inch o.c. for slopes below 7:12 an and minimum 4'r slopes 7:12 and greater. Overlap successive courses MI 2 inches (horizontal lap) end (vertical) laps. Install final underlayment layer atop Citadel Plus per'direct-to-decle instructions for Boral TileSeal 50K, Boral TleSeal"r or GatorSeal. 6.4.4 To Base Sheet: install base sheet of ASTM D226, Type 11 felt in accordance with Code requirements or install base ply o Citadel Plus in accordance with Boral Roofing published installation instructions and Section 6-4.3 and when used as part of a multi -ply system. published installation install optional Citadel Plus as a mid -ply in accordance with Boral Roofing instructions and Section 6.4.3. atop Citadel Plus per 'direct -to deck instructions for Boral TileSeal 50 , Install final underlayment layer Boral TileSeaF or GatorSeal. Evaluation Report M357 9 FL74317--R Exterior Research and Design, LLe rn'E lRrae EVALUATION Revision 9: 10/14/2017 @dflmte ofAuthododoa=9503 Bomi RoofUnderlayments;(602[269-2298 Page 5 of 7 TFUNIFY7 ER. Note: For adhesive -set tile systems, if there is a base ply or mid -ply of Citadel Plus in the system, the project design pressure requirements may not exceed -120 psf. 6 5 Boral TileSeal SO"r 6.5.1 Shall be installed in compliance with the requirements for ASTM D197O undedayment in FFit. ladle 1507.1.1 for the type of prepared roof covering to be installed. 6.5.2 Do not use Boral TileSeal 50"r on roof, pitches less than 2:12. 6.5.3 Non -Tile Aoolications Directto Deck: Cut the membrane into manageable lengths, typially 10 dt m 12 ft. Align the membrane parallel h the roof rn the ge onto itself. Remove e release dge, extending over by Y.-Inch. Fold the membrane away fro sh et Place the membrane with the exposed rubberized asphalt onto the deck, pressing firmlyinto place. Roll into place with a weighted roller. Boral recommends fastening of the black selvedge edge to the deck with roofing nails, nails &tin -tags or f- inch diameter plastic or steel cap nails spaced 24-inch o.c. for slopes below 7.12 and 12-inch o.c- for slopes 7:12 and greater. Overlap successive courses the width of the black -selvedge area, minimum 34nch. Seal under end (vertical) laps using approved mastic, or use Joined and Folded Seam or Inverted Sheet Seam method detailed in Boral Roofing published installation instructions. 6.5.4 Non Tile Aoalications to Base Sheet: Install ASTM D226, Type it felt in accordance with Code requirements or install Citadel Plus in accordance with Boral Roofing published installation instructions and Section 6.4. Install Boral TileSeal Se in accordance over ASTM D226, Type II felt or Citadel Plus with Boral Roofing published installation instructions and Section 6.5.3, except end (vertical) laps, described below. Apply SBS Mastic under all end (venial) laps or any other laps where the self -adhering bituminous underside is in contact with the fabric top surface, rolling the interface into place with a weighted roller. 6.6 Gatrseal: 6.6.1 Shall be installed in compliance with the requirements for ASTM D197O undedayment in FBC Table 1507.1 1 for the type of prepared roof covering to be installed. 6.6.2 Do not use GatorSeal on roof pitches less than 2.12. 6.6.3 Non -Tile aoolications Direct to Deck: Cut' he membrane into manageable lengths, typically 10 to 12 ft. Align the membrane parallel h the roof edge onto itself. Remove the release edge, extending over by %-inch. Fold the membrane away from the sheet. Place the membrane with the exposed rubberized asphalt onto the deck, pressing firmly into place. Roll into place with a weighted roller. Boral recommends fastening of the black selvedge edge to the deck with roofing nails, nails & tin -tags or inch diameter plastic or steel o nails spaced 24-inch o.c. for slopes below 7:12 and 12-inch o.c for slopes cap 7:12 and greater. Overlap successive courses the width of the black -selvedge area, minimum 34nch. Seal end (vertical) laps using SBS Mastic under all side (vertical) laps or any other laps where the self - adhering bituminous underside is in contact with the granular or mineral top surface, rolling the interface into place with a weighted roller, or using the Inverted Sheet Seam detailed in Boral Roofing published installation instructions. 6.6.4 Non -Tile AODliati0ns. to Base Sheet: Install ASTM D226, Type 11 felt in accordance with Code requirements or install Citadel Plus in accordance with Boral Roofing published installation instructions and Section 6.4. Install GatorSeal over ASTM 0726, Type II felt or Citadel Plus in accordance with Boral Roofing published installation instructions and Section 6.6.3 except end (vertical) laps, described below. Apply SBS Mastic under all side (vertical) laps or any other laps where the self -adhering bituminous underside is in contact with the granular top surface, rolling the interface into place with a weighted roller. Evaluation Report M35710.32.30'R9 E,derlor Research and Design, LLG FL4317-RR eertlfmrenluurharizntlnn a9503 5o'EDnTON 12017)FRCiVOIvLRVHZ EVALUATIONRevision 9: 10/14/2017 Boni Roof Underiaymenm, j602) 269-2289 Page 6 of 7 6.7 Boral illeSealRr: q p1970 underlaymenY in FBC Table 6.7.1 shall Be installed in compliance with the re requirements for ASTM 1507.1.1 for the type of prepared roof covering to be installed. 6.7.2 Do not use Boral i ileSeal `r` on roof pitches less than 2:12. 6.7.3 Non -Tile A lications Direct to Deck: extending For OSB substrate, prime with ASTNI D41 primer and allow to dry Prior to installation- toatien. Cut the membrane into manageable lengths, typically le to 12 ft. Align the membrane Remove to the roof edge, over by'/ -inch. Fold the membrane away from the edge onto itself. Remove the release sheet Place the membrane with the exposed rubberized asphalt onto the deck, pressing firmly into place_ Roll into place with a weighted roller. Boral recommends fastening of the black selvedge edge to the deck with roofing nails, nails & tin tags or I - minimum 3-inch. inch diameter plastic or steel rap nails spaced 244nch o.c. for slopes below 7:12 and 12-inch o.c. for slopes 7:12 and greater. Overlap successive courses the widthof usethe loined and Folded ck-selvedge area'seam or Inverted Sheet seal under end (vertical) laps using approved mastic, Seam method detailed in Boral Roofing published installation instructions. 6.7.4 Non -Tile A olications.toBaseSheet: with Code requirements or install Citadel Plus in accordance Install ASTM D226, Type 11 felt in accordance With BoraI Roofing published installation instructions and Section 6.4. Install Boral TileSeal 'R over ASTM D226, Type II felt or Citadel Plus in accordance with w- Roofing published installation instructions and section 6.7.3, except end (vertical) laps, described below. Aply SBS Mastic under ) laps or any other laps the under de. is in contact withlthe fabric top l end (surface, rolling the interface, nhere to place with a weightedltro➢er- 6.7.5 Tile APPlications using the Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, instructions noted above as a guideline. For mechanically fastened file roofing over 2-ply system, consisting of Base SheetTable 1. self -adhering toP sheet(s), Base Sheet fastening shall be not less than FRS A/TRI April 2012 (84-12), For adhesive -set tile applications, refer to Section 5.6.4 herein. of Citadel Plus in the system, the Note: For adhesive -set the systems, if there is a base ply or mid-piy project design pressure requirements may not exceed -120 psi. Refer to Section 5.8 for the staging limitations. Battens must be used for all file installations atop Boer Refer t Rr with roof pitches to 2%: to less than 3:12. Boral Roofings Elevated Batten system or counter TileS battens are required_ 7, BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation o this product. 8. MANUFACTURING PLANTS: Brentwood, NH 9, QUALITY ASSURANCE ENTITY: UL, LLC. — QUA9625; (631) 546-2458; 1(anchi.AP.rawa-1a_ I]ol_ ania�ul.com -END OF EVALUATION REPORT - E.terlar leesearch and pozign; LLG 6... EDOON(20171 FHC Ilow-44VFR-EVALU�:'na�h [ertifmte ofAUMoriradon a95P3 8oral Roof UnderlaymeoM 1602)269.2288 Evaluattan Report M357 Fu4317-RB Page of