Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
Client: Ryan Homes
1450 Centrepark Blvd Suite 340 SCANNED
West Palm Beach, FL 33401 BY
Project: Oakland Lake Subdivision Lot 60 St. Lucie County
5271 Oakland Lake Circle Permit 02 , Ft. Pierce; St. Lucie County, FL
As requested, Universal Engineering Sciences, Inc. (LIES) representative(s) performed construction materials testing and/or
field inspection services on the above project. 'Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No. Date Type of Report
105834-1 01/17/2019 In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
RECEIVED
MAR 18 2019
L
6eEla seantp5 P@YtH1ENfiq
Sincerely, ,,, ;
Universal -Engineering Sciences, Inc.
Certificate of Authorization Nv.-00000549
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
ICC Email: cbugg@nvrinc.com; rhager@nvrinc.com; signtseal MAIL to ryan homes at 5369 Oakland Lake, Vero Beach, FL 32966
UES Project No: 0310.1700251.0039
U N' V f -� I �' � A 1- UES Report No: 105834 1 ARC 011719
ENGINEERING SCIENCES On -Site Time (hrs): 0.60
Consultants In: Geotechnical Engineering • Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services • Materials Testing • Threshold Inspection Travel Time (hrs): 0.25
91 Building Code Administration, Compliance Inspection&Plan Review Total Time (hrs): 0.75
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 60
5271 Oakland Lake Circle Permit 1812-0284, Ft. Pierce, St. Lucie County, FL
Date of Activity: Thursday, 17 January, 2019
Technician: Timothy Hughes
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the house pad.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for house
pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing -Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820'Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
In -Place Density Test Report
UES Project No: 0310.1700251.0039
LIES DOCS No:
LIES Report No: 105834-1 DT 011719
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 60
5271 Oakland Lake Circle Permit 1812-0284, Ft. Pierce, St. Lucie County, FL
Area Tested: house pad
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 01/17/2019
Lab: ASTM D1557 Modified Proctor
Technician: Timothy Hughes
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the' underlvina soils helnw the tpstpd rienths
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1
NE corner of pad
0 to -1 ft
12.00
21143
112.0
3.8
97 ,
A'
2
NW corner of pad
0 to -1 ft
12.00
21143
112.2
5.3
98
A
3
SW corner of pad
0 to -1 ft
12.00
21143
111.4
5.0
97
A
4
SE comer of pad
0 to -1 ft
12.00
21143
109.8
4.7
95
A
t'l KeT. uatum: U = I op of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21143
115.0
12.0
This test was perionned without deviation from ASTM procedures.
(3) Comments Key
A. Compaction meets min, requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
..L
UNIVeRSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering s Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
/g/2— 0-2V_T
UES P• : 0 170 9
UES Re ortLIES D % 4- �
On -Site Time (hrs): 0.50
Lab Time (hrs): 0.00
Travel Time (hrs): 0.25
Total Time (hrs): 0.75
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 60
5271 Oakland Lake Circle Permit 128`4�Ft. Pierce, St. Lucie County, FL
Date of Activity: Thursday, 17 January, 2019
Technician: Timothy Hughes
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the house pad.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for house
pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were -found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
RIr
F`3 15 20i9
Permitting
St. Lucie
Department
countyI FL
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
•
UES Project No: 0310.1700251.0039
UES DOCS No:
UES Report No: 105834-1 DT 011719
In -Place Density Test Report
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 60
5271 Oakland Lake Circle Permit 1812-0284, Ft. Pierce, St. Lucie County, FL
Area Tested: house pad
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 01/17/2019
Lab: ASTM D1557 Modified Proctor
Technician: Timothy Hughes
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
nnly and do not address the condition of the underlvino soils below the tested depths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1
NE corner of pad
0 to -1 ft
12.00
21143
112.0
3.8
97
A
2
NW corner of pad
0 to -1 ft
12.00
21143
112.2
5.3
98
A
3
SW corner of pad
0 to -1 ft
12.00
21143
111.4
5.0
97
A
4
SE corner of pad
0 to -1 ft
12.00
21143
109.8
4.7
95
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21143
115.0
12.0
This test was performed without deviation from ASTM procedures.
(;s) t:ommenis trey
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing •Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32956 - P: 321.638.0808 - F: 321.638.0978
LIES Project No.:
Date Typed:
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 60
5271 Oakland Lake Circle Permit 1812-0284, Ft. Pierce, St. Lucie County, FL
0310.1700251.0039
February 07,2019
As requested, Universal Engineering Sciences, Inc. (LIES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observationsare reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No. Data Type of Report
105834-1 01/17/2019 In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
Sincerely,
Universal Engineering Sciences, Inc.
Certificate of Authorization No. 00000549
Z
Richard E.
• ��cE,vSF'
Hoaglin, P.E.
,��%�
IVY2019.02.07
48796
12:59:37
s:TAT�:o.�.
-05,00,
• C A ��
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796